2-5-15 Flashcards

1
Q

Modern manufactured kits are so easy to install that special cable splicing training is no longer necessary for the installer.

A

false

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Two categories of manufactured kits that have requirements for production (factory) testing are elbows and __?__.

A

terminations

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Production tests that are required for 15 kV premolded splice kits are the alternating current withstand test, impulse withstand test (lightning impulse) and __?__ test.

A

corona (partial discharge)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Heat shrink splices are not subjected to production tests because of their components configuration and are therefore exempted from the IEEE Standard for production testing.

A

true

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

For an indoor switchgear cabinet application, it would be considered okay to upgrade an IEEE Class 2 Termination to an IEEE Class 1.

A

true

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

The first step in preparing for an accessory kit installation is __?__.

A

the selection of the correct kit for the job

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Which item listed below is NOT useful information when selecting a manufactured splice kit?

A

KVA

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Which application listed below is NOT used with manufactured splice kits?

A

underwater

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Four common termination applications that could affect the selection of a manufactured termination kit are indoors, outdoors, contaminated environment and __?__.

A

inverted installations

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Before selecting a 600 Amp deadbreak elbow for a transformer connection, you should confirm that the transformer has __?__.

A

600 amp dead front bushing

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

The key to making a quality installation when using a manufactured kit, is to carefully follow the manufacturer’s instructions.

A

true

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Manufactured kits always provide the best splicing or terminating solution for the job.

A

false

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

According to the Underground Distribution reference, List the following steps that are followed before starting a splicing job using the Raychem XLPE Feeder Cable Heat Shrinkable Splice: ensure that the appropriate isolation and grounding procedures have been followed; prepare the work area; visually inspect the kit components; read the manufacturer instructions; and__?__.

A

make sure the proper tools are on hand

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Refer to: Introduction, Splice Primary Cables. Complete the following saying (which emphasizes the wisdom of making quality splices). “No cable is better than the__?__.”

A

splices that are made in it

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Two different types of cable accessories that are used for terminating primary shielded cable runs are terminators and __?__.

A

elbows

How well did you know this?
1
Not at all
2
3
4
5
Perfectly