Systems Integration Flashcards
Can lighting remain below an air handler unit?
Yes (ensure the space between finished ceiling and slab?)
What should the thermostat be kept away from?
Supply and Return may affect proper reading
When you can it is easier to just move sprinkler head rather than whole branch line
True
It is better not to put a supply on top of persons seat at desk….
Because it blows on them
Light over moveable conference table that is a path of egress and what should ceiling height be?
Ceiling ht 7’-6” (90”)
Protruding objects in path of egress man be 6’-8” (80”)
Light over 42” transaction top
72”-78” (2’-6”-3’-0” above surface)
How much space do you need to have above finished ceiling to accommodate sprinklers?
12 “ for recessed and 15” for pendant - 3” of that is hanging space for both. 9”-12” is for piping
Wall mounted sconces 4” or less should be mounted at what height?
5’-0” - 6’-6”
60”-78” AFF
If sprinkler head and duct conflict (with no flexible duct) then what show you move?
Sprinkler head
Should you call out exact terminology “24” x 48” parabolic troffer”?
YES!
Height from top of sprinkler branch line to finished ceiling?
9” or 12” (pendant)
3” clearance above that
Max height of thermostat if no 24” work surface?
48” but if need to reach over something that it changes
Don’t place thermostat where…
Supply, return, exterior wall, glass
Could be a problem with plumbing and column grid
May need trench or drain but there’s a column grid
Put access panel for AHU not where?
Where connected to ductwork