conduit fill Flashcards
What size EMT is required to install a 2.225 inch diameter cable?
3” EMT
Can 3 x 1.574” OD cables be installed in a 4” ID circular pathway, as per the CEC?
False
What is the area (in inches²) of a circle 2.32” in diameter?
4.2273 in²
What is the area (in mm²) of a circle 37mm in diameter?
1075.21 mm
What size EMT is required to install the following cables?
12 x 0.278” diameter cables
12 x 0.5 cm radius cables
63 trade size EMT
Is 1” ID circular pathway be sufficient to install 0.369” radius cables?
False
How many cables with a radius of 0.188 inches may be installed in a 41 trade size EMT?
7
What size EMT is required to install a 0.35 inch diameter cable and a 0.27 inch diameter cable?
21 trade size EMT
What is the area (in mm²) of a circle that would fit in a square opening with the dimensions of 8.6 cm x 8.6 cm?
5808.8 mm²
Calculate (using CEC table 9I) the maximum allowable number of 0.18” diameter cables that may be installed in a 2” EMT.
51
What is the minimum allowable size (in inches) EMT required to serve a workstation with 2 x 0.27” diameter cables, 1 x 0.285” diameter cable and 1 x 0.24” diameter cable?
27
What is the minimum allowable size (in trade size) of a zone conduit to serve an area that has 12 WAs(Work Areas) each configured with 2 x 0.27” diameter cables, 1 x 0.285” diameter cable and 1 x 0.24” diameter cable?
78
Calculate the maximum allowable number of 0.18” diameter cables that may be installed in a 2” ID innerduct.
49
What is the cross sectional area (in mm²) of 12 x 4 mm diameter cables and 7 x 0.12” radius cables?
355.1 mm²
What is the minimum allowable size EMT(in trade size) required to install 20 x 0.25” diameter cables?
53