BISCI chapter 4 Flashcards
How much spaces does a Rack Unit (RU) occupy?
1.75 inches
What is the purpose of an EF?
To contain the transition point for access providers to the building
What may be done to reduce EMI radiating into telecommunication cabling?
Keep electrical circuits separate from communication pathways
What is the minimum vertical distance recommended between a cable tray in the ceiling and a celling tile?
3 inches
Select the installation limitations of a conduit system used for horizontal cabling before a box or fitting is installed.
Maximum 90 degree bends - 2
Maximum length - 30m
1-1/4 inch EMT is the largest size that may be formed using a hand bender.
True
What is the minimum and maximum distances J-hooks may be installed?
min 4 feet
max 5 feet
An antioxidant compound should be applied to the bare metal of the cabinet or rack and the equipment bonding conductor lug surface before the lug is bolted to the cabinet or rack
True
What are the 2 popular sizes of rack mounting screws
12-24 10-32