Transformers III Flashcards
A(n) ? is an explosion that occurs when the surrounding air becomes ionized and conductive.
Select one:
a.
arc blast
b.
ground fault
c.
main bonding jumper
d.
voltage spike
A
A(n) ? is a short circuit through air.
Select one:
a.
arc blast
b.
arc flash
c.
voltage spike
d.
voltage surge
B
? specifically addresses “electrical safety requirements for employee workplaces that are necessary for the safeguarding of employees in their pursuit of gainful employment”.
Select one:
a.
ANSI Z535.4
b.
IEEE Standard 1584-2002
c.
NFPA 70E
d.
OSHA Part 1910.333
C
The Occupational Safety and Health Administration is a federal agency that requires all employers to provide a safe environment for their employees.
Select one:
True
False
True
A control transformer should never be protected on both the primary and the secondary.
Select one:
True
False
True
A(n) ? is a method of wiring transformers where the windings are divided over several legs of transformer core.
Select one:
a.
double-delta connection
b.
interconnected wye connection
c.
T-connection
d.
zigzag connection
D
A ? is two or more transformers wired in parallel that carry a common load.
Select one:
a.
double-delta connection
b.
parallel connection
c.
Scott connection
d.
T-connection
B
A(n) ? is a low-cost method of wiring two transformers to provide 3-phase power.
Select one:
a.
double-delta connection
b.
interconnected wye connection
c.
Scott connection
d.
T-connection
D
A ? is a power supply consisting of two phases that are 90° out-of-phase.
Select one:
a.
2-phase system
b.
double-delta connection
c.
Scott connection
d.
Scott system
A
A 3-phase to 3-phase transformer connection without taps can be divided into one of three groups with angular displacements of ? .
Select one:
a.
0°, 30°, or 90°
b.
0°, 30°, or 180°
c.
30°, 60°, or 90°
d.
30°, 60°, or 180°
B
Which of the following is not a consideration involved in selecting an appropriate transformer?
Select one:
a.
The permitted noise level
b.
The present and future loads
c.
The required and available cooling and ventilation
d.
The requirements for the primary and secondary voltages
e.
The time required to install the transformer
E
Note: There are additional considerations:
- A two-winding transformer, autotransformer, or buck-boost transformer
- Single-phase or 3-phase
- To be used for step up, step down, or isolation
What is the full load primary current of a 3-phase 15-kilovolt-ampere dry-type transformer at 480 volts?
18 A
(KVA X 1000)/(V X 1.73)
(15 X 1000)/(480 X 1.73) = 18A
What is the full load secondary current of a 3-phase 75-kilovolt-ampere dry-type transformer at 600 volts?
72A
(KVA X 1000)/(V X 1.73)
(75 X 1000)/(600 X 1.73 = 72A
The ? is the ratio of the 10-minute reading to the 1-minute reading taken on a dielectric absorption test.
Select one:
a.
dissipation factor
b.
insulation power factor
c.
polarization index
d.
turns ratio
C
Insulating mineral oil is lighter than water.
Select one:
True
False
True