C-1(IR HI Flux Rod Stop)
Inputs, Setpoints, and Coincidence
Input - IR NIS
Setpoint - >20%
Coincidence - 1/2
C-2(PR HI Flux Rod Stop)
Inputs, Setpoints, and Coincidence
Input - PR NIS
Setpoint - >103%
Coincidence - 1/4
C-3(OTdeltaT Rod Stop)
Inputs, Setpoints, and Coincidence
Input - PR NIS/Tave/PZR Pressure
Setpoint - <1.5% of setpoint
Coincidence - 2/4
C-4(OPdeltaT Rod Stop)
Inputs, Setpoints, and Coincidence
Input - PR NIS/Tave/PZR Pressure
Setpoint - <1.5% of setpoint
Coincidence - 2/4
C-5(Low Turbine Impulse Pressure Rod Stop)
Inputs, Setpoints, and Coincidence
Input - Impulse Pressure( Unit 2 PT-505)
*Inlet Pressure(Unit 1 ONLY uses average of PT-505/506 or average of PT-7483/7484 as selected)
Setpoint - <15%
Coincidence - 1/1
C-7(Steam Dump Load Rejection)
Inputs, Setpoints, and Coincidence
Input - Impulse Pressure( Unit 2 PT-506)
*Inlet Pressure(Unit 1 ONLY average of PT-7483/7484)
Setpoint - >10% Step load loss or >5%/Min load loss
Coincidence - 1/1
C-8(Turbine Trip)
Inputs, Setpoints, and Coincidence
Input - EH Pressure or TV Valves
Setpoint - <1245.8PSIG or TV Closed
Coincidence - 2/3 or 2/4
C-9(Condenser Available for Steam Dumps)
Inputs, Setpoints, and Coincidence
Input - Condenser Vacuum and CW Breaker
Setpoint - >22”HG and >1 CW Breaker Closed
Coincidence - 2/3 and 1/4
C-11(Top Rod Stop)
Inputs, Setpoints, and Coincidence
Input - CR Bank D
Setpoint - >248 Steps
Coincidence - N/A
C-17(Stop Turbine Loading)
Inputs, Setpoints, and Coincidence
Input - Lo-Tave17F or <563F
Coincidence - N/A
C-20(AMSAC Armed)
Inputs, Setpoints, and Coincidence
Input - Impulse Pressure
Setpoint - >30%
Coincidence - 2/2
C-1(IR HI Flux Rod Stop)
Function(When True)
Stops ALL Rod OUT Motion
*Blocked by P-10(PR Low Flux Trip Block Permissive)
C-2(PR HI Flux Rod Stop)
Function(When True)
Stops ALL Rod OUT Motion
C-3(OTdeltaT Rod Stop)
Function(When True)
Stops ALL Rod OUT Motion
C-4(OPdeltaT Rod Stop)
Function(When True)
Stops ALL Rod OUT Motion