Fill in the blank:
All single-phase, 125-volt 15- and 20-ampere rated receptacles located within _____ of the inside walls of a storable pool, storable spa, or storable hot tub shall be provided with GFCI protection.
20 feet
What is the MAXIMUM length permitted for flexible cord used to supply an electrically operated insink kitchen waste disposer?
36 inches
Fill in the blank:
Type AC cable installed horizontally through wooden or metal framing members is considered supported and secured where such support doesn’t exceed _____ intervals.
4 1⁄2 feet
Fill in the blank:
At least one 15- or 20-ampere, 125-volt, single-phase receptacle outlet NOT more than _____ above a balcony, deck, or porch walking surface shall be installed at each balcony, deck, or porch that is within 4 in. horizontally or attached to a dwelling and accessible from the dwelling unit.
6 1⁄2 feet
Fill in the blank:
Where raceways contain _____ or larger insulated circuit conductors and these conductors enter a raceway in a cabinet, the conductors shall be protected from abrasion by a smoothly rounded insulating surface such as a bushing.
4 AWG
Fill in the blank:
The lightning protection system ground terminals shall be bonded to the building or structure grounding electrode system. The bonding shall be _____ and to all raceways, boxes, and enclosures between the cabinets or equipment and the grounding electrode.
bonded at both ends
Fill in the blank:
When switching luminaires with three-way and four-way switches, the switches shall be wired so that all switching is done only in the _____ conductor.
ungrounded
Fill in the blank:
The service conductors between the terminals of the service equipment and a point usually outside the building, clear of building walls, where joined by splice or tap to the service drop or overhead service conductors are recognized as _____.
service entrance conductors
What is the ampacity (current-carrying capacity) of a size 10 AWG, THHN CU conductor when there are a total of four (4) current-carrying conductors in a raceway? Assume all terminations are rated 75°C.
32 amperes
10 AWG THHN ampacity before adjusting (90°C column) = 40 amperes
40 amperes x .8 (adjustment factor) = 32 amperes ampacity
However, according to 240.4(D)(7) the overcurrent
protection is limited to 30 amperes
Fill in the blank:
Additional services shall be permitted for a single building or other structure sufficiently large to make two (2) or more services necessary if permitted by _____.
special permission
Fill in the blank:
Branch circuits that supply electric signs shall be considered _____ loads for the purposes of calculations.
continuous
Fill in the blank:
Where a ground ring is used as a grounding electrode consisting of a size 2 AWG bare copper conductor encircling a building, buried 36 in. deep, in direct contact with the earth, the conductor is required to have a MINIMUM length of _____.
20 feet
Fill in the blank:
For low voltage lighting systems operating at 30 volts or less, the output circuits of the power supply are to be rated for NOT more than _____ under all load conditions.
25 amperes
Fill in the blank:
Any connections or splices in an underground installation shall be approved for such locations, and the NEC® defines an underground installation, such as the interior surface of enclosures or raceways that are installed underground are considered a _____ location.
wet
What is the horsepower rating of a single-phase, 120-volt ac motor that draws 9.8 amperes of current?
1⁄2 hp
Fill in the blank:
For installations of resistors and reactors, a thermal barrier shall be required if the space between them and any combustible material is LESS than _____.
12 inches
Given: A trade size 3 in. electrical metallic tubing (EMT) will enter the bottom of a pull box and a trade size 3 in. flexible metal conduit (FMC) will enter the side of the box; the raceways will contain conductors of size 4 AWG or larger. What MINIMUM size pull box is required for this installation?
18 in. x 18 in
3 inches (raceway) x 6 = 18 inches
Fill in the blank:
The service equipment for a mobile home is not permitted to be located in or on the exterior wall of the mobile home however, the service equipment shall be located in sight and NOT more than _____ from the exterior wall of the mobile home it serves.
50 feet
Fill in the blanks:
For legally required standby systems, storage batteries and UPS used to supply emergency lighting shall have the
capacity to supply and maintain the total load for a minimum period of _____, without the voltage applied to the load falling below _____ of normal.
11⁄2 hours, 871⁄2 percent
Fill in the blank:
A size 10 AWG flexible Type SJ cord shall be permitted for _____.
a maximum of 300 volts
Fill in the blank:
All hydromassage bathtub metal piping systems and all grounded metal parts in contact with the circulating water associated with the bathtub shall be bonded together using a solid copper bonding jumper NOT smaller than _____.
8 AWG
Fill in the blank:
Where a 125-volt, single-phase, 20-ampere receptacle is install in a residential laundry area, designated for the washing machine, the receptacle must be provided with _____.
both AFCI and GFCI protection
Fill in the blank:
According to the NEC® the required MINIMUM burial depth of a direct burial cable run of a GFCI protected, 15-ampere, 120-volt circuit, where the cable passes directly under the residential driveway is _____.
12 inches
Fill in the blank:
Where practical, conductors of dissimilar metals shall _____ in a terminal or splicing connector.
not be intermixed