Week 17 Chapter 8 - Pages 8-1 - 8-28 Flashcards
It is permissible to use metallic water pipes as a single ground (earth) source.
a. True
b. False
False
p 8-6
Metallic water piping should be used with great caution since maintenance and upgrades are generally performed with nonconductive plastic pipes. If used, metallic water pipes should never be a single ground (earth) source.
The secondary bonding busbar (SBB) must be a predrilled copper busbar with holes for use with standard-sized lugs. The minimum thickness for a SBB is:
a. 6mm (0.25 in)
b. 12.5 mm (0.50 in)
c. 19.1 mm (0.75 in)
d. 25.4 mm (1.00 in)
a. 6mm (0.25 in)
All sites have bonding conductors that exhibit some value ___ than ___ due to improperly wired electrical outlets, faulty equipment, and induction of ac and dc currents on telecommunications cable shields.
a. Less than 1 A
b. Less than 0 A
c. Greater than 500 mA
d. Greater than 0 A
d. Greater than 0 A
p 8-7: A reading of 0 A is the best possible reading for any bonding conductor. However, all sites have bonding conductors that exhibit some value greater than 0 A due to improperly wired electrical outlets, faulty equipment, and induction of ac and dc currents on
telecommunications cable shields.
Generally speaking, ___ is the establishment of a reference for the electrical power source (ac or dc), the electrical equipment, or both.
a. Grounding
b. Equalizations
c. Bonding
a. Grounding
Which one of the following systems typically the responsibility of the ITS distribution designer?
a. ac grounding electrode system
b. Equipment grounding system
c. Telecommunications circuit protectors
c. Telecommunications circuit protectors
The recommended maximum dc current value on any bonding conductor should be:
a. Greater than 0 A
b. 0 A
c. Less than 500 mA
d. Less than 1 A
c. Less than 500 mA
The PBB must be a pre-drilled copper busbar with holes for use with standard-sized lugs, have minimum dimensions of ≈6.3 mm (0.25 in) thick by ___ wide.
a. 25.4 mm (1.00 in)
b. 50.8 mm (2.00 in)
c. 101.6 mm (4 in)
d. 152.4 mm (6 in)
c. 101.6 mm (4 in)
The equipment grounding (earthing) system is the portion of the ac electrical distribution that maintains 0 volts (V):
a. On all equipment enclosures during normal operations.
b. For ac electrical power systems, whether utility-provided or customer-derived.
a. On all equipment enclosures during normal operations.
The equipment grounding (earthing) system is the portion of the ac electrical distribution that maintains 0 volts (V):
a. On all equipment enclosures during normal operations.
b. For ac electrical power systems, whether utility-provided or customer-derived.
a. On all equipment enclosures during normal operations.
When exposed to lightning, direct-buried cable collects ground strikes within a distance determined by soil resistivity. ____ soil resistance intensifies this problem.
a. High
b. Equalized
c. Non-uniform
d. Low
a. High
Which one of the following is NOT used to connect a telecommunications grounding (earthing) or bonding conductor to the telecommunications ground (earthing) electrode?
a. Listed clamps
b. Exothermic weld
c. Listed pressure connectors
d. Steel clamps
d. Steel clamps
The equipment grounding (earthing) system is the portion of the ac electrical distribution that acts as the intentional path of fault currents under:
a. Normal operations
b. Ground fault conditions
b. Ground fault conditions
The ___ is a telecommunications bonding conductor intended to equalize potentials between TRs on multiple floors of a building with an ultimate connection to the EF’s PBB
a. BBC
b. IG
c. TBB
d. TBC
c. TBB
BBC is is intended to equalize potentials between TRs on the SAME floor of a structure where multiple TBBs are used in a multi-story building.
TBC is intended to bond the PBB to the ac grounding (earthing) electrode system via the ac main service entrance panelboard.
To prevent any bonding or grounding (earthing) conductor (regardless of its purpose) from reaching this temperature, all grounding (earthing) or bonding conductors should be calculated to limit the total voltage drop to a maximum of ___ along its entire length.
a. 10 V
b. 20 V
c. 30 V
d. 40 V
d. 40 V
p 8-20
The IAEI calculations are based upon the sizing for the GEC over ≈30.5 m (100 ft). Since the bonding conductor sizing in the NEC is based on these same criteria, it can be assumed that following the same calculations will result in a suitable TBC.
One purpose of the ac ground (earthing ) electrode system is to establish a ___ reference for ac electrical power systems, whether utility-provided or
customer-derived.
a. 100 mV
b. 0 V
c. 500 mV
d. 1 V
b. 0 V