11/5 Specific Hazards : Special Extinguishing Systems Flashcards

1
Q

Foam extinguishing system, water spray system, cardon dioxide extinguishing system and fixed water spray systems are tested ____

A

annual, look for the State fire Marshal certified tester tag.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Dry chem extinguishing system: Tested ____ by a State Fire Marshal certified tester

A

semi-annually

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Halon and clean agent systems: tested ____

A

Annually , All systems shall be tested by a state certified tester

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

An approved automatic or manually activated local fire alarm system shall be provided for:
Every apartment house ____ stories in height or containing ____ dwelling units.

A

three or more / 16 or more

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Fire alarm system :
Every hotel ____ stories in height or containing ____ guest rooms. (57.122.08) The operation of fire alarm systems in hotels and apartments must be checked at least once a month. This check is to be performed by the responsible person or by an authorized service agency. A record of these tests is to be kept at the control panel. The installer’s name and telephone number shall be placed inside the control panel cabinet.

A

three or more / 20 or more

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

An approved permanent sign which reads, “_____” shall be installed by each manual pull station and annunciator panel. 57.122.06

A

LOCAL ALARM ONLY - CALL FIRE DEPARTMENT

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Fire Alarm Systems shall be tested ____ to the satisfaction of the Chief’s Regulation #4. An accurate record of such tests shall be kept and these records shall be open to examination by the Chief.

A

annually

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Single-station smoke detectors shall be provided in _____ by Section 91.1210 of the Los Angeles Municipal Code.

A

multiple dwelling occupancies

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Smoke detectors shall be installed by _____ in all existing multiple dwelling occupancies and duplexes.

A

August 1, 1983

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Installation shall be made directly to the _____ of the occupancy.

A

electrical wiring

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Smoke detectors shall be installed in every ____ room and the corridor or area ____ to any such sleeping room.

A

sleeping / giving access

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Existing single-family dwellings shall have smoke detectors installed at the time of sale, or when an improvement requires a permit and the total valuation of the improvement exceeds ____.

A

$1,000.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Group R, Division 1 occupancies. (Hotel, Apts. and Condominiums) Single-station smoke detectors required by Section 91.1210 of the Los Angeles Municipal Code shall be maintained in dependable operating condition and tested ___ or as otherwise required by the Chief.

A

every six months

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Group R, Division 3, occupancies. (Duplexes, Multi-Unit Bldgs., Single Family Residence) Single-station smoke detectors required by Section 91.1210 of the Los Angeles Municipal Code shall be maintained in dependable operating condition and tested every ____ or as otherwise required by the Chief.

A

six months

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

An owner or the owner’s agent may enter any dwelling unit, efficiency dwelling unit, guest room and suite owned by such owner for purpose of ________.

A

installing, repairing, testing, and maintaining single-station smoke detectors

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

The top of any smoke detector installed on a wall shall be no closer than ______ to the ceiling and no farther than ___ from the ceiling.

A

six inches / twelve (12) inches

17
Q

All required detectors shall be located in accordance with the manufacturer’s instructions; with no part of the detector located more than ____ below the ceiling.

A

12 inches