Cs Flashcards

1
Q

C-1(IR HI Flux Rod Stop)

Inputs, Setpoints, and Coincidence

A

Input - IR NIS
Setpoint - >20%
Coincidence - 1/2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

C-2(PR HI Flux Rod Stop)

Inputs, Setpoints, and Coincidence

A

Input - PR NIS
Setpoint - >103%
Coincidence - 1/4

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

C-3(OTdeltaT Rod Stop)

Inputs, Setpoints, and Coincidence

A

Input - PR NIS/Tave/PZR Pressure
Setpoint - <1.5% of setpoint
Coincidence - 2/4

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

C-4(OPdeltaT Rod Stop)

Inputs, Setpoints, and Coincidence

A

Input - PR NIS/Tave/PZR Pressure
Setpoint - <1.5% of setpoint
Coincidence - 2/4

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

C-5(Low Turbine Impulse Pressure Rod Stop)

Inputs, Setpoints, and Coincidence

A

Input - Impulse Pressure( Unit 2 PT-505)
*Inlet Pressure(Unit 1 ONLY uses average of PT-505/506 or average of PT-7483/7484 as selected)
Setpoint - <15%
Coincidence - 1/1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

C-7(Steam Dump Load Rejection)

Inputs, Setpoints, and Coincidence

A

Input - Impulse Pressure( Unit 2 PT-506)
*Inlet Pressure(Unit 1 ONLY average of PT-7483/7484)
Setpoint - >10% Step load loss or >5%/Min load loss
Coincidence - 1/1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

C-8(Turbine Trip)

Inputs, Setpoints, and Coincidence

A

Input - EH Pressure or TV Valves
Setpoint - <1245.8PSIG or TV Closed
Coincidence - 2/3 or 2/4

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

C-9(Condenser Available for Steam Dumps)

Inputs, Setpoints, and Coincidence

A

Input - Condenser Vacuum and CW Breaker
Setpoint - >22”HG and >1 CW Breaker Closed
Coincidence - 2/3 and 1/4

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

C-11(Top Rod Stop)

Inputs, Setpoints, and Coincidence

A

Input - CR Bank D
Setpoint - >248 Steps
Coincidence - N/A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

C-17(Stop Turbine Loading)

Inputs, Setpoints, and Coincidence

A

Input - Lo-Tave17F or <563F

Coincidence - N/A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

C-20(AMSAC Armed)

Inputs, Setpoints, and Coincidence

A

Input - Impulse Pressure
Setpoint - >30%
Coincidence - 2/2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

C-1(IR HI Flux Rod Stop)

Function(When True)

A

Stops ALL Rod OUT Motion

*Blocked by P-10(PR Low Flux Trip Block Permissive)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

C-2(PR HI Flux Rod Stop)

Function(When True)

A

Stops ALL Rod OUT Motion

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

C-3(OTdeltaT Rod Stop)

Function(When True)

A

Stops ALL Rod OUT Motion

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

C-4(OPdeltaT Rod Stop)

Function(When True)

A

Stops ALL Rod OUT Motion

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

C-5(Low Turbine Impulse Pressure Rod Stop)

Function(When True)

A

Stops AUTO Rod OUT Motion

17
Q

C-7(Steam Dump Load Rejection)

Function(When True)

A

Arms Steam Dumps in Load Reject Mode C-9(Condenser Available for Steam Dumps) True
Tave Mode with Variable Setpoint for Load

18
Q

C-8(Turbine Trip)

Function(When True)

A

Rx Trip P-9(Turbine Trip to Rx Trip) True
Main Generator Trip
Arm Steam Dumps in Trip Mode
Tave Mode with setpoint of No Load: 567F

19
Q

C-9(Condenser Available for Steam Dumps)

Function(When True)

A

Allows Steam Dump Operation

20
Q

C-11(Top Rod Stop)

Function(When True)

A

Stops AUTO Rod OUT Motion

21
Q

C-17(Stop Turbine Loading)

Function(When True)

A

Blocks Raising Turbine Load

22
Q

C-20(AMSAC Armed)

Function(When True)

A

Arms AMSAC