2-5-13 Flashcards
One-reason rubber gloves must be worn when conducting an inspection of an underground system during an outage is because __?__.
back feed may exist
Animals never burrow into pad mounted transformers or switchgear.
false
Test reclosing of a switch or fuse when an underground fault has taken place as a method of locating a fault should be a(n) __?__ procedure.
authorized
In order to get half of the customers back on when troubleshooting an underground radial feed system, the elbows at the __?__ of the system are placed in standoff position and the cutout feeding the section of the system is closed in.
center point
When a fault exists on an underground system but you have power up to a standoff elbow, you can leave the exit cable on standoff and energize the transformer by hand, while wearing rubber gloves.
false
A device that points the way to the general area of a fault on an underground system is a(n) __?__.
fault circuit indicator
A fault-circuit indicator is designed to activate a signal at a preset over-voltage level
false
Your first stop when responding to an outage on an underground system should be at the __?__.
take off
According to this lesson, you should not reenergize an underground system at the riser pole and try it one time as you might with an overhead system because of public accessibility to equipment.
true
While waiting for help to arrive with an outage on an underground system, a __?__ inspection can be carried out.
drive through
One critical element when troubleshooting an underground system is having up-to-date maps.
true
Two things to look for when doing an underground system drive through inspection is damage to equipment and evidence of a(n) __?__
dig in
One reason for a cable to fault may be that it has been in the ground a long time.
true
Cable treeing is mainly caused by water containing __?__ being in contact with the cable over a long period of time.
contaminats
When drain tapes or wires corrode, the __?__ current will arc across the gap and cause the insulation to fail.
charging