Chapter 12 OSP Flashcards

1
Q

When sizing Underground Entrance Conduits, a minimum of ________ should be specified.

A

(4) 103 metric (4 trade size)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

One spare _______ conduit should be considered for each ______________.

A

4 trade size
Telecommunications service entrance point

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

OSP allowed fill ratio

A

N/a

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Innerducts

A

Used to maximize amount of cable that can be placed in an underground OSP pathway

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Innerduct requirements

A

Each should be equipped with a pull cord/tape

Copper conductor should be installed within the conduit system for locating purposes when non-metallic fiber is installed

In compartmentalized innerducts, a pull cord should be in each

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Additional OSP conduits could be required to meet other needs such as

A

Separation of services including:
Video
Tie cables
Dual feeds for diverse paths/redundancy
Secure circuits w/ sensitive info
Misc. circuits (fire, security)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Terminating space must have plywood backboard sized according to the

A

space served

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

A building larger than 100k sq. Ft must contain a dedicated room for EF. The size of the room is determined by:

Door requirements:

A

Type of facility
Terminating hardware selected
Neccessity for electrical protection

Open outward
Lockable with access control
Have same fire rating as room
Min. Size of 3’x6.5’

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

EF conduit entering design specs

A

4” from wall
4” above floor
4” below ceiling

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Intrabuilding vs EF penetration/ conduit sizing

A

EF = 4”
Intrabuilding = 1-3”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Main considerations when designing an aerial entrance

A

Proper clearance and separation from power lines

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Unground conduit minimum depth

A

24”

Or below the 50 year frost line where frost can damage cable

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Encase underground conduit in concrete when

A

Min depth cant be attained
Conduits pass under roads, driveways, or tracks
Bend points might be subject to movement
Directed by owner

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Shoring requirements for trench 5’ or more deep

A

Be shored to prevent cave in
Have a minimum clearance of 24” from edge of excavation dirt pile to the nearest edge of trench

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Minimum separation between telecom conduits and other foreign/power conduit in a joint trench

A

3” of concrete
4” of masonry
Or 12” of well tamped earth

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Minimum separation between telecom conduits and street railways in a joint trench

A

1m or 3.28’

17
Q

Minimum separation between telecom conduits and railroads in a joint trench

A

50” below top of rail