The wax filled sensor probe in a combination pressure-temperature relief valve will expand and open the valve by means of a piston at approximately:
Select one:
A. 110°C (230°F)
B. 99°C (210°F)
C. 134°C (273°F)
D. 50°C (122°F)
E. 60°C (140°F)
B. 99°C (210°F)
The relief valve on hot water boilers with a working pressure of up to 414 kpa (60 psi) should open with in a variation of _____ below or above the setpoint.
Select one:
A. 10 kPa (1.5 psi)
B. 30 kPa (4.5 psi)
C. 20 kPa (3 psi)
D. 5%
E. 14%
C. 20 kPa (3 psi)
The discharging piping from the relief valve should be piped to a safe point for disposal and can be:
Select one:
A. Connected to any vent
B. Connected to any drain
C. Terminated above a floor drain
D. Connected to a condensate tank
E. Connected to the Deaerator
C. Terminated above a floor drain
The minimum size of the hot water heating boiler bottom blow off or drain connection shall be:
Select one:
A. 19 mm (3/4 in.)
B. 15 mm (1/2 in.)
C. 25 mm (1 in.)
D. 75 mm (3 in.)
E. 6 mm (1/4 in.)
A. 19 mm (3/4 in.)
The temperature of the water in a hot water heating system with an open expansion tank is normally limited to:
Select one:
A. 99°C (210°F)
B. 80°C (175°F)
C. 121°C (250°F)
D. 60°C (140°F)
E. 150°C (302°F)
B. 80°C (175°F)
The automatic fill valve is a _____ valve which keeps the system filled with water and maintains a set pressure in the system.
Select one:
A. Temperature control valve
B. Pressure reducing valve
C. Back pressure valve
D. Air vent valve
E. Pressure control valve
B. Pressure reducing valve
On a hot water boiler, the highest value on the graduated scale of the pressure gauge shall not be less than_____ times the pressure at which the pressure relief valve is set.
Select one:
A. 2
B. 1.5
C. 3.5
D. 2.5
E. 3
B. 1.5
The purpose of the expansion tank in a hot water heating system is to:
Select one:
A. Provide storage space for excess water
B. Add make-up water to the system
C. Provide storage space for excess steam
D. Provide space to store the returning condensate
E. Separate the water and steam produced
A. Provide storage space for excess water
The highest pressure to which the scale on the pressure gauge of a hot water boiler may be graduated is _____ times the pressure at which the pressure relief valve is set.
Select one:
A. 3
B. 3.5
C. 2.5
D. 1.5
E. 2
B. 3.5
The pressure relief valve is typically installed on the boiler or reasonably close to the boiler outlet with:
Select one:
A. A plug valve for isolation
B. A gate valve for isolation
C. A ball valve for isolation
D. A globe valve for isolation
E. No valve between
E. No valve between
The operating handle of the valve to the pressure gauge on a hot water boiler must be of the:
Select one:
A. A valve is not permitted in this location
B. Solenoid type
C. Hand wheel type
D. Tee or lever handle design
E. Diaphragm type
D. Tee or lever handle design
The relief valve on hot water boilers with a working pressure of up to 414 kPa (60 psi) should open with a variation of _____ below or above the set point.
Select one:
A. 5%
B. 20 kPa (3 psi)
C. 30 kPa (4.5 psi)
D. 14%
E. 10 kPa (1.5 psi)
B. 20 kPa (3 psi)
The discharge piping from the relief valve should be piped to a safe point for disposal and can be:
Select one:
A. Connected to any vent
B. Terminated above a floor drain
C. Connected to the condensate tank
D. Connected to any drain
E. Connected to the Deaerator
B. Terminated above a floor drain
The temperature of the water in a hot water heating system with an open expansion tank is normally limited to:
Select one:
A. 99°C (210°F)
B. 80°C (175°F)
C. 150°C (302°F)
D. 60°C (140°F)
E. 121°C (250°F)
B. 80°C (175°F)
The minimum size of the hot water heating boiler bottom blow off or drain connection shall be:
Select one:
A. 25 mm (1 in.)
B. 6 mm (1/4 in.)
C. 15 mm (1/2 in.)
D. 75 mm (3 in.)
E. 19 mm (3/4 in.)
E. 19 mm (3/4 in.)