Steps To Unload A Unit Flashcards
1
Q
Steps 7-12
A
- Adjust voltage reposts to keep/take MVAR to 0
- Follow gate position with gate limit
- Open VCB at 0MW and 0 MVAR
- Remove voltage. Regulator from service (manual)
- Run gate limit in the hole, 0%
- Place 1CS1 to stop position
2
Q
Steps 13-17
A
- Observe RPM to begin to fall
- Observe brakes come on approx 25RPM
- Acknowledge brake applied annunciation
- Observe RPM continues to fall
- Record in log book time unit is shutdown
3
Q
What are steps 1-6
A
- CK generation schedule
- Record HW & TW on 84A
- CK 103B for proper unit to shut down
- Compare MW on 103B and watt hour meter to know target MW output
- CK/place reactive at zero with voltage adjusting rheostat on apron
- Adjust speed adjust to the slow side to take unit to 0 MW (approx. 2.5% slow)