P-4(Rx trip breakers open)
Inputs, Setpoints, and Coincidence
Input - Rx trip breakers and Rx trip bypass breakers
Setpoint - open and open
Coincidence - 2/2 and 2/2
P-6(SR Trip Block Permissive)
Inputs, Setpoints, and Coincidence
Input - IR NIS
Setpoint - >1e-10Amps
Coincidence - 1/2 Increasing or 2/2 Decreasing
P-7(At-Power Trip Permissive)
Inputs, Setpoints, and Coincidence
Inputs - P-10(PR Low Flux Trip Block Permissive) or P-13(Turbine At-Power Trip Permissive)
Setpoints - N/A
Coincidence - N/A
P-8(Single Loop Low Flow Permissive)
Inputs, Setpoints, and Coincidence
Input - PR NIS
Setpoint - <40%
Coincidence - 2/4 Increasing or 3/4 Decreasing
P-9(Turbine Trip to Rx Trip)
Inputs, Setpoints, and Coincidence
Input - PR NIS
Setpoint - >50%
Coincidence - 2/4 Increasing or 3/4 Decreasing
P-10(PR Low Flux Trip Block Permissive)
Inputs, Setpoints, and Coincidence
Input - PR NIS
Setpoint - >10%
Coincidence - 2/4 Increasing or 3/4 Decreasing
P-11(Low Pressure SI/SLI Block Permissive)
Inputs, Setpoints, and Coincidence
Input - PZR Pressure
Setpoint - <1985PSIG
Coincidence - 1/3 Increasing or 2/3 Decreasing
P-12(Low Tave Steam Dump Permissive)
Inputs, Setpoints, and Coincidence
Input - Tave
Setpoint - <563F
Coincidence - 2/4
P-13(Turbine At-Power Trip Permissive)
Inputs, Setpoints, and Coincidence
Input - Impulse/Inlet Pressure
Setpoint - >10%
Coincidence - 1/2
P-14(SG HI Level Trip)
Inputs, Setpoints, and Coincidence
Input - SG Level
Setpoint - >87.5%
Coincidence - 2/4 for 1/4 S/Gs
P-16(Rx Trip to Turbine Trip)
Inputs, Setpoints, and Coincidence
Input - P-4(Rx Trip Breakers Open) or SSPS
Setpoint - True
Coincidence - N/A
P-4(Rx Trip Breakers Open)
Functions(When True)
Turbine Trip
Allows FWI on Low Tave(<574F)
Allow Block and Reset of SI
Closes S/G Blowdown if SR Flux Trip is Blocked
P-6(SR Trip Block Permissive)
Functions(When True)
Blocks Rx Trip(Auto Unblock)
SR High Flux Trip
P-7(At-Power Trip Permissive)
Functions(When True)
Allows Following Rx Trips: PZR Low Pressure PZR High Level RCS Low Flow RCP UV/UF
P-8(Single Loop Loss of Flow Permissive)
Functions(When True)
Blocks Rx Trip:
RCS Low Flow in any Single Loop
P-9(Turbine Trip to Rx Trip)
Functions(When True)
Allows Rx Trip: Turbine Trip(C-8)
P-11(Low Pressure SI/SLI Block Permissive)
Functions(When True)
Allows Blocks:
PZR Low Pressure SI
S/G Low Pressure SI
Allows Closure of SI Accumulator Outlet Valves on Reset(Provides Open signal to valves)
P-12(Low Tave Steam Dump Permissive)
Functions(When True)
Blocks Steam Dump operations
Vents air from steam dump operators
P-13(Turbine At-Power Trip Permissive)
Functions(When True)
Input to P-7(At-Power Trip Permissive)
P-10(PR Low Flux Trip Block Permissive)
Functions(When True)
Allows Block of IR High Flux Rod Stop(C-1) Allows Block of PR Flux(Low SP) Trip Backup to P-6(SR Trip Block Permissive) Removes SR Power Input to P-7(At-Power Trip Permissive)
P-14(S/G HI Level Trip)
Functions(When True)
Trips Main Turbine
Trips SGFWP Turbines
Trips SUFP
FWI on P-4(Rx Trip Breakers Open)
P-16(Rx Trip to Turbine Trip)
Functions(When True)
Trips Main Turbine