1210.0 Foam Operations with In Line Eductor Flashcards
I. Foam Eductors
A. The three eductors in service on various apparatus are rated at ____ GPM, ____ GPM, or _____ GPM.
60 / 95 / 125
I. Foam Eductors
B. The eductor must be used with a nozzle having the same \_\_\_\_\_ \_\_\_\_\_. An \_\_\_\_\_\_\_ \_\_\_\_\_ nozzle is attached to the foam tube. The proper GPM setting on the \_\_\_\_\_\_\_ must be set to match the rated GPM of the \_\_\_\_\_\_\_\_.
rated flow / Elkhart SOF / nozzle / eductor
II. Procedure
A. Eductor at engine discharge outlet 1. Attach the eductor to a \_\_\_\_\_ pump discharge outlet by using a \_\_\_\_\_ to \_\_\_\_\_ reducer.
2 1/2”
2 1/2” to 1 1/2” reducer
II. Procedure
A. Eductor at an engine discharge outlet 2. Connect \_\_\_\_\_' of \_\_\_\_\_" hose to the eductor discharge. The hose lay between eductor and the nozzle must not exceed \_\_\_\_\_'. 3. Place the \_\_\_\_\_\_\_\_\_ \_\_\_\_\_ nozzle and the foam tube assembly on the \_\_\_\_\_" hose.
150’ of 1 3/4” hose
150’
Elkhart SOF
1 3/4”
II. Procedure
A. Eductor at an engine discharge outlet 4. Adjust the \_\_\_\_\_\_\_ \_\_\_\_\_\_\_ on the eductor to the correct percentage setting required for the foam concentrate. 5. Open \_\_\_\_\_\_\_ outlet and set the eductor inlet pressure at \_\_\_\_\_psi for accurate proportioning of foam concentrate into the water stream and efficient nozzle performance. Be sure nozzle is \_\_\_\_\_\_ \_\_\_\_\_.
metering device
discharge outlet
200psi
fully open
II. Procedure
A. Eductor at an engine discharge outlet 6. Insert the eductor \_\_\_\_\_\_\_ tube into the foam supply. There will be a delay of \_\_\_\_ to \_\_\_\_ seconds before the foam solution will be discharged at the nozzle.
pick-up tube
12 to 15 seconds
II. Procedure
B. Eductor in an Extended layout 1. Attach \_\_\_\_" hose to a \_\_\_\_\_" pump discharge outlet. 2. Attach the eductor to the \_\_\_\_" hose by using a \_\_\_\_\_" to \_\_\_\_" reducer. 3. Connect \_\_\_\_' of \_\_\_\_" hose to the eductor discharge. The hose lay between the eductor and the nozzle must exceed \_\_\_\_\_'.
3” hose to 2 1/2” pump discharge outlet
3” / 2 1/2 to 1 1/2 reducer
150’ of 1 3/4” hose
150’
II. Procedure
B. Eductor in an Extended layout 4. Place the \_\_\_\_\_\_\_ \_\_\_\_\_ nozzle and foam tube assembly on the \_\_\_\_\_" hose. 5. Adjust the \_\_\_\_\_\_\_ \_\_\_\_\_\_ on the eductor to the correct percentage setting required for the foam concentrate.
Elkhart SOF / 1 3/4” hose
metering device
II. Procedure
B. Eductor in an Extended layout 6. Open the \_\_\_\_\_\_\_ outlet and set the eductor inlet pressure at \_\_\_\_\_psi for accurate proportioning of foam concentrate onto the water stream and efficient nozzle performance. Be sure nozzle is \_\_\_\_\_\_ \_\_\_\_\_. 7. Insert the eductor \_\_\_\_\_\_ tube into the foam supply. There will be a delay of \_\_\_\_ to \_\_\_\_\_ seconds before the foam solution will be discharged at the nozzle.
discharge / 200 psi
fully open
pick-up tube
12 to 15 seconds
It is the policy of the Richardson FD to utilize the _______ Eductor as a backup to the _________ system or for operations requiring an ________ layout.
In-Line / built-in / extended