Chapter 24 Refrigeration Cycle Controls Flashcards
1. One of the most important secondary controls in a refrigerating system is the refrigerant flow control used to regulate the amount of liquid refrigerant flowing into the: A. Refrigerator B. Condenser C. Evaporator D. Receiver E. Refrigerated space
C. Evaporator
- The thermostatic refrigeration controller has a range adjustment that sets the
temperature level at which the:
A. Expansion valve opens and closes
B. Level in the evaporator control activates
C. Cut-in and cut-out occurs
D. Condenser cooling water control activates
E. Fan starts and stops
C. Cut-in and cut-out occurs
- The thermostatic refrigeration controller has a differential adjustment that sets the
temperature at which the:
A. Expansion valve opens and closes
B. Level in the evaporator control activates
C. Condenser cooling water control activates
D. Cut-in and cut-out occurs
E. Fan starts and stops
D. Cut-in and cut-out occurs
4. With the direct type of temperature-actuated refrigeration control the thermostat is located directly in the: A. Evaporator B. Condenser C. Refrigerator D. Space to be cooled E. Receive
D. Space to be cooled
5. With the indirect type of temperature-actuated refrigeration control the bulb is installed in the \_\_\_\_\_ while the remainder of the control is located outside in a convenient location. A. Evaporator B. Condenser C. Refrigerator D. Receiver E. Refrigerated space
E. Refrigerated space
- An evaporator pressure regulator prevents _____ conditions from occurring in the
evaporator while the compressor is running.
A. Low pressure and temperature
B. High pressure and temperature
C. Low pressure and high temperature
D. High pressure and low temperature
E. Low pressure and humidity
A. Low pressure and temperature
7. The \_\_\_\_\_ is used in those systems where a drop in temperature below the minimum setting of the operating thermostat could result in damage to the equipment. A. Pressure limiting device B. Low limit thermostat C. Pressure-operated safety switch D. Evaporator pressure regulator E. Solenoid valve
B. Low limit thermostat
- The CSA B52 Mechanical Refrigeration Code requires the pressure limiting device
to be connected between the: CSA B52
A. Compressor and the first stop valve in the suction line
B. Condenser and the first stop valve in the discharge line
C. Evaporator and the first stop valve in the discharge line
D. Condenser and the first stop valve in the suction line
E. Compressor and the first stop valve in the discharge line
E. Compressor and the first stop valve in the discharge line
- The CSA B52 Mechanical Refrigeration Code requires that the pressure limiting
device be designed to stop the action of the compressor or generator at a pressure
not more than _____ of the system high side design pressure.
A. 80%
B. 100%
C. 70%
D. 90%
E. 60%
D. 90%
10.The CSA B52 Mechanical Refrigeration Code requires that all refrigeration
systems containing more than _____ kg of refrigerant and operating above
atmospheric pressure shall be equipped with a pressure limiting device.
A. 5 kg (11 lb)
B. 15 kg (33.1 lb)
C. 9 kg (19.8 lb)
D. 20 kg (44.1 lb)
E. 12 kg (26.4 lb)
C. 9 kg (19.8 lb)
11.The pressure-actuated refrigeration control is actuated by the:
A. Discharge pressure of the compressor B. Suction pressure of the condenser C. Discharge pressure of the receiver D. Suction temperature of the compressor E. Suction pressure of the compressor
E. Suction pressure of the compressor
- The high-pressure safety cutout protects the refrigerating system from higher than normal pressures due to the:
A. Presence of non-condensables in evaporator
B. Presence of non-condensables in the system
C. Loss of refrigerant
D. High compressor oil pressure
E. Presence of refrigerants in the system
B. Presence of non-condensables in the system
13. The high oil temperature cutout is a safety control that shuts down the compressor when the lubricating oil temperature becomes too high due to: A. Loss of refrigerant B. Evaporator high temperature C. Condenser high pressure D. Condenser high temperature E. Loss of oil cooling
E. Loss of oil cooling
- The low oil sump temperature protection device prevents the compressor from starting if the oil temperature falls below a preset value so that:
A. The oil will flow freely
B. The oil viscosity will be low enough
C. Any refrigerant dissolved in the oil is separated from the lubricant.
D. The oil will drain from the condenser
E. The oil will drain from the evaporator
C. Any refrigerant dissolved in the oil is separated from the lubricant.
- The condenser automatic cooling water regulating valve is operated by the:
A. Liquid pressure on the compressor discharge
B. Vapour pressure on the compressor suction
C. Liquid pressure on the compressor suction
D. Vapour pressure on the evaporator discharge
E. Vapour pressure on the compressor discharge
E. Vapour pressure on the compressor discharge