  1. Adjust voltage reposts to keep/take MVAR to 0
  2. Follow gate position with gate limit
  3. Open VCB at 0MW and 0 MVAR
  4. Remove voltage. Regulator from service (manual)
  5. Run gate limit in the hole, 0%
  6. Place 1CS1 to stop position
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Steps 13-17

A
  1. Observe RPM to begin to fall
  2. Observe brakes come on approx 25RPM
  3. Acknowledge brake applied annunciation
  4. Observe RPM continues to fall
  5. Record in log book time unit is shutdown
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What are steps 1-6

A
  1. CK generation schedule
  2. Record HW & TW on 84A
  3. CK 103B for proper unit to shut down
  4. Compare MW on 103B and watt hour meter to know target MW output
  5. CK/place reactive at zero with voltage adjusting rheostat on apron
  6. Adjust speed adjust to the slow side to take unit to 0 MW (approx. 2.5% slow)