What size main drain is required for a 6” riser?

A

2”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
1
Q

What class of standpipe is designed to “primarily” be used by building occupants? (I, II, III, IV)

A

I

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Minimum design pressure for class 1 hose outlet on roof of high-rise BLDG. (65, 100, 130, 160)

A

100

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What does a thermal barrier do?

A

Limits average temperature rise of unexposed surface to not more than 250 degrees after 15 minutes fire exposure.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What is the difference between closed array and open array?

A

Open arrays have smaller horizontal beam width. Open arrays are larger, heavier and require more power.

see page 13-17 under sprinklers. Paragraphs 3.9.1.1 and 3.9.1.2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What type of sprinkler head is required for new light hazard occupancy?

A

Standard response

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What temperature range is indicated by a blue color code?

A

250-300 degrees

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

In which occupancy category would a hospital be listed?

A

Light Hazard

Annex A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What is the temperature classification of an unventilated attic?

A

Intermediate - Temperature

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What is the maximum protection area coverage for any sprinkler?

A

400 square feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Open building is 2900 Sq Ft. Assuming maximum coverage for any one head, what is the minimum number of sprinklers required?

A

8

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Maximum ceiling temperature for wet sprinkler system for operation and maintenance is _______ degrees? (85, 95, 100, 110)

A

100

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What is the minimum temperature for wet sprinkler system for operation and maintenance?

A

40 Degrees

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Minimum distance from grade for Fire Department Codes F.D.C.? (12, 18, 24 and 36) inches

A

18 inches

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What is the minimum design pressure for a class 1 hose outlet on the roof of a high rise building?

A

100PSI

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What is the maximum distance of a fire dept connection from a standpipe system?

A

100’ Ft.

16
Q

Fire dept connections should be located no less than how many inches above the level of the adjacent grade of access level?

Point of reference: The red and or brass Fire dept hookