Ts Flashcards

1
Q

List Flux Trips

A
PR Hi Flux
PR Low Flux
PR Flux Rate
IR Flux
SR Flux
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

List DNB Trips

A
OTdeltaT
PZR Low Pressure
RCS Low Flow
RCP UV
RCP UF
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

List Overtemperature Trips

A

OPdeltaT
PZR High Pressure
PZR High Level

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

List undercooling Trips

A

S/G Low Level

C-8 (Turbine Trip)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

List SI Trips

A

Manual
Containment Pressure Hi (Hi-1)
PZR Low Pressure
Steam Low Pressure

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

PR Hi Flux

Setpoints, Coincidences, Blocks

A

Setpoint - 109%
Coincidence - 2/4
Blocks - N/A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

PR Low Flux

Setpoints, Coincidences, Blocks

A

Setpoint - 25%
Coincidence - 2/4
Block - P-10(PR Low Flux Trip Block Permissive) True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

PR High Flux Rate

Setpoints, Coincidences, Blocks

A

Setpoint - 5%RTP/2Sec
Coincidence - 2/4
Block - N/A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

IR Flux

Setpoints, Coincidences, Blocks

A

Setpoint - 25%Equivalent Amps
Coincidence - 1/2
Blocks - P-10(PR Low Flux Trip Block Permissive) True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

SR Flux

Setpoints, Coincidences, Blocks

A

Setpoint - 1e5CPS
Coincidence - 1/2
Blocks - P-6(SR Trip Block Permissive) True
P-10(PR Low Flux Trip Block Permissive) True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

OTdeltaT

Setpoints, Coincidences, Blocks

A

Setpoint - 114%(+/- Penalties)
Coincidence - 2/4
Blocks - N/A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

PZR Low Pressure

Setpoints, Coincidences, Blocks

A

Setpoint - 1870PSIG
Coincidence - 2/4
Block - P-7(At-Power Trip Permissive) False

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

RCS Low Flow

Setpoints, Coincidences, Blocks

A

Setpoint - 91.8%
Coincidences - P-8(Single Loop Loss of Flow Permissive) True 2/3 on 2/4
P-8(Single Loop Loss of Flow Permissive) False 2/3 on 1/4
Block - P-7(At-Power Trip Permissive) False

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

RCP UV

Setpoints, Coincidences, Blocks

A

Setpoint - 72.6%(10014V) for 1.5Sec
Coincidence - 2/4
Block - P-7(At-Power Trip Permissive) False

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

RCP UF

Setpoints, Coincidences, Blocks

A

Setpoint - 57.2Hz
Coincidence - 2/4
Block - N/A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

OPdeltaT

Setpoints, Coincidences, Blocks

A

Setpoint - 108%( - Penalties)
Coincidence - 2/4
Block - N/A

17
Q

PZR High Pressure

Setpoints, Coincidences, Blocks

A

Setpoint - 2380PSIG
Coincidence - 2/4
Block - N/A

18
Q

PZR High Level

Setpoints, Coincidences, Blocks

A

Setpoint - 92%
Coincidence - 2/4
Block - P-7(At-Power Trip Permissive) False

19
Q

S/G Low Level

Setpoints, Coincidences, Blocks

A

Setpoint - 20%
Coincidence - 2/4 on 1/4 S/Gs
Block - N/A

20
Q

C-8(Turbine Trip)

Setpoints, Coincidences, Blocks

A

Setpoint - EH Pressure <1245PSIG or TV Closed
Coincidence - 2/3 or 2/4
Block - P-9(Turbine Trip to Rx Trip) False