Major Valves and Interlocks Flashcards

1
Q

To Open the Recirc Sump valve ICM-305, what alignment must you have?

A

Can’t go onto recirc sump unless your isolated from the RSWT via RHR and CTS suctions

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

To Open the CCP or SI pp Suction from the RHR Pumwhat alignment must you have?

A

Can’t supply the CCP or SI pump with water from RHR pump unless you’re on the recirc sump and the SI pump recirc back to the RWST is isolated bc you’d pump your recirc sump to RWST

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

To open RHR Spray valves, what alignment must you be in?

A

Must be on recirc sump

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

To Open your RHR pump suction valve, what alignment must you have?

A

Can’t be on the recirc sump, trying to Spray, or trying to supply CCP / Si with water from RHR

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What is the normal position for RWST Valves to CCP Suction IMO-910 and 911 and what auto opens them?

A

Parallel, normally-closed, motor-operated Automatically open on SI signal Automatically open on Refueling Water Sequence: low-level (2.5%) in VCT

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

How to the CCP Emergency Leak-off Valves (ELO) QMO-225 and 226 work on a SI?

A

Close on SI signal Open after2 sec time delay with SI signal present and RCS pressure above 1825 PSIG. Close if RCS pressure drops below 1812 PSIG

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

CCP Emergency Leak-off Valves (ELO) QMO-225 and 226 continue to cycle on pressure after a SI until?

A

SI signal is reset Control switch placed in PULL TO RESET position - resets SI seal-in circuit

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

East CCP Emergency Leak-off Valves QMO-225 receives pressure signal from

A

NPP-151

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

West CCP Emergency Leak-off Valves QMO-226 receives pressure signal from

A

NPP-153

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

IMO-340 East RHR HX to Charging Pumps Suction Supply Normal Position and Purpose?

A

Normally closed Aligns RHR pump discharge to CCP suction header

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

When is IMO-340 East RHR HX to Charging Pumps Suction Supply Open?

A

Open for cold leg recirculation

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What are the interlocks with IMO-340 East RHR HX to Charging Pumps Suction Supply in order to open this valve ?

A

ICM-305 Recirc Sump Suction must be Opened and have control power IMO-262 OR IMO-263 SI mini flow must have control power and be closed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What are Recirc Sump to RHR Suction Valves ICM 305 and 306 Interlocks?

A

Will not open unless RHR Suction from RWST Iso valves are closed (IMO-310 and 320) AND CTS suction from RWST Iso valves (IMO-215 and 225) are closed.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What are the interlocks with IMO-350 West RHR HX to Charging Pumps Suction Supply in order to open this valve ?

A

ICM-306 Recirc Sump Suction must be Opened and have control power IMO-262 OR IMO-263 SI mini flow must have control power and be closed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What are the interlocks for IMO-330 and 331 RHR to Upper spray header to open?

A

Recirc sump isolation valves ICM-305 and 306 must be open

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What are the interlocks for IMO-310 and 320 RHR Suction from RWST to open?

A

Recirc sump iso valves ICM-305 and 306 must be closed RHR to upper containment spray IMO-330 and 331must be closed RHR to CCP (IMO-340) and RHR to SI (IMO-350) suction header iso valves must be closed.

17
Q

What is the purpose of the ICM-305 and 306 suction fro, recirc sump interlocks for opening RHR Pump Suction Valves IMO-310/320?

A

prevent draining RWST to recirculation sump

18
Q

What is the purpose of the IMO-330/331 RHR to upper spray interlocks for opening RHR Pump Suction Valves IMO-310/320?

A

prevent pumping RWST to upper spray nozzles before cold leg recirculation properly aligned

19
Q

What is the purpose of the IMO-340/350 interlocks for opening RHR Pump Suction Valves IMO-310/320?

A

prevent aligning CCP/SI pump suctions to recirculation sump

20
Q

What is RC Loop #2 hot leg to RHR Suction IMO-128 interlocked to ?

A

will NOT open if RCS pressure > 411 psig on NPS-122, Loop 1 Ch3

21
Q

What is the RC Loop #2 Hot Leg to RHR Suction IMO-129 interlocked to?

A

will NOT open if RCS pressure > 411 on psig NPS-121, Loop 2 Ch2

22
Q

How does IRV-311 RHR Hx Bypass Valve fail on loss of air?

A

Open

23
Q

How do RHR Hx Outlet valves IRV-310 and 320 fail?

A

Open

24
Q

What is the NORMAL COOLDOWN FLOWPATH for RHR?

A

Suction from Loop 2 Hot Leg Discharges to Loops 2 and 3 Cold Legs via ICM-111 thru both Hx and Hx Bypass

25
Q

What is the ALTERNATE COOLDOWN PATH for RHR?

A

Suction from Loop 2 Hot Leg Discharges to Loops 2 and 3 OR 1 and 4 Cold Legs, NOT using ICM-111 Choice is temperature dependednt

26
Q

Do Cold Leg Loops 1 and 4 have thermal sleeves?

A

NO

27
Q

Do Cold Leg Loops 2 and 3 have thermal sleeves?

A

YES

28
Q

What is the INJECTION FLOWPATH for RHR?

A

Suction from RWST Discharges to Loops 1-4 Cold Legs with all flow thru the Hxs

29
Q

What are the 3 LTOP Protections? 270*F (300*F)

A

RC Loop 2 Hot Leg to RHR Suction safety valve SV-103 2 PZR PORVS >2 inch RCS vent

30
Q

Whate are the interlocks on th Clean and Dirty Waste HUT Inlet Valves?

A

Both cannot be closed at the same time. This ensures you always have a flowpath for drains

31
Q

What is the interlock on Liquid waste to U1/U2 discharge tunnel shuteoff valves RRV-287/286?

A

You cannot open unless at least 1 CW Pump is I/S

32
Q

What is the interlock on the GDT Inlet Valves?

A

Interlocked so that if 1 is open, all the others remain closed

can’t have more than 1 open at a time