2-5-5 Flashcards

1
Q

An IEEE Class 1 Termination does not provide a seal to the external environment and must be sealed with two layers of tape

A

false

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

One function that an IEEE Class 1 Termination provides is __?__ between the high voltage conductor and ground.

A

external leakage protection

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Three problems that are associated with a non-shielded termination include __?__, electrical connection of the conductor, and physical protection of the cable insulation.

A

mechanical support

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

A(n) __?__ gradually increases the total thickness of insulation from the edge of the semi-conducting shield out to a certain point on the cable’s insulation.

A

stress cone

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

The two functions of a termination insulator are to provide BIL protection against flashover damage and to provide __?__ protection for the cable’s insulation.

A

tracking

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

In addition to the termination’s voltage stress, two conditions are necessary for tracking. One condition is contamination and the other is __?__.

A

moisture

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

The two best insulator materials for providing cable tracking protection are silicone rubber and __?__.

A

porcelain

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

The upper level at which a termination can withstand surges, such as lightning surges is known by the initials __?__.

A

BIL

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

The upper level at which a 15-kilovolt rated termination can withstand surges, such as lightning, is __?__ crest.

A

110kv

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

An IEEE Class1 Termination has two seals located at the top and bottom.

A

true

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

The function of the bottom seal on a IEEE Class 1 Termination is to provide a(n) __?__ to the cable jacket and ground wire.

A

moisture seal

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Some porcelain terminations are referred to as “potheads.” A pothead performs sealing functions because it is filled with a(n) __?__.

A

potting compound

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

A termination’s __?__ distance is the surface distance between a conductor and ground, also referred to as the string distance.

A

creepage

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Assume a five-kilovolt rated cable to be terminated indoors in switchgear, the thickness of the stress cone at its peak (T) is __?__.

A

quarter of an inch

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

The type of stress control used in heat shrink terminations is a __?__.

A

stress control tube

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

A basic (tubular) heat shrink termination for outdoor use can be upgraded by installing separate heat shrink skirt(s).

A

true

17
Q

The way to shrink a Quick Term II Termination onto the cable is to slide the termination body onto the cable and remove the core. Starting with the loose end, pull while unwinding __?__.

A

counter-clockwise

18
Q

The type of IEEE termination that provides stress control and should be used in a clean, dry environment is the Class __?__.

A

3

19
Q

Without stress control, the cable’s electric field becomes very concentrated and the resulting voltage stress is high enough to break down the air. This break down is referred to as a partial discharge or __?__.

A

corona

20
Q

The information sheet to this lesson names __?__ common termination types.

A

5

21
Q

Tape termination is not one of the common termination types because it takes too long to apply.

A

false

22
Q

Terminations are categorized as live-front connections.

A

true

23
Q

For additional protection, the termination’s creepage path may be covered with __?__ tape.

A

silicone