Week 20 Chapter 10 - Pages 10-1 to 10-41 Flashcards

1
Q

Which one of the following is optional information for the administration record of the Cable component in the Cabling category?

a. Number of termination
b. Performance category
c. Cable length
d. Date installed

A

c. Cable length

p 10-9 Table 10.2

Also optional:

  • Bonding and grounding record
  • Equipment record
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
1
Q

Which one of the following is an optional administration system linkage/cross-reference for the Cable component in the Cabling category?

a. Termination position record
b. Splice record
c. Pathway record
d. Equipment record

A

d. Equipment record

p 10-9 Table 10.2

Also optional:

  • Bonding and grounding record
  • Cable length
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Which one of the following is the only required administration system linkage / cross-reference for the Firestopping component in the Spaces and Pathways category?

a. Cable record
b. Space record
c. Building floor plan
d. Pathway record

A

d. Pathway record

p 10-8 Table 10.2

Also required:
Firestop location

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

A campus is a required identifier for which class(es) of telecommunications administration?

a. Class 4
b. Class 3 and higher
c. Class 2 and higher
d. All classes

A

a. Class 4

p 10-6 Table 10.1

Note, Class 3 only classifies Campus (interbuilding) backbone cable and Campus backbone termination position, pair, or strand and NOT CAMPUS. CAMPUS is for Class 4.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

When determining the minimum class of administration required, the ____ of telecommunications spaces is one indicator of complexity.

a. Locations
b. Contents
c. Type
d. Number

A

d. Number

p 10-4

The most relevant factors in determining the minimum class of administration is the size and complexity of the infrastructure.

The number of telecommunications spaces (e.g., ER, TR, EF) is one indicator of complexity.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Which one of the following is required information for the administration record of the Cabinet, Rack, Frame, or Wall Segment component in the Spaces and Pathways category?

a. Manufacturer and part number
b. Available space
c. Total space
d. Cabinet identifier

A

d. Cabinet identifier

p 10-8 Table 10.2

Also required:

  • Space record
  • Cable record
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

ANSI/TIA-606-B specifies the records required by class of administration. Telecommunications space records are required for all classes of administration.

a. True
b. False

A

b. False

p 10-37 Table 10.5

Note, this differs from Table 10.1 on page 10-6. Table 10.1 states ALL CLASSES. Since the question specifically calls out ANSI/TIA-606-B, go with FALSE, per Table 10.5.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

The administration of pathways and spaces, and outside plant elements is recommended for buildings larger than:

a. 10,000 square meters (107, 645 square feet)
b. 7000 square meters (75,347 square feet)
c. 5000 square meters (53, 820 square feet)

A

b. 7000 square meters (75,347 square feet)

p 10-4

Classes are scalable and allow expansion without requiring changes to existing identifiers or labels. For mission-critical systems, buildings larger than ≈7000 m2 (75,347 ft2) or multi-tenant buildings, administration of pathways and spaces and OSP elements is recommended.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

ANSI/TIA-606-B specifies the records required by class of administration. Building backbone cable records are only required for class 3 and higher of administration.

a. True
b. False

A

b. False

p 10-6 Table 10.1

Is also required for Class 2 and higher.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

The class of telecommunications administration system recommended for a campus environment is:

a. Class 1
b. Class 2
c. Class 3
d. Class 4

A

c. Class 3

p 10-5

Class 3 administration addresses the needs of a campus, including its buildings and OSP elements.

Note, Table 10.1 states otherwise.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

The administration of pathways and spaces, and outside plant elements is recommended for buildings larger than:

a. 10,000 m2 (107, 645 ft2)
b. 7000 m2 (75,347 ft2)
c. 5000 m2 (53, 820 ft2)

A

b. 7000 m2 (75,347 ft2)

p 10-4

For mission-critical systems, buildings larger than ≈7000 m2 (75,347 ft2) or multi-tenant buildings, administration of pathways and spaces and OSP elements is recommended.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Which one of the following is an optional identifier for a class 1 telecommunications administration system?

a. Secondary bonding busbar (SBB)
b. Primary bonding busbar (PBB)
c. Telecommunications bonding backbone (TBB)
d. Telecommunications bonding conductor (TBC)

A

c. Telecommunications bonding backbone (TBB)

p 10-6 Table 10.1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Which one of the following is optional information for the administration record of the Primary Bonding Busbar (PBB) component in the Bonding and Grounding (Earthing) category?

a. Date of measurement
b. GEC identifier
c. Busbar type
d. PBB connection positions

A

d. PBB connection positions

p 10-11 Table 10.2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

The administration of cabling pathways in a class 2 telecommunications administration system is:

a. Required
b. Optional

A

b. Optional

p 10-4

The presence of cabling pathways may be assumed, so the administration of these elements is optional.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Which one of the following is required information for the administration record of the Bonding Conductor component in the Bonding and Grounding (Earthing) category?

a. Cable sheath color
b. Length
c. Identifier of components connected at both ends
d. Conductor size and type

A

d. Conductor size and type

p 10-11 Table 10.2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

The administration record of the Cords and Jumpers component in the Cabling category has no required linkages / cross-references.

a. True
b. False

A

a. True

p 10-10 Table 10.2

16
Q

Which one of the following is part of the security metric to consider in selecting the appropriate labels for an administrative system?

a. Tamper resistance
b. Smudge resistance
c. Temperature rating
d. Adhesive type

A

a. Tamper resistance

p 10-25

Security:
––Tensile strength
––Tamper evidence
––Tamper resistance

17
Q

If a telecommunications grounding busbar is installed in the telecommunications room (TR) with the identifier of 310, located on the third floor, then the telecommunications grounding busbar should be labeled as:

a. 310-SBB
b. SBB
c. SBB in TR 310
d. SBB in room 310

A

a. 310-SBB

p 10-28

18
Q

You have been asked to provide a UPS that is always serving the load from its batteries and the electrical supply is used only to recharge the batteries. Which one of the following types of UPS will meet this requirement?

a. Off line, standby
b. Line interactive
c. Online double conversion
d. Rotary

A

c. Online double conversion