Steam Generating/SGWLC/Blowdown Flashcards
What do the J tubes help to prevent?
Water Hammer when AFW initiates
What does the flow restrictor do on each MS outlet from the SG?
- Provide plant protection, in case of MSLB, by decreasing steam flow rate to reduce RCS cooling rate.
What is P-14 permissive?
SG Hi HI Lvl at 67% on 1 SG (2/3) FWI
SG level at 64% allows feeding
What will P-14 permissive cause?
- Turbine Trip
- MFP Trip
- FWI
What enables AMSAC?
Greater than 40% Power (C-20, 2/2 Turbine first stage Impulse pressure)
What generates an AMSAC signal?
FW flow < 25% (3/4 Feed flow)
What will AMSAC actuate?
- Trips Main Turbine (30 Sec)
- Starts All 3 AFW Pumps
What is the cooling water to the BD Hx and flash tank quenching?
Containment Chill Water
What causes a Steam Line Isolation (SLI)?
- Cnt # High-High at 2.8# (2/4)
- SG # low < 500# (1/1 on 2/4 SG)
- High Stm flow with P-12 (1.42E6/1.6E6) (1/2) on 2 SG
What is density compensation?
Converts volumetric flowrate of steam to mass flowrate for input into SGWLC circuit
(Left 2 Channels)
Where do we measure SG Level?
SG Downcomer
What is swell caused by?
An increase in steam flow
(which will cause an increased indication of SG lvl in the downcomer due to decreased SG pressure)
What is shrink caused by?
A Reduction in steam flow
(which will cause an decreased indication of SG lvl in the downcomer due to a rise in SG pressure)
If the controlling channel STEAM flow fails high, what will happen the FRV?
The FRV will go open because Feed Flow will want to match Steam Flow
If the controlling channel STEAM flow fails low, what will happen the FRV?
The FRV will go closed because Feed Flow will want to match Steam Flow