What cast iron item is not allowed on a high-pressure boiler?
Nozzles or flanges
When piping up a boiler gauge glass to a water tube boiler, the lowest visible part of the Water gauge glass shall be at least how many inches above the lowest permissible water level (determined by the boiler manufacturer?)
2
The ASME high pressure boiler code limits the use of non-ferrous valves. What is the limitation for 250 psi class bronze threaded gate valve?
406°F
All gage glass connections shall not be less than what size pipe?
1/2”
The ASME high pressure boiler code says that non-ferrous pipe or tubes shall not be used in the boiler proper for any service where the temperature exceeds how many degrees?
406°F
Gage glass drains shall have an unrestricted drain opening of not less than _______ inch.
1/4
When two or more high pressure boilers are connected to a common steam header, the connection from each boiler having a manhole opening shall be fitted with,
Two stop valves having an ample free-blow drain between them
For high pressure boilers having a water heating surface of more than 100 sq. ft of heating surface the feed connection to the boiler shall not be smaller than what pipe size?
3/4
ASME B.31.1 Power piping code limits the size of slip-on flanges to be used for boiler external piping. The size limitation is what pipe size in diameter?
4
A slow- opening valve requires how many complete turns to be fully opened or closed?
5
The ASME power piping code B31.1 limits the size of ANSI class 600 socket welded for use in boiler external piping. Choose the maximum size limitation.
3
According to the ASME high pressure boiler code, a boiler that has more than how many square feet of heating surface must have two or more safety valves?
500
ASME B31.1 power piping code part 6 boiler external piping requires the attachment of slip on flanges shall be of what type of welds
Double fillet
The steam and water connections to a water column or a water gage glass on a high-pressure boiler shall be such that they?
Readily accessible for internal inspection and cleaning
ASME B31.1 Power piping code requires that boiler blow-off fittings shall be steel and
pressure exceeds what pressure (psi)?
the thickness of pipe and fittings shall not
100