Block 2 - Commission Fuel Train Components & ICI Burners Self Assessment Flashcards

1
Q

According to ASME CSD1, where is the installation of a strainer recommended in the gas train?

A

Before the horizontal components

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

How are oil burner valve trains different from gas fuel valve trains?

A

Oil valve trains often combine components into an “oil block”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Where should a high gas pressure safety device be installed according to B149.3 clause 12.5.1?

A

Downstream of the pressure regulator

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What is the purpose of the low gas pressure safety device according to B149.3 clause 12.5.2?

A

To initiate shut off of the gas supply if pressure drops below 50% of the lowest normal operating pressure

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

How is fuel adjusted on a burner with a fuel cam?

A

By changing the position of the input flow control valve

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Which type of VPS uses a pump and advanced instrumentation?

A

Active VPS

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What should be checked to ensure gas-tightness of the valve seats according to B149.3 clause 15.1?

A

1) Appliance shutoff valve

2) Test firing valves

3) SSOV valves

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What is the purpose of the overtravel linkage on a fuel cam system?

A

To set and lock high fire and low fire stops

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What is the first step when checking the tightness of closure of a fuel valve?

A

Install a manometer or pressure gauge

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Which clause in B149.3 specifies the outlet pressure maintenance capability of a pressure regulator?

A

Clause 4.4

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What is a suitable option for selecting overpressure protection (OPP) when high inlet pressure is encountered?

A

Monitor regulation

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What is the required accuracy of a pressure regulator outlet pressure during burner operation?

A

Within 10% above or below the regulator set pressure

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

When adjusting a flow control valve, what tool should be used to ensure accurate adjustments?

A

Combustion analyzer

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

For appliances with inputs in excess of 400,000 Btu/h (120 kW), where should a low gas pressure safety device be installed?

A

Downstream of the pressure regulator and upstream of the safety shutoff valve

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What is a common feature of the SSOVs in oil burner valve trains?

A

Normally closed solenoid valves piped in series and wired in parallel

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Which system allows precise adjustment to a single valve or damper position without affecting other components?

A

Parallel Position system (FARC)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

What action is recommended if a fuel valve leakage is detected?

A

Correct any conditions causing leakage

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

What is the purpose of the B149.3 Annex A procedure?

A

To ensure safe start-up of high input gas-fired equipment

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

Which type of valve shall be of the quarter-turn type according to B149.3 - 6.2?

A

Test firing valve

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

What does a modern unified valve combine into a single device?**

A

1) Pressure regulation

2) Valve closing

3) Variable flow rate and pressure switch

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q

What is the opening time for electro-hydraulic SSOVs?

A

13 seconds or 23 seconds

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
22
Q

What is the purpose of the Proof of Closure switch?

A

To prove the valve is in the closed position

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
23
Q

What is the purpose of the FGR flow control damper?

A

To regulate the quantity of flue gas to the FGR inlet box

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
24
Q

When setting FGR rates, why are two emissions analyzers required?

A

To measure the stack O2 levels, CO, NOx emissions, and oxygen content in the burner housing

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
25
Q

What is the purpose of the FGR flow control damper?

A

To regulate the quantity of flue gas to the FGR inlet box

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
26
Q

How should the draft be adjusted if it is too low during commissioning?

A

Add weight to the damper chain to choke dilution air and increase draft

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
27
Q

What is primary air in the context of combustion?

A

The air supplied to achieve stoichiometric combustion

28
Q

Why is it important to insulate the duct, FGR damper, and inlet box assembly?

A

To prevent accidental burns in high-temperature areas

29
Q

What is the purpose of adjusting fan speed during combustion optimization?

A

To find the optimal point where combustion is efficient and stable

30
Q

What is the role of the PID gain settings in an integrated or standalone draft control system?

A

To adjust for the correct draft and set response and accuracy if modulating

31
Q

Why is it important to have provisions to drain condensate in the FGR system?

A

To prevent water vapor accumulation and condensation in low points

32
Q

How should the stack temperature switch be set during FGR system start-up?

A

A few degrees below the normal low fire stack temperature (approximately 200°F)

33
Q

What effect does a positive combustion chamber pressure have on the system?

