Steam Generating/SGWLC/Blowdown Flashcards

1
Q

What do the J tubes help to prevent?

A

Water Hammer when AFW initiates

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What does the flow restrictor do on each MS outlet from the SG?

A
  • Provide plant protection, in case of MSLB, by decreasing steam flow rate to reduce RCS cooling rate.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is P-14 permissive?

A

SG Hi HI Lvl at 67% on 1 SG (2/3) FWI

SG level at 64% allows feeding

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What will P-14 permissive cause?

A
  • Turbine Trip
  • MFP Trip
  • FWI
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What enables AMSAC?

A

Greater than 40% Power (C-20, 2/2 Turbine first stage Impulse pressure)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What generates an AMSAC signal?

A

FW flow < 25% (3/4 Feed flow)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What will AMSAC actuate?

A
  • Trips Main Turbine (30 Sec)
  • Starts All 3 AFW Pumps
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What is the cooling water to the BD Hx and flash tank quenching?

A

Containment Chill Water

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What causes a Steam Line Isolation (SLI)?

A
  • Cnt # High-High at 2.8# (2/4)
  • SG # low < 500# (1/1 on 2/4 SG)
  • High Stm flow with P-12 (1.42E6/1.6E6) (1/2) on 2 SG
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What is density compensation?

A

Converts volumetric flowrate of steam to mass flowrate for input into SGWLC circuit
(Left 2 Channels)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Where do we measure SG Level?

A

SG Downcomer

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What is swell caused by?

A

An increase in steam flow
(which will cause an increased indication of SG lvl in the downcomer due to decreased SG pressure)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What is shrink caused by?

A

A Reduction in steam flow
(which will cause an decreased indication of SG lvl in the downcomer due to a rise in SG pressure)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

If the controlling channel STEAM flow fails high, what will happen the FRV?

A

The FRV will go open because Feed Flow will want to match Steam Flow

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

If the controlling channel STEAM flow fails low, what will happen the FRV?

A

The FRV will go closed because Feed Flow will want to match Steam Flow

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

If the controlling channel FEED flow indication fails low, what will happen the FRV?

A

The FRV will go open because Feed Flow will want to match Steam Flow

17
Q

If the controlling channel FEED flow indication fails high, what will happen the FRV?

A

The FRV will go closed because Feed Flow will want to match Steam Flow

18
Q

What will happen if either the SG Level or Flow Controllers are lost?

A

The RU will instantly go to manual to maintain the FRV at its current position

19
Q

Unit 1 was operating at 100% power when a loss of main feedwater occurs to a single SG due to the failure of the controlling feedwater flow instrument.

A valid indication on the affected SG “Flows / Level / Pressure” recorder for this failure would be a rapidly lowering SG level and a?

A

high feedwater flow indication on the feedwater flow pen

20
Q

What will cause a FWI?

A
  • SG High-High level (P-14) (67% NR 2/3 on 1 SG)
  • SI
  • Rx trip (P-4) with low Tavg (Tavg less than 554°F on 2/4 loops)
21
Q

What happens on a High High SG Level of 67%?

A
  1. FWI
  2. Turbine Trip
  3. MFP Trip
22
Q

Why does a failure of the SG Pressure input affect that SGs SF channel?

A

Because the steam flow channels are density compensated