Life Safety Flashcards
1 hour rated walls
- partitions btw tenant spaces
- ” along public corridors
- ” that DEMISE an assembly of 750 SF
- storage rooms exceeding 100SF
Aluminum door frame
Retail and glass doors over 240 SF
There must be an AV fire signal device and emerg lighting where?
What height should they be mounted at?
- Restroom
- Hallway
- Lobby
- General Assembly
Use 7’-6” (but in reality 6’-8” to 7’-6”) pay attention to ceiling ht.
Smoke and heat detectors must be located
ALL ROOMS &; CORRIDORS
Everywhere but adjacent tenant suite and stairs
but still place outside the suite in Janitors room, restrooms….
Minimum number of fire extinguishers
w/i 75’ to furthest occupant and 1/3000SF
Where do you place exit signs?
Corridors pointing to exits, over doors, change in direction, stair doors
Do acoutical walls stop at ceiling or deck?
deck
****If an door is locking &; fire rated what does it need?
Panic bar
Should you use over 240SF glass door if acoustical privacy is needed?
No
If locking provisions are not indicated in the program and its for a conference room what kind of lockset should you use?
Lever passage set
When would you use a flushbolt instead of roller latch?
Flushbolt - for double doors if you want to use 1 side (pins 1 side of the door closed, going in and out with rolling carts etc,
Dummy set with roller latch - better for bedroom closet, standard closet, less strong, wouldn’t pin one side stationary
Does any life safety equipment (SD, emerg lighting…) get placed in stairway or adj tenant space?
No.
Exit sign in rooms (ex PDP training room) must be placed on the door leading to public corridor and door leading back to office area?
Yes
What to remember about emerg lighting?
place so can light max amt of space
Think about how to aim them!
Illuminate door and path to door
Aim to light the path of egress
Where is AV best placed?
Occupants have to be able to see it but also good to place near exits (wayfindingish)
For mounting consider window and ceiling heights