A

Adds a closing force on the regulator, upsetting control of the system

34
Q

What should be confirmed before operating the burner for an extended period?

A

The FGR blower is in operation

35
Q

What is the primary function of the FGR inlet box?

A

To pull flue gas from the stack and deliver it to the combustion air fan inlet

36
Q

What should be the maximum pressure drop between the stack and burner inlet in the FGR ductwork?

A

1-inch w.c.

37
Q

What should be tested and set to correct settings during operating and limit controls check?

A

All operating and limit controls

38
Q

What should be confirmed before performing a combustion analysis?

A

Drafts for the appliance are correct

39
Q

What should be done if the low fire light off position results in noticeable physical vibration of the equipment?

A

Decrease the burner firing rate

40
Q

When setting FGR rates, why are two emissions analyzers required?

A

To measure the stack O2 levels, CO, NOx emissions, and oxygen content in the burner housing

41
Q

What should be done if the low fire light off position results in noticeable physical vibration of the equipment?

A

Decrease the burner firing rate

42
Q

What should be done if temperature and pressure variations in the boiler room prevent repeatable operation of the burner?

A

Add control components such as oxygen trim

43
Q

What should be done if clocking is not possible due to other appliances firing?

A

Install an orifice plate

44
Q

Why is an impulse line used in combustion systems?

A

To connect the combustion chamber to the air/gas ratio regulator, correcting regulator action

45
Q

What is the main goal when setting the high fire air/gas ratio in a zero governor system?

A

To achieve the correct high fire setting using a limiting orifice

46
Q

What is the function of the FGR duct temperature switch?

A

To shut down the burner if duct temperature exceeds the set point

47
Q

Why is it important to perform a pilot turn down test?

A

To ensure the smallest pilot flame will ignite the main flame safely

48
Q

What should be confirmed before showing up on-site for commissioning an appliance?

A

All appropriate permits are in order

49
Q

Why is it important to note the stack temperatures during commissioning?

A

To compare them to the manufacturer’s specifications

50
Q

Why is it important to insulate the duct, FGR damper, and inlet box assembly?

A

To prevent accidental burns in high-temperature areas

51
Q

How should FGR damper position adjustments be made, especially at low firing rates?

A

In very small increments while observing readings and burner operation

52
Q

What should be the maximum pressure drop between the stack and burner inlet in the FGR ductwork?

A

1-inch w.c.

53
Q

What should be done if temperature and pressure variations in the boiler room prevent repeatable operation of the burner?

A

Add control components such as oxygen trim

54
Q

Why is it essential to prove the stack damper is open before allowing the combustion air blower to start?

A

To ensure safety and proper operation of the system during the purge sequence

55
Q

What information does a gas safety officer need to check permits?

A

Customer name, company site name, and address

56
Q

What should be confirmed before operating the burner for an extended period?

A

The FGR blower is in operation

57
Q

How should the air damper position be adjusted if the system uses linkages?

A

Adjust in increments of 10% using a potentiometer

58
Q

What is the function of the FGR duct temperature switch?

A

To shut down the burner if duct temperature exceeds the set point

59
Q

How should initial airflow be set during commissioning?

A

By adjusting the air damper(s) or fan speed

60
Q

How should the stack temperature switch be set during FGR system start-up?

A

A few degrees below the normal low fire stack temperature (approximately 200°F)

61
Q

When adjusting initial damper positions, why is it important to follow the manufacturer’s recommendations?

A

To achieve proper air-fuel mixing and combustion stability

62
Q

What is the primary function of the FGR inlet box?

A

To pull flue gas from the stack and deliver it to the combustion air fan inlet

63
Q

What should be checked during a site visit ahead of time?

A

Gas piping size, pressure, and testing

64
Q

Why is it important to have provisions to drain condensate in the FGR system?

A

To prevent water vapor accumulation and condensation in low points

65
Q

How should FGR damper position adjustments be made, especially at low firing rates?

A

In very small increments while observing readings and burner operation

66
Q

Which of the following should be verified with gas firing valves closed?**

A

Prove high fire purge