Unit Review : Refrigeration & AC System Controls Comprehensive Self-Assessment Flashcards
1
Q
1. With the indirect type of temperature-actuated refrigeration control the bulb is installed in the \_\_\_\_\_ while the remainder of the control is located outside in a convenient location. A. Evaporator B. Condenser C. Refrigerator D. Receiver E. Refrigerated space
A
E. Refrigerated space
2
Q
- On larger capacity refrigeration compressors the _____ valves prior to starting.
A. Open the suction and discharge
B. Close the suction and open the discharge
C. Open the suction and close the discharge
D. Close the suction and discharge
E. Open the bypass
A
B. Close the suction and open the discharge
3
Q
- What is the symptom of a refrigeration system when the compressor runs continuously due to a lack of refrigerant?
A. Excessive load
B. Bubbles in the sight glass
C. High discharge pressure
D. Low temperature of substance to be cooled
E. Thermostat set too low
A
B. Bubbles in the sight glass
4
Q
4. The CSA B52 Mechanical Refrigeration Code requires that all refrigeration systems containing more than \_\_\_\_\_ kg of refrigerant and operating above atmospheric pressure shall be equipped with a pressure limiting device. A. 5 kg (11 lb) B. 15 kg (33.1 lb) C. 9 kg (19.8 lb) D. 20 kg (44.1 lb) E. 12 kg (26.4 lb)
A
C. 9 kg (19.8 lb)
5
Q
- The charge of refrigerant in a system with a high-pressure float valve is critical. Too much refrigerant in the evaporator may cause:
A. Vapour to be carried over to the compressor with the liquid
B. Liquid to be carried over to the compressor with the vapour
C. Liquid to be carried over to the condenser with the vapour
D. Vapour to be carried over to the condenser with the liquid
E. Liquid to be carried over to the receiver with the vapour
A
B. Liquid to be carried over to the compressor with the vapour
6
Q
- One of the disadvantages of evaporator capacity control by face damper is that the:
A. Air volume to the space is reduced
B. Refrigerant volume to the space is reduced
C. Temperature of the space is reduced
D. Temperature of the space is increased
E. Refrigerant pressure to the space is reduced
A
A. Air volume to the space is reduced
7
Q
7. An automatic expansion or constant pressure valve is suitable when compressors are controlled by a: A. Pressurestat B. Humidistat C. Thermostat D. Rheostat E. Aquastat
A
C. Thermostat
8
Q
- What is the purpose of the weighted valve pin” used with a high-pressure float valve?
A. Control the flow of refrigerant into the evaporator
B. Control the flow of refrigerant into the condenser
C. Maintain a back pressure in the condenser
D. Control the pressure in the refrigeration system
E. Reduce the amount of line frosting after the float valve
A
E. Reduce the amount of line frosting after the float valve
9
Q
9. The pressure-actuated refrigeration control is actuated by the: A. Discharge pressure of the compressor B. Suction pressure of the condenser C. Discharge pressure of the receiver D. Suction temperature of the compressor E. Suction pressure of the compressor
A
E. Suction pressure of the compressor
10
Q
10. A pressure-actuated refrigeration control cannot be used in conjunction with a/an \_\_\_\_\_ expansion valve A. Automatic B. Thermostatic C. Hand D. Humidity E. Solenoid
A
A. Automatic
11
Q
11. One of the three distinct classes of refrigeration controls is the \_\_\_\_\_ control. A. Temperature actuated B. Actuating or secondary C. Pressure actuated D. Humidity actuated E. Solenoid
A
B. Actuating or secondary
12
Q
- Motor overload protection is a manual reset device that will take the motor itself offline when the current drawn by the motor exceeds:
A. Its minimum allowable value
B. Its maximum allowable value
C. The condenser maximum allowable pressure
D. The evaporator maximum allowable temperature
E. Its maximum allowable oil temperature
A
B. Its maximum allowable value
13
Q
- Why must you avoid running a refrigeration system below 14 KPa when pumping down?
A. A slightly positive system pressure is required to prevent air infiltration
B. Too much refrigerant will be required for a recharge
C. The compressor will need to be stopped to prevent it running dry
D. The systems heat exchangers will ice up
E. The heat exchanges may collapse due to the low pressure
A
A. A slightly positive system pressure is required to prevent air infiltration
14
Q
- What is the symptom of a refrigeration system when the compressor discharge pressure is too high due to the improper operation错误操作of the evaporative condenser?
A. Very hot condenser
B. Fouled tubes in shell and tube condenser
C. Non-condensables in system
D. Overcharge of refrigerant
E. Scaled coil surface
A
E. Scaled coil surface
15
Q
- The low-pressure side is isolated when its minimum design pressure is reached and then the pressurizing gas is admitted to the refrigeration system high-pressure side and increased to the required:
A. High-pressure side minimum design pressure
B. Low-pressure side operating pressure
C. High-pressure side operating pressure
D. Low-pressure side minimum design pressure
E. High-pressure side maximum design pressure
A
A. High-pressure side minimum design pressure