Every building four or more stories in height shall be provided with interior Class II (wet) standpipes. Exceptions - _____.

A

completely sprinklered buildings.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Every building or portion thereof constructed subsequent to ____, exceeding 150 feet in height, shall be provided with combination standpipes that are directly connected to a water supply.

A

May 25, 1960

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Location of standpipe:

There shall be a ___ above the roof line when the roof has a slope of less than 4 inches in 12 inches.

A

three-way outlet / 4 inches in 12 inches.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Location of standpipe:
In a Group A, Divisions 1, 2, and 2.1 Occupancies, with occupant loads of more than 1000, outlets are located on _____ of the auditorium and on ___ of the balcony.

A

each side of any stage, on each side of the rear / each side

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Every building ____ in height shall be provided with not less than one standpipe for use during construction.

A

six stories or more

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Such standpipes are installed when the progress of construction is not more than ___ above grade.

A

50 feet in height

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Such standpipe shall be provided with Fire Department hose connections at accessible locations adjacent to ____

A

usable stairs.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Such standpipe systems shall be extended as construction progress to within one floor of the ____.

A

highest point of construction having secured decking or flooring

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Where construction height requires installation of a Class III standpipe,____ shall be provided to serve the standpipe.

A

fire pumps and water main connections

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Temporary standpipes may be provided in place of permanent systems if they are designed to furnish ____ of water per minute at ___ per square inch pressure with a standpipe size of not less than ____.

A

500 gallons / 50 pounds / four inches.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Sprinkler system: In every story or basement of all buildings when the floor area exceeds ___ and there is not provided at least ____ of opening entirely above the adjoining ground level in each ____or fraction thereof of exterior wall in the story or basement on at least one side of the building.

A

1,500 square feet / 20 square feet / 50 lineal feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Openings shall have a minimum dimension of not less than ___. Such openings shall be accessible to the Fire Department from the exterior and shall not be obstructed in a manner that fire fighting or rescue cannot be accomplished from the exterior.

A

30 inches

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

When openings in a story are provided on only one side and the opposite wall of such story is more than ___ from such openings, the story shall be provided with an approved automatic sprinkler system,

A

75 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

At the top of _____ and in their terminal rooms. Chutes extending through ___ floors will have additional sprinkler heads installed within such chutes at alternate floors. Sprinkler heads are to be accessible for servicing.

A

rubbish and linen chutes / three or more

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Sprinkler System :

In rooms where ____is stored or handled.

A

nitrate film

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Sprinkler System :
In restaurants, nightclubs, discos. Rooms primarily used for entertaining occupants who are drinking or dining and unseparated accessory uses where the total area of such unseparated rooms and assembly uses exceeds _____.

A

5,000 square feet

17
Q

In basements classified as a Group A Occupancy when the basement is larger than ____ in floor area.

A

1500 square feet

18
Q

Sprinkler Alarms. On all sprinkler systems having more than_____ a local waterflow alarm shall be provided which will sound an audible signal on the premises upon water flow through the system equal to the flow from a single sprinkler.

A

twenty (20) sprinklers

19
Q

Sprinkler System Alarms: When serving more than____ , automatic sprinkler systems shall be supervised by an approved _____ or a local alarm which will give an audible signal at a constantly attended location.

A

100 sprinklers / central, proprietary or remote station service

20
Q

Maintain at least a ____ access and a minimum operating clearance of_____ around standpipe valves.

A

three foot / 18 inches

21
Q

Provide and maintain a clearly identifiable sign stating “Fire Hose” with letters not less than ____ in height on a contrasting background.

A

three inches

22
Q

Fire Department connections in dark or obscured areas may have to be highlighted with a_____ background painted behind the connections.

A

two-to-three foot white

23
Q

Signs :
Such sign shall not be less than _____ and _____ and have the following inscription: (specify wording and system locations)

A

eight inches in width / four inches in height

24
Q

Provide and maintain a _______ background behind Fire Department connections

A

two foot diameter white

25
Q

LOCATION - Where sprinkler heads are located closer than _____, ____ are required so that he discharge from one head will not wet the adjacent head and prevent its operation.

A

5 lineal feet / metal baffles

26
Q

AISLE - Maintain access aisle with a minimum clearance of _____ to valve(s).

A

three feet