Book 1: 3-11 "Basic Boiler Operation" Flashcards
Basic Boiler Operation
If boiler water level has dropped below the gauge glass during boiler operation, the operator is to:
Select one:
A. Slowly reduce the boiler load
B. Immediately restore water level before shutting off the unit
C. Contact the boiler inspector immediately
D. Shut down, cool, and then inspect the boiler for damage before refilling
E. Open the blowdown valves in order to have the low water fuel cut-off trip the unit
D. Shut down, cool, and then inspect the boiler for damage before refilling
When removing a hot water boiler from service open the blow-off or drain valve on the bottom of the boiler to remove any sediment that may have collected stopping when the:
Select one:
A. Low water level alarm sounds
B. Water runs clear
C. Boiler is empty
D. Low water fuel cutoff activates
E. Water level drops below the gauge glass
B. Water runs clear
Reduced heat transfer through the heating surfaces can be caused by:
Select one:
A. Over firing
B. Proper water treatment
C. Soot deposits on the waterside
D. Sludge deposits on the fireside
E. Improper water treatment
E. Improper water treatment
When doing routine checks on a heating system one thing which is often overlooked is:
Select one:
A. System pressure
B. Expansion tank level
C. Fuel pressure
D. Unusual noises
E. System temperature
D. Unusual noises
Uneven thermal expansion in a firetube boiler occurs between the:
1. Fire tubes
2. Water tubes
3. Furnace
4. Drum
5. Shell
Select one:
A. 1, 2, 3
B. 1, 3, 5
C. 2, 3, 4
D. 1, 2, 4
E. 3, 4, 5
B. 1, 3, 5
Boiler stack temperature is rising due to soot build-up on the boiler tubes. This could:
Select one:
A. Cause a furnace explosion
B. Result in condensation forming in the flue gas system
C. Result in a pressure explosion
D. Cause the water level to drop to the trip level
E. Cause foaming of the boiler water
A. Cause a furnace explosion
Flame failure may occur during operation due to:
Select one:
A. Insufficient fuel oil supply due to a plugged filter
B. Air in the fuel
C. Excessively high fuel pressure
D. High boiler load
E. Overly high gas pressure
A. Insufficient fuel oil supply due to a plugged filter
During the filling of an empty boiler, a valve that should be open to allow the air to escape is the:
Select one:
A. Gauge glass drain valve
B. Boiler stop valve
C. Gauge glass steam valve
D. Boiler vent valve
E. Boiler drain valve
D. Boiler vent valve
When removing a steam boiler from service, the vent valve should be opened at 15-20 kPa in order to:
Select one:
A. Prevent a vacuum from forming in the boiler
B. Let the O2 within the boiler escape
C. Allow water to drain from the drum
D. Maintain the boiler water level at operating level
E. Permit draining of the boiler while it is still hot
A. Prevent a vacuum from forming in the boiler
When a hot water boiler in a multi-boiler heating plant has the stop valve at the boiler outlet is closed the:
Select one:
A. Bypass valve in the return line of that boiler should be closed
B. Bypass valve in the return line of that boiler should be open
C. Vent valve in the return line of that boiler should be open
D. Stop valve in the return line of that boiler should be open
E. Stop valve in the return line of that boiler should be closed
E. Stop valve in the return line of that boiler should be closed
When a cold oil-fired boiler is started up, the operator may notice that during the first part of the warm-up period the stack will smoke slightly due to:
Select one:
A. The incorrect gas/oil ratio
B. Using the wrong oil
C. The furnace temperature not being high enough to vaporize the incoming fuel oil immediately and completely
D. The oil not being pre heated
E. The incorrect gas/air ratio
C. The furnace temperature not being high enough to vaporize the incoming fuel oil immediately and completely
More severe foaming in steam heating boilers is usually controlled by:
Select one:
A. Decreasing the continuous blowdown
B. Decreasing the intermittent blowdown
C. The use of antifoam chemicals
D. Increasing the continuous blowdown
E. Increasing the intermittent blowdown
E. Increasing the intermittent blowdown
When a cold, gas-fired boiler is started up, condensation (sweating) may occur to such an extent that it appears that the boiler is leaking. What (if anything) should be done to stop this?
Select one:
A. Decrease the firing rate to stop the sweating
B. Decrease the fuel/air ratio to stop the sweating
C. This condensation will stop after the boiler becomes hot
D. Increase the fuel/air ratio to stop the sweating
E. Increase the firing rate to stop the sweating
C. This condensation will stop after the boiler becomes hot
The operating pressure of low-pressure hot water heating boilers varies considerably, it is recommended that the differential between the safety relief valve set pressure and the boiler operating pressure is kept to a minimum of _____ or 25% of the relief valve setting, whichever is greater.
Select one:
A. 3 psi. (20 kPa)
B. 6 psi. (40 kPa)
C. 100 psi. (700 kPa)
D. 15 psi. (100 kPa)
E. 69 kPa (10 psi)
E. 69 kPa (10 psi)
Boiler explosions may be listed under two general classifications:
1. Furnace explosions
2. Smelt water explosions
3. Fuel explosions
4. Pressure explosions
Select one:
A. 2, 4
B. 1, 4
C. 1, 2
D. 2, 3
E. 1, 3
B. 1, 4