TB 054 - Hazardous/Illegal Mezzanines Flashcards
If a building with a mezzanine is fully sprinklered where must sprinkler be installed?
Above and beneath any mezzanine
How should overloaded mezzanine conditions be treated?
As immediate life hazards
What is a mezzanine or mezzanine floor?
An intermediate floor placed in any story or room.
When is a mezzanine considered an additional “story” in a building
When the area of the mezzanine exceeds 33-1/3 percent of the total floor area in that room
The clearance height above and below a mezzanine shall not be ______?
less than 7 feet
There shall not be more than how many levels of mezzanine in a room?
Not more than 2 levels
Is theres limitation on the number of mezzanines within a room?
No limitation
____ portions of a mezzanine shall be open to the room in which it is located.
All
Railing on a mezzanine should not be more than how many inches in height
42” in height
Partitioning may be installed, provided the aggregate floor area of the enclosed space does not exceed _____ percent of the area of the mezzanine or have and occupant load exceeding ____, whichever is greater.
- 10%
- 10 occupants
Mezzanines having _____ or more exits need not open into the the story in which they are located, provided at least one of the exits gives direct access to a protected exit corridor, an exit court, enclosed exit stairway, exterior exit, exterior balcony, or exit passageway
two or more exits
Two exits shall be provided from mezzanines having an occupant load of more than _____ or when they area of the mezzanine exceeds _____ square feet, whichever is the more restrictive.
- 10 occupants
- 2,000 square feet
The occupant load of the mezzanine shall be added to the occupant load of the _____ or ____ in which it is located
Story or Room
For a sprinklered building with sprinklers extending beneath the mezzanine, a notice shall be issued directing the removal of all __________ beneath the mezzanine and notifications shall be made to the ________
- Combustible Materials
- Fire Prevention Bureau
For mezzanines which do not appear to be adequate to support the weight of storage, a ________ Notice requiring “forthwith” compliance shall be issued for removal of storage to a weight which is a safe structural load; and notification shall be made to the ________
- Fire/Line Safety Violation Notice
- Fire Prevention Bureau