CEC questions Flashcards
What are the CSA designations of the following
Non-conductive
Conductive
Non-conductive → OFNP
Conductive → OFCR
What is the minimum clearance required between communication equipment and electrical equipment?
900mm
What section in the CEC would you find the rules for Conductors for a Class 2 power and Data Circuits?
section 16
What CSA type designations communication cables may be substituted for FT4?
CMP
CMR
FT6
What is the allowable ampacity for a 24 awg, 75 ºC, 8 conductor Class 2 power and Data circuit, when using only 4 conductors and bundled with 1 other cable?
1.96 amps
What is the area in square inches of a 27 mm EMT?
0.8355in²
Is the Multiplying factor of 1.4, for ampacity, used when only using 4 of the 8 conductors for Class 2 power and data Communication circuits?
True
What are the CSA type designations for communication cables?
CMP
CMR
Rule 2-130 applies to the installation of fire stopping material.
false
What is the imperial (in feet) equivalent of 30 meters?
98.43 ft
What Table in the CEC refers to the Allowable Ampacity for Copper, Eight Conductor, Class 2 power and data Communication Circuit cables (PoE)?
Table 60
What are the basic types of optical fiber cables as described by the CEC?
Conductive,
Non-conductive,
Hybrid
What CEC rules apply when installing communication systems conductors in a plenum? Please select one or more
12-010
12-100,
2-130,
60-314
What must be done to the metallic members of a conductive optical fiber cable as it enters the building?
Grounded as close as possible to the point of cable entry
What is the minimum distance required between the top of a cable tray and the ceiling?
300mm