Ps Flashcards

1
Q

P-4(Rx trip breakers open)

Inputs, Setpoints, and Coincidence

A

Input - Rx trip breakers and Rx trip bypass breakers
Setpoint - open and open
Coincidence - 2/2 and 2/2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

P-6(SR Trip Block Permissive)

Inputs, Setpoints, and Coincidence

A

Input - IR NIS
Setpoint - >1e-10Amps
Coincidence - 1/2 Increasing or 2/2 Decreasing

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

P-7(At-Power Trip Permissive)

Inputs, Setpoints, and Coincidence

A

Inputs - P-10(PR Low Flux Trip Block Permissive) or P-13(Turbine At-Power Trip Permissive)

Setpoints - N/A

Coincidence - N/A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

P-8(Single Loop Low Flow Permissive)

Inputs, Setpoints, and Coincidence

A

Input - PR NIS
Setpoint - <40%
Coincidence - 2/4 Increasing or 3/4 Decreasing

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

P-9(Turbine Trip to Rx Trip)

Inputs, Setpoints, and Coincidence

A

Input - PR NIS
Setpoint - >50%
Coincidence - 2/4 Increasing or 3/4 Decreasing

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

P-10(PR Low Flux Trip Block Permissive)

Inputs, Setpoints, and Coincidence

A

Input - PR NIS
Setpoint - >10%
Coincidence - 2/4 Increasing or 3/4 Decreasing

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

P-11(Low Pressure SI/SLI Block Permissive)

Inputs, Setpoints, and Coincidence

A

Input - PZR Pressure
Setpoint - <1985PSIG
Coincidence - 1/3 Increasing or 2/3 Decreasing

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

P-12(Low Tave Steam Dump Permissive)

Inputs, Setpoints, and Coincidence

A

Input - Tave
Setpoint - <563F
Coincidence - 2/4

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

P-13(Turbine At-Power Trip Permissive)

Inputs, Setpoints, and Coincidence

A

Input - Impulse/Inlet Pressure
Setpoint - >10%
Coincidence - 1/2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

P-14(SG HI Level Trip)

Inputs, Setpoints, and Coincidence

A

Input - SG Level
Setpoint - >87.5%
Coincidence - 2/4 for 1/4 S/Gs

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

P-16(Rx Trip to Turbine Trip)

Inputs, Setpoints, and Coincidence

A

Input - P-4(Rx Trip Breakers Open) or SSPS
Setpoint - True
Coincidence - N/A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

P-4(Rx Trip Breakers Open)

Functions(When True)

A

Turbine Trip
Allows FWI on Low Tave(<574F)
Allow Block and Reset of SI
Closes S/G Blowdown if SR Flux Trip is Blocked

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

P-6(SR Trip Block Permissive)

Functions(When True)

A

Blocks Rx Trip(Auto Unblock)

SR High Flux Trip

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

P-7(At-Power Trip Permissive)

Functions(When True)

A
Allows Following Rx Trips:
PZR Low Pressure
PZR High Level
RCS Low Flow
RCP UV/UF
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

P-8(Single Loop Loss of Flow Permissive)

Functions(When True)

A

Blocks Rx Trip:

RCS Low Flow in any Single Loop

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

P-9(Turbine Trip to Rx Trip)

Functions(When True)

A
Allows Rx Trip:
Turbine Trip(C-8)
17
Q

P-11(Low Pressure SI/SLI Block Permissive)

Functions(When True)

A

Allows Blocks:
PZR Low Pressure SI
S/G Low Pressure SI
Allows Closure of SI Accumulator Outlet Valves on Reset(Provides Open signal to valves)

18
Q

P-12(Low Tave Steam Dump Permissive)

Functions(When True)

A

Blocks Steam Dump operations

Vents air from steam dump operators

19
Q

P-13(Turbine At-Power Trip Permissive)

Functions(When True)

A

Input to P-7(At-Power Trip Permissive)

20
Q

P-10(PR Low Flux Trip Block Permissive)

Functions(When True)

A
Allows Block of IR High Flux Rod Stop(C-1)
Allows Block of PR Flux(Low SP) Trip
Backup to P-6(SR Trip Block Permissive)
Removes SR Power
Input to P-7(At-Power Trip Permissive)
21
Q

P-14(S/G HI Level Trip)

Functions(When True)

A

Trips Main Turbine
Trips SGFWP Turbines
Trips SUFP
FWI on P-4(Rx Trip Breakers Open)

22
Q

P-16(Rx Trip to Turbine Trip)

Functions(When True)

A

Trips Main Turbine