Unit 2: Branch Circuits Flashcards

Learning NEC® requirements for branch circuits, including conductor sizing, overcurrent protection, load calculations, and grounding to ensure safe and code-compliant electrical installations.

1
Q

In general, for other than dwelling units, all 15- and 20-ampere, 125-volt, single-phase receptacles installed on rooftops must be provided with:

I. GFCI protection
II. AFCI protection

A

I only

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Fill in the blank:

Where the motor controller also serves as a disconnecting means, it shall open all _____ conductors to the motor.

A

ungrounded

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Fill in the blank:

Before demand factors are taken into consideration for commercial occupancies, general-purpose 125-volt, single-phase 15- or 20-ampere rated receptacles are to be computed at not less than _____ per duplex or single receptacle outlet mounted on one yoke.

A

180 VA

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Fill in the blank:

Conductors with ____\__ insulation have a greater ampacity when used in a dry location compared to when used in a wet location.

A

THHW

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Fill in the blank:

Where a submersible pump is used in a metal well casing, the well casing shall be _____ the pump circuit equipment grounding conductor.

A

connected to

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Fill in the blank:

In a health care facility, low voltage electrical equipment that is likely to become energized that is frequently in contact with the bodies of patients, shall operate on a voltage of _____ or less if the equipment is not approved as intrinsically safe, double insulated or moisture resistant.

A

10 volts

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Fill in the blank:

When ambient temperature is not a factor, a size 8 AWG single-insulated copper conductor with type FEPB insulation, installed in free air, has an ampacity of _____.

A

80 amperes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Fill in the blank:

For the purpose of determining conductor fill in a device box, a three-way toggle switch is counted as equal to _____ conductor(s), based on the largest conductor connected to the switch.

A

two

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Fill in the blank:

When determining the required ampacity of the branch circuit conductors to supply a 3-phase, continuous duty ac motor, current values given on _____ shall be used.

A

Table 430.250 of the NEC

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

When calculating the total load for a building or structure, what is the minimum computed branch circuit load, in volt-amps, permitted by the NEC for a branch circuit serving an exterior continuous-duty electric sign?

A

1,500 volt-amps

1,200 VA x 125% = 1,500 VA

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Determine the maximum number of size 1 AWG XHHW copper conductors permitted in a trade size 3 in. Schedule 40 rigid PVC conduit more than 24 inches long.

A

19

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Fill in the blank:

Infrared commercial and industrial heating appliances shall have overcurrent protection not exceeding _____.

A

50 amperes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Fill in the blank:

Class _____ hazardous locations are those in which flammable liquidproduced vapors, or combustible liquid-produced vapors are or may be present in the air in quantities sufficient to produce explosive or ignitable mixtures.

A

I

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Fill in the blank:

In indoor areas where walls are frequently washed, such as laundries or car washes, metallic conduit and metallic panelboards shall be mounted with a _____ space between the wall and conduit or panelboard when the equipment is installed exposed.

A

1/4 in.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Fill in the blank:

A branch circuit served by size 12 AWG conductors is a _____ rated branch circuit when protected by a 15-ampere circuit breaker.

A

15 ampere

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What is the maximum overcurrent protection allowed for the protection of resistance-type fixed electric space heating equipment?

A

60 amperes

17
Q

Fill in the blank:

Information technology equipment shall be permitted to be connected to a branch circuit by a listed power-supply cord having a length not to exceed _____.

18
Q

Fill in the blank:

Type MI cable shall be supported and secured by straps, staples or similar fittings at intervals not exceeding _____.

19
Q

Fill in the blank:

General use snap switches supplying inductive loads shall be loaded to no more than _____ of the ampere rating of the switch at the applied voltage.

A

50 percent

20
Q

Fill in the blank:

Direct-buried conductors emerging from grade shall be protected by raceways or covers up to a point of at least _____ above finished grade.

21
Q

What is the required size wire-type copper equipment grounding conductor for a 50-ampere rated branch circuit where the conductors are installed in PVC conduit?

22
Q

Fill in the blank:

Disregarding exceptions, all 3-phase, 4-wire, 480Y/277-volt, electrical services, require ground-fault protection for each service disconnecting means, when rated for at least _____ or more.

A

1,000 amperes

23
Q

Determine the conductor ampacity given the following related information:
* conductors are size 500 kcmil copper
* conductor insulation is THWN
* eight (8) current-carrying conductors are in the raceway
* ambient temperature is 125 deg. F
* conduit length is 50 feet
* installation is a wet location

A

178.2 amperes

Size 500 KCMIL THWN copper ampacity before derating = 380 amperes

380 amperes x .67 (temp. correction) x .7 (adjustment factor) = 178.22 amperes

24
Q

Fill in the blank:

When connecting to luminaires, trade size 3/8 in. flexible metal conduit (FMC) is permitted to enclose tap conductors, provided the length of the FMC does not exceed _____.

25
# Fill in the blank: Where a trade size 1/2 in. rigid metal conduit (RMC) is installed in a Class I location and a 1/2 in. conduit completed seal is required, the minimum thickness of the sealing compound shall not be less than \_\_\_\_\_.
5/8 in.