Rod Ctrl Flashcards

1
Q

What is the C-1 Conditional?

A

Intermediate Range Rod Stop
- Stops AUTO and MANUAL Rod Withdraw
- 1/2 - IRNI > 18% (16%)
- Manually blocked above P10 (≥ 10% PR)
- Unblocked below P10

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is the C-2 Conditional?

A

Power Range Rod Stop
- Stops AUTO and MANUAL Rod Withdraw
- 1/4 PR > 103%
- Blocked when ROD STOP BYPASS selected to alarming channel

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is the C-3 Conditional?

A

OTΔT Rod Stop
- 2/4 PRNI 3% < trip setpoint
- Stops AUTO and MANUAL rod withdraw
- No Block!

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What is the C-4 Conditional?

A

OPΔT Rod Stop
- 2/4 PRNI 3% < trip setpoint
- Stops AUTO and MANUAL rod withdraw
- No Block!

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What is the C-5 Conditional?

A

Turbine Power Interlock
- MPC-253 < 15%
- Stops AUTO ONLY rod withdraw
- No Block!

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What is the C-11 Conditional?

A

Control Bankd D Rod Stop
- Ctrl Bank D at 229 steps
- Stops AUTO ONLY rod withdraw
- No Block!

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What are the Rod Ctrl Inputs?

A
  • Auctioneered High Tave
  • Auctioneered High PR NI
  • MPC-253, Turbine 1st Stage Impulse #
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Where are the MG Sets powered from?

A

11/21A and 11/21D busses

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Given the following conditions:
* Unit 1 is at 100% power
* A loss of power to CRP-3 occurs

What is the effect on the Rod Position Indication (RPI) system and the procedural action necessary, if any?

A

RPI indications are lost. Dispatch an operator to manually align backup power supply (via ELSC) to energize the RPI Cabinets. Operation is allowed since RPI has been restored.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What does the Variable Gain Unit do?

A

Increases the output at low power because reactivity change at lower power has a smaller effect on power than at high power

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

At what speed do the shutdown banks move?

A

62 SPM

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

At what speed do the rod ctrl banks move in auto?

A

8-72 SPM
- Error of 1.5-3 degrees = 8 steps per minute
- Error of 3-5 degrees = 32 steps per Degree + 8
1.5-3 degrees - 8 steps
3.5 degrees - 24 steps
4 degrees - 40 steps
4.5 degrees - 56 steps
5 degrees - 72 steps

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

At what speed do the rod ctrl banks move in manual?

A

48 SPM

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What is Differential Rod Worth?

A

The change in reactivity resulting from a unit change of rod position. (pcm/step)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What is Integral Rod Worth?

A

Reactivity inserted by moving a control rod from a reference position to any other rod height

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

When does the Rod dropped/Rod Bottom alarm clear for Control Bank A?

A

When all shutdown Banks are withdrawn AND Control Bank A gets to 20 Steps

17
Q

If MPC-253 fails low, what happens with rods in automatic? Why?

A

Rods will step in due to PR rate change and temp error

18
Q

When does the Rod Dropped alarm enabled for Control Banks B-C?

A

When demand is > 35 steps for that group

19
Q

When does the Rod Dropped alarm annunciate for Control Banks B -C?

A

When IRPI is < 20 steps with a demand > 35 steps, AFTER the alarm has been enabled.

20
Q

When do Rod Bottom lights clear for the control banks?

A

When the rods are withdrawn > 20 steps

21
Q

If MPC-253 fails high, what happens with rods in automatic? Why?

A

Rods step OUT due to power rate of change and temperature error

22
Q

If Tavg fails high, what happens with rods in automatic? Why?

A

Rods step in due to the temperature error

23
Q

If Tavg fails low, what happens with rods in automatic? Why?

A

NOTHING! Rod control uses auctioneered high Tavg

24
Q

If a Power Range NI fails low, what happens with rods in automatic? Why?

A

Nothing! Rod control uses auctioneered high

25
Q

If a power range NI fails high, what happens with rods in automatic? Why?

A

Rods step in due to the power rate of change.

26
Q

If you have a PR NI Failure high, will rods step back out due to the temperature error afterwards?

A

It depends. If C2 (103% on 1/4 PRNI) is met, NO. If the failure is less than that setpoint, yes, they will step back out

27
Q

What is the purpose of bank overlap?

A

Provides a more uniform axial power distrubtion as well as a more uniform Differential Rod Worth

28
Q

When moving which rods would you expect no indication on your rod speed indicator?

A

Shutdown Banks C and D

29
Q

If a rod is dropped, is the effect on axial or radial power distribution more noticable?

A

Radial power distribution

30
Q

If a rod is inserted 20 steps, is the greater effect on radial or axial power distribution?

A

Axial

31
Q

What is the purpose of maintaining QPTR within limits?

A

It keeps radial power distribution within limits

32
Q

What is the purpose of maintaining raidal and axial core power distribution within limits?

A

It keeps power density (kw/ft) and DNBR within limits

33
Q

What provides the Reactor Power input to the rod insertion limit comparator?

A

RCS Delta-T

34
Q

What is the normal source of power to the Rod Control Logic Cabinets?

A

120 VAC stepped down from Rod Drive MG Set Output

35
Q

Given the following conditions: Unit stable at 75% power w equilibrium Xe. Rod control is in auto. Rod height is 180 Steps on CB D. PR Channel N-44 fails High. Which one of the following describes the response of the Rod Control system? The control rods will….

A

Step in until the power mismatch circuit output decays away