What types of connections are allowed on boilers?
Tapped (threaded) bolted flange or welded (socket or butt) but not victaulic
What are the minimum connections for feed water piping in power boilers?
Less than or equal to 100 sq. ft water heating surface ½ “NPS
Greater than 100 sq. ft water heating surface ¾” NPS
1 Q
What is hanger spacing on 6 inch pipe?
Water -
Gas -
Water — 17
Gas — 21
3Q
What is required when pressure in the discharge pipe can exceed pressure in the inlet pipe?
A check valve in the discharge line
5 Q
Why does each gauge connection need a syphon (pigtail)?
To develop and maintain a water seal that will prevent steam from entering the gauge tube
11 Q
At what size must hangers be designed to permit adjustment while supporting load?
Greater or equal to 2 1/2 inches
48 Q
What is the common length that pipe comes?
22 feet
49 Q
What is the approximate hanger rod size
2” and less — 3/8
2-1/2 and greater — 1/2
50 Q
What is the approximate support spacing for 6 inch NPS for water and for air/steam?
Water — 17 foot
Air/steam — 21 foot
51 Q
Socket weld flanges may be used up to what size?
3 inch NPS 600 lbs
52 Q
When is a journeyman pipefitter license required for anyone installing repairing replacing maintaining or altering any apparatus for piping appliances devices or accessories for heating systems?
What chapter is this listed?
For systems in excess of 700,000 btu per hour
Chapter 146
53 Q
What acceptable method of meeting the requirements for internal inspection and cleaning shall be made for steam and water connections to a water column?
Fitting with a back outlet at each right angle turn
54 Q
What is required when 2 or more traps discharge into the same header?
A stop valve in each discharge line
55 Q
How many pressure gages must a power boiler have and where?
At least one easily readable
35 Q
What is a slow opening valve?
One that requires five 360° turns to fully open or fully close
36 Q
Steam boiler gages shall not be less than how many psi?
30 psi
56 Q
What size must the connection from the boiler to the water column be?
@ least 1”
14 Q
The minimum temperature rating of all valves on a heating boiler shall be at least equal to how many degrees F?
250°F
57 Q
What is the drain for on a gage glass?
To facilitate cleaning
58 Q
When does power boiler code (section l) apply?
- For boilers with gas pressure greater than 15 psig (high pressure)
- For boilers with high temp water with operating pressure greater than 160 psig and temp greater than 250 degrees F
59 Q
The lower edge of the steam connection to a water column shall be?
Not below the highest visible water level in gage glass
60 Q
What is boiler external piping?
Piping that begins at the first weld, thread or flange and includes all piping up to and including the second stop valve
61 Q
What is the service limit for non ferrous pipe or tubes (copper or copper alloys)?
406°F
62 Q
What is the minimum size of the gage connection to the power boiler?
Greater or equal to 1/4 but 1/2” NPS for steal or wrought iron
63 Q
What size is the minimum size of siphon for the pressure gage?
1/4” ID
64 Q
How must the pressure gage be graduated on a power boiler?
To approx. double the pressure of the safety valve but no less than 1.5 times the pressure
65 Q
How can the fuel cutoff be connected to the boiler?
Through tapped openings if nonferrous whys and tees are used
66 Q
What is the boiler proper?
Superheaters economizers and other pressure parts connected directly to the boiler without intervening valves.
67 Q
What are the minimum and maximum sizes for blowoff connections?
Greater than 100 sq ft heating area 1” to 2½” NPS
less than or equal to 100 sq ft heating area ¾ NPS
68 Q
Which is mandatory to have installed on a separate connection on a hot water heating boiler?
Thermometer
69 Q
What section of the code pertains to the construction of power boilers?
Section l
70 Q
What does the feedwater piping for all boilers except high temp water include?
It extends through the required stop valve and check valve.