Dom Class Flashcards
Vibersorbers installed…
- Parallel to crankshaft,
- highest probability of leak location
- Not used on hermetic compressors
Receiver charge
Must hold 90% of charge at 90F
Minimum 10% full at any time
Winter charge
Additional charge for receivers due to low ambient condition
Heat pump filter driers
Special non directional
Filter drier Sight glass location
Immediately after filter drier to indicate full column of liquid. Especially when evap is at higher elevation than condensor
LLSV always after filter drier, why?
Keeps filter drier on high side, prevents impurities from escaping during pump down
Txv outlet position
Always up
What type of txv is needed to eliminate the need for a CPR
Pressure limiting txv
Where to discharge air on pull through evaporator
Towards opening to prevent air infiltration
Another name for push through evaporator and location
Low velocity, center of room HIGH HUMIDITY (flowers)
Suction line solenoids, location, application and purpose
After EPR, large case with critical set points, used to avoid excessive pressure drops
Accumulator location and and sizing
Close as possible to inlet. Sized based on tonnage of system
When should you insulate Accumulators
Outdoors only, intent is to boil off remaining liquid refrigerant, insulated indoor could prevent this
CPR location
Close as possible to compressor after accumulator
Max temp before damage to compressor occurs
135F
Head pressure control methods (3)
Fan cycling
Fan speed control
Condensor flooding
Fan cycling monitors what and is most used on what system
Monitors discharge pressure or temperature
Most used on cap tube system
Two types of fan speed controls
VFD and ECM motors
Insulation thickness for freezer
3/4 or greater
Dom test said 5/8
Insulation thickness for cooler
1/2 inch or greater
High temp ac insulation thickness
3/8” or greater
Copeland unloading
Suction port is C OPE(n)lan D(energized) Unloading Copeland uses discharge as closing force Copelan(D) Carlyle uses electromagnet to close valves Carlyl(E)
Suction lift unloading
Coil energized, oil pressure lifts lever, loads compressor cylinder
Uses oil pump
Ideal evap Temperature Difference
8-10F
Importance of proper evap TD
Too high = frost build up
Easiest method of defrost
Manual defrost
Types of defrost methods (5 types)
Manual frost removal
Manual defrost
Off cycle defrost
Timed shut down
SUPPLEMENTARY DEFROST Water defrost Brine spray defrost Electric defrost Vapor defrost
Temperature operated defrost setting
35F cut it, 22F cut out
Accumulator sizing during hot gas bypass conventional flow (3 pipe system)
1.5 times system
3 pipe HGBP with re evaporator
Suction line Solenoid position and purpose during normal operation
Open to prevent excessive pressure drop
Max temp difference across 4 way valve
5F
Purpose of DPRV
Maintain pressure difference to ensure flow of refrigerant
Fin spacing colder vs warmer evap
Wider in colder
Closer on warmer
Manual frost removal equipment status
Running
Cooler application evap fan run time
24hrs