11/6 Inspection Guides Flashcards

1
Q

“No Smoking - Stop Motor” signs with letters ___ posted at every AFS.

A

3” high

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Auto Fueling Station

At least one 10 BC within ___ of each island.

A

75’

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Auto Fueling Station

Must have ___ separate extinguishers on premises.

A

two

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Electrical shut-offs for main power and pump shut-offs must have signs;
not closer than ___ or farther than ____ with “Gas Pump Shutoff? letters ____

A

25 feet / 100’ / 1” high.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

For self service operations (Mom-Pop Stores) dead man’s switch required on a wall at a height of ____ above the floor, located in an area adjacent to a window. All pumps must be visible from this location.

A

6 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Interior Exits (in B-2 50 or over) must have ___, panic hardware only, must swing in direction of travel (must open out), and must be ___

A

two exits / 36” wide.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Exit corridors should not be less than ___.

A

44”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Exit and directional signs showing path of travel to exits If not visible.
Exit signs with ____ over exits.

A

6” letters

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Extinguishers - One 2A within ___ of travel; ___ 10B provided adjacent to cooking facilities.

A

75’ / one

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Check for ____ obstructed area around sprinkler control valve and an access aisle to the valve.

A

3’

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Check for ____ clearance below sprinkler head.

A

18”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Stove and heaters must be spaced and insulated from the wall, preventing wall temperature from exceeding ____.

A

160 degrees

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Check for ___ clearance around electrical or fuse boxes; make sure no cords on appliances are over___

A

3’ / 12’ long.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Fire Department sprinkler connection sign - _____

A

8” length, 4” width (labeled)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Need two exits if occupant load is over ___.

A

50.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Exit doors openable without a key, tool, implement, or special knowledge within ____.

A

30 seconds.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

Storage of combustibles ____under lowest point of ceiling or interior roof brace, if un-sprinklered.

A

3’

18
Q

Sprinklers ____ above combustibles.

A

18”

19
Q

Fire extinguisher top not less than ______ from floor.

A

3 ft. nor more than 5 ft.

20
Q

Provide and maintain an approved portable fire extinguisher within ____ of every portion of the place of business (or in lieu, small hose is acceptable

A

75’

21
Q

____ clearance required for standpipe inlets. ____ sign indicating use.

A

3’ / 8” x 4”

22
Q

Lobby :
Fire alarm tested every ____ maintain and retain records.
Single-station smoke detectors tested every ____ maintain and retain records.

A

30 days / six months

23
Q

___ clearance of hose and outlets.

A

3’

24
Q

____ clearance on roofs of wires, etc. (guy wires may extend out ___ the length of the supported antenna, etc.)

A

7’ / 1/6

25
Q

Extension cords shall not extend ____ or extended to exceed original length.

A

12 feet or be spliced

26
Q

All sprinkler systems must have directional signs with ____ showing location of control valve. A ____ sign showing Fire Department connection is required.

A

3-inch letters / 4” x 8”

27
Q

6 spare sprinkler heads for system with up to ___.

A

300 heads.

28
Q

12 spare heads for system with _____.

A

300 to 1,000 heads.

29
Q

24 heads for system with over_____.

A

1,000 heads.

30
Q

Heads shall be in a identified cabinet near control valve with maximum storage temperature ___

A

100 degrees F.

31
Q

Minimum of ___ clearance around inlet and outlets.

A

3’

32
Q

Maintain ___ clearance around fire doors and their operating mechanisms.

A

3’

33
Q

Building Code Fire assemblies shall close automatically at ____ or____ above ambient temp

A

165 degrees / 50 degrees

34
Q

Red button in elevator “To Be Used in Case of Fire” ____. Break beam and operation of button should cause door to close

A

overrides the photo-electric door closure

35
Q

Smoke Barrier

Floor separation walls shall be at least ____ on each side of wood studs.

A

one-half inch gypsum wallboard

36
Q

Smoke Barrier

Openings to be protected by not less than ____ of the self-closing type with approved latching device.

A

1-3/4 inch solid core doors

37
Q

Smoke Barrier

Doors shall not open over steps but shall open over a floor or landing not more than ___ below the threshold.

A

two inches

38
Q

Smoke Barrier

Depth of the landing shall ____ than the width of the door.

A

not be less

39
Q

Exterior Industrial Occupanices:

___ clearance between guy wires and roof except TV antenna (___ height of mast away from base).

A

7’ / 1/6

40
Q

No excessive height for lumber yard piles.
___ high with __ driveway.
___ from building, ___ from openings in buildings.

A

25’ / 15’ / 5’ / 10’