TB 54 Mezzanines Flashcards
TB 54 Mezzanines
A flly sprinklered building must have sprinklers installed above and beneath any mezzanine.
Reference
TB 54 Mezzanines
When the total area of any such mezzanine floor exceeds ___ percent of the total floor area in that room, it shall be considered as constituting an addition “story” in the building. The clear height above or below a mezzanine floor constuction shall not be less than ___ feet
33 1/3 percent
7feet
TB 54 Mezzanines
There shall not be more than two leves of mezzanines in a room.
Reference
TB 54 Mezzanines
Railings not more than 42 inches in height
Reference
TB 54 Mezzanines
Partitioning may be installed, provided the aggregate floor area of the enclosed space does not exceed ten percent of the area of the mezzanine or have an occupant load exceeding ten, whichever is greater.
Reference
TB 54 Mezzanines
Two exits shall be provided from mezzanines having an occuoant load of more that ten or when the area of the mezzanine exceeds 2,000 square feet, whichever is the more restrictive.
Reference