Dry bulb temp
Temp of air
Wet bulb temp
Temperature of the air measured with a glass bulb covered with a wet cloth
Relative humidity
Actual amount of moisture in the air compared to the total or maximum moisture the air can hold
Grains of moisture
Unit of measure used to determine the amount of moisture in the air
Dew point temp
Temperature at which moisture condenses on a surface
How many grains of moisture in 1 LB of water
7000
Mass flow rate unit
LB/hr
Enthalpy unit of measure
Btu/Lb
BTU capacity formula
Mass Flow Rate X delta H (change in enthalpy)
Mass flow rate formula
Cfm x Specific Density x 60
= lb/hr
Q sensible formula
1.08 x cfm x delta T
Air heat capacity formula
Mass Flow Rate x delta H
= BTU/H
Or
4.5 x cfm x delta H
Economizer open% formula
Return air - mixed air
—————
Return air - outside air
Coil bypass factor formula
Leaving air - coil temp
____________
Entering air - coil temp
Sensible heat factor formula
Sensible heat quantity
____________
Total heat quantity
What is more dense, dry air or moist air
Dry air
Where is the vapor barrier placed
On warmest wall
Total pressure formula
Static + velocity
Pitot tube ports give what measurements on the side and bottom
Side port is static
Bottom port is total
Velocity (ft/min) formula
4005 x (square root of velocity pressure)
Cross sectional area of round duct
3.14 x (radius squared)
Total external static pressure formula (furnaces)
Supply static just before coil - return static right after filter
CFM fan laws
RPM 2/RPM1 = CFM2/CFM1
Double RPM -= double CFM
Static pressure fan laws
(RPM2/RPM1)squares = SP2/SP1
Double RPM = 4 x static
HP fan laws
(RPM2/RPM1)cubed = HP2/HP1
Double RPM = 8 x HP
Fan driver and sheave relationship
RPM driver x diameter of driver (motor)
RPM driven x diameter driven (fan)
2 main main fan classifications
Propeller and axial
3 main centrifugal fan types
1) Forward curve
2) Backward inclined
3) Radial or straight blade
Forward curve fan application
Furnace or small to medium RTU
Pros of forward curve fan (3)
Low speed
Quiet
Light inexpensive construction