A pressure-actuated refrigeration control cannot be used in conjunction with a/an _____ expansion valve
Select one:
A. Thermostatic
B. Solenoid
C. Automatic
D. Hand
E. Humidity
C. Automatic
In the event of a low oil pressure condition, the oil pressure failure switch will:
Select one:
A. Sound an audible alarm
B. Open the recycle valve to take the load off the compressor
C. Stop the flow of refrigerant to the system
D. Shutdown the compressor
E. Stop the air circulation fan
D. Shutdown the compressor
The thermostatic refrigeration controller has a range adjustment that sets the temperature level at which the:
Select one:
A. Fan starts and stops
B. Condenser cooling water control activates
C. Level in the evaporator control activates
D. Cut-in and cut-out occurs
E. Expansion valve opens and closes
D. Cut-in and cut-out occurs
Motor overload protection is a manual reset device that will take the motor itself offline when the current drawn by the motor exceeds:
Select one:
A. Its minimum allowable value
B. The condenser maximum allowable pressure
C. The evaporator maximum allowable temperature
D. Its maximum allowable oil temperature
E. Its maximum allowable value
E. Its maximum allowable value
The high-pressure safety cutout protects the refrigerating system from higher than normal pressures due to the:
Select one:
A. Presence of refrigerants in the system
B. Presence of non-condensables in evaporator
C. High compressor oil pressure
D. Loss of refrigerant
E. Presence of non-condensables in the system
E. Presence of non-condensables in the system
Flow switches are used on chilled water and cooling water lines and air ducts are used as _____ switches.
Select one:
A. Evaporator level control
B. Safety lockout
C. Low temperature lockout
D. Over pressure lockout
E. Condenser pressure control
B. Safety lockout
The condenser automatic cooling water regulating valve is operated by the:
Select one:
A. Liquid pressure on the compressor suction
B. Vapour pressure on the compressor suction
C. Vapour pressure on the evaporator discharge
D. Liquid pressure on the compressor discharge
E. Vapour pressure on the compressor discharge
E. Vapour pressure on the compressor discharge
One of the three distinct classes of refrigeration controls is the _____ control.
Select one:
A. Solenoid
B. Cooling water regulating
C. Limiting and safety
D. Condenser fan
E. Humidity actuated
C. Limiting and safety
The sensing device of a humidistat may consist of a/an _____ element.
Select one:
A. Pneumatic
B. Hydrophobic
C. Hydroponic
D. Hydroscopic
E. Hygroscopic
E. Hygroscopic
The operation of the compressor (starting, stopping, and unloading) may be accomplished by a _____ type of actuated control.
Select one:
A. Temperature
B. Volume Humidity
C. Mass
D. Density
E. Level
A. Temperature
The thermostatic refrigeration controller has a differential adjustment that sets the temperature at which the:
Select one:
A. Level in the evaporator control activates
B. Condenser cooling water control activates
C. Cut-in and cut-out occurs
D. Fan starts and stops
E. Expansion valve opens and closes
C. Cut-in and cut-out occurs
The CSA B52 Mechanical Refrigeration Code requires that the pressure limiting device be designed to stop the action of the compressor or generator at a pressure not more than _____ of the system high side design pressure.
Select one:
A. 80%
B. 100%
C. 70%
D. 90%
E. 60%
D. 90%
The operation of the compressor (starting, stopping, and unloading) may be accomplished by a _____ type of actuated control.
Select one:
A. Density
B. Volume Humidity
C. Level
D. Pressure
E. Mass
D. Pressure
The thermostatic refrigeration controller produces mechanical when subjected to _____ fluctuations in the cooled medium.
Select one:
A. Humidity
B. Electrical
C. Pressure
D. Electronic
E. Temperature
E. Temperature
The high oil temperature cutout is a safety control that shuts down the compressor when the lubricating oil temperature becomes too high due to:
Select one:
A. Loss of refrigerant
B. Condenser high pressure
C. Evaporator high temperature
D. Loss of oil cooling
E. Condenser high temperature
D. Loss of oil cooling