The infrared scanner is mounted on the end of a sighting tube in such a way that it’s temperature will not exceed:
Select one:
A. 150°C (302°F)
B. 75°C (167°F)
C. 120°C (248°F)
D. 100°C (212°F)
E. 50°C (98°F)
E. 50°C
This scanner is mounted as close to the flame as physically possible without subjecting it to a temperature over:
Select one:
A. 50°C (98°F)
B. 150°C (302°F)
C. 100°C (212°F)
D. 75°C (167°F)
E. 120°C (248°F)
C. 100°C (212°F)
Damper position switches are found on boilers with the following burner control system:
1. On-Off control
2. High-low control
3. Modulating control
4. High Limit control
Select one:
A. 1,3
B. 1,2
C. 2,3
D. 4,5
E. 3,4
C. 2,3
Quick closing gauge glass valves require _______ turn/s to close.
Select one:
A. 1
B. 1/2
C. 1/4
D. 3
E. 2
C. 1/4
The lock-out switch will be actuated when the:
Select one:
A. Power fails
B. Low water fuel cut off opens
C. Flame scanner loses the flame
D. Operating control opens
E. Operating control closed
C. Flame scanner losses the flame
The low gas pressure cut-off switch can be tested by:
Select one:
A. Closing the main gas valve quickly
B. Slowly raising the boiler pressure above the operating setpoint
C. Quickly closing the main burner shut-off valve
D. Slowly covering the air supply to the fan
E. Slowly closing the main gas valve
E. Slowly closing the main gas valve
If the pilot burner fails to ignite, or if the pilot does go on, the gas burner fails to ignite a lockout switch will be energized after a short trial period of _____ seconds from the time of startup.
Select one:
A. 5 to 10
B. 15 to 30
C. 10 to 20
D. 20 to 40
E. 30 to 50
B. 15 to 30
If the blower starts but stops again after 5-10 seconds:
Select one:
A. Check the low air pressure switch
B. Reset safety lock-out switch
C. Replace motor
D. Close the blower switch
E. Refer to manufacturers manual
A. Check the low air pressure switch
The boiler vent valve is used for the purpose of allowing:
Select one:
A. Steam to enter while draining
B. Steam to escape while filling
C. Air to escape while draining
D. Air to escape while filling
E. Water to escape while filling
D. Air to escape while filling
The switch in the operating control of a steam boiler is opened by:
Select one:
A. Falling steam pressure
B. Falling steam temperature
C. Falling water pressure
D. Rising steam pressure
E. Rising steam temperature
D. Rising steam pressure
Before feedwater enters a boiler the feedwater pipe must be fitted with a:
Select one:
A. Stop valve between the check valve and the boiler
B. Check valve between the stop valve and the boiler
C. Ball valve between the check valve and the boiler
D. Gate valve between the check valve and the boiler
E. Globe valve between the check valve and the boiler
A. Stop valve between the check valve and the boiler
The voltage supply generated by the thermocouple is usually not more than :
Select one:
A. 30 millivolts
B. 15 millivolts
C. 100 millivolts
D. 50 millivolts
E. 0 millivolts
A. 30 millivolts
A heating boiler must have a permanently attached marker indicating:
Select one:
A. Lowest permissible water level
B. The maximum allowable working temperature
C. The maximum allowable working pressure
D. Highest permissible water level
E. Lowest permissible steam level
E. Lowest permissible steam level
Quick closing gauge glass valves are operated by:
Select one:
A. Actuators
B. Levers and chains
C. Valve rods
D. Diaphragms
E. Solenoids
B. Levers and chains
The low water level fuel cut-off will shut off the fuel to the heating boiler when the water level drops below:
Select one:
A. 50 mm(2 in) above the bottom of the gauge glass
B. 25 mm (1 in) above the bottom of the gauge glass
C. One half of the gauge glass
D. The lowest visible part of the gauge glass
E. The lowest permissible water level
D. The lowest visible part of the gauge glass