Book 1: 2-09 - Boiler Combustion Controls Flashcards

1
Q

The infrared scanner is mounted on the end of a sighting tube in such a way that it’s temperature will not exceed:

A. 50°C (98°F)
B. 100°C (212°F)
C. 120°C (248°F)
D. 75°C (167°F)
E. 150°C (302°F)

A

A. 50°C (98°F)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

The most commonly used flame detection devices are:
1. Ultraviolet detectors
2. Thermocouples
3. Flame rods
4. Infrared detectors
5. Photoelectric cells

Select one:

A. 3,4,5
B. 2,3,4
C. 2,3,5
D. 1,2,3
E. 1,2,4

A

C. 2,3,5

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

If the pilot flame fails, no power is generated by the thermocouple preventing the _____ from supplying fuel to the burner on boiler startup.

Select one:
A. Main fuel control valve
B. Main relay valve
C. Operating control
D. Air supply valve
E. Pilot fuel control valve

A

A. Main fuel control valve

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

With the photoelectric flame scanner upon loss of flame it should take no longer than _____ seconds for the gas valve to close.

Select one:

A. 2
B. 20
C.10
D. 4
E. 15

A

D. 4

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

The voltage supply generated by the thermocouple is usually not more than:

Select one:

A. 0 millivolts
B. 15 millivolts
C. 100 millivolts
D. 50 millivolts
E. 30 millivolts

A

E. 30 millivolts

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

The rectifying photocell, shown in Fig. 10, is also known as a _____ cell.

Select one:

A. IR
B. Cad
C. UV
D. Photoelectric
E. Rectifying

A

B. Cad

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

The time it takes for the automatic pilot valve to close in the event of a flame detection is about _____ seconds

Select one:

A. 15
B. 4
C. 10
D. 20
E. 2

A

C. 10

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

A photoelectric cell reacts to the _____ emitted by the flame.
1. Ultraviolet rays
2. Thermocouples
3. Flame rods
4. Infrared rays

Select one:

A. 1,3
B. 1,4
C. 1,2
D. 2,4
E. 2,3

A

B. 1,4

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

If for any reason, the burner should go out during normal operation, or the fuel should fail to ignite during startup:

Select one:

A. Increase the fuel flow
B. No action is required
C. The air to the burner must be shut off immediately
D. The fuel to the burner must be shut off immediately
E. Increase the combustion air flow

A

D. The fuel to the burner must be shut off immediately

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

When the hot junction of a thermocouple is exposed to heat it’s temperature is higher than that of the cold junction and a small ______ is generated.

Select one:

A. Conductance
B. Resistance
C. Wattage
D. Amperage
E. Voltage

A

E. Voltage

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

A flame rod uses the principle that a flame is capable of:
Select one:

A. Holding the solenoid open
B. Heating the rod
C. Conducting electricity
D. Supplying fuel to the burner
E. Holding the solenoid closed

A

C. Conducting electricity

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

The flame rod method of scanning is often referred to as:
Select one:

A. Ultraviolet detection
B. Infrared detection
C. Photoelectric scanning
D. Flame rectification
E. The ionized particle principle

A

D. Flame rectification

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

The infrared scanner contains a _____ cell which reacts to infrared rays.
Select one:

A. Lithium bromide
B. Sodium chloride
C. Sodium sulphide
D. Lead sulphide
E. Lead sulphate

A

D. Lead sulphide

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

In an oil fired boiler the fuel enters the furnace in a _____ state mixes with combustion air and is ignited.
Select one:

A. Vaporized
B. Gaseous
C. Liquid
D. Mixed
E. Solid

A

A. Vaporized

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Each automatically fired hot water boiler shall have a high limit temperature control that will shut off the fuel supply to the boiler to prevent the water from exceeding the maximum allowable temperature of:
Select one:

A. 150°C (302°F)
B. 120°C (248°F)
C. 200°C (392°F)
D. 75°C (167°F)
E. 100°C (212°F)

A

E. 120°C (248°F)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

The scanner is mounted as close to the flame as physically possible without subjecting it to a temperature over:
Select one:

A. 50°C (98°F)
B. 150°C (302°F)
C. 75°C (167°F)
D. 120°C (248°F)
E. 100°C (212°F)

A

E. 100°C (212°F)

17
Q

A thermocouple consists of two dissimilar wires welded together at one end to form a:
Select one:

A. Cold junction
B. Metering junction
C. Electric circuit
D. Reference junction
E. Hot junction

A

E. Hot junction

18
Q

In a gas fired boiler the fuel enters the furnace in a _____ state mixes with combustion air and is ignited.
Select one:

A. Liquid
B. Solid
C. Gaseous
D. Mixed
E. Vaporized

A

C. Gaseous

19
Q

Unburned fuel collecting in the furnace can mix with the combustion air and may ignite, causing a
Select one:

A. Spike in steam production
B. Boiler drum failure
C. Serious explosion
D. Fire tube failure
E. Water tube explosion

A

C. Serious explosion

20
Q

The infrared scanner is mounted on the end of a sighting tube in such a way that it’s temperature will not exceed:

Select one:

A. 150°C (302°F)
B. 50°C (98°F)
C. 75°C (167°F)
D. 100°C (212°F)
E. 120°C (248°F)

A

B. 50°C (98°F)