Your supervisor has made you aware of a turbine that has gone offline/out of operation. How do you go about troubleshooting?
A
- Log onto the turbine through VOT interface.
- Note alarm ID and refer to the “Alarms and Warnings” document.
- Gives information on fault I.e. Safety circuit/Control circuit/Devices.
- Refer to the Schematics and find the relevant circuit, giving information of devices, cabinets, RDSPP codes etc.
- Identify potential devices to test when on WTG and take spares.
2
Q
When on the turbine at a fault that you have previously investigated, what process would you follow to further identify the issue?
A
- Inspect the suspected area/circuit for obvious signs, such as…
- Visual damage
- Abnormal smells
- Strange noises
- Heat
- Depending on the device/circuitry, test it is getting voltage/flow when it should be.
- Test the device for manual operation.
- Test fuses/wiring for continuity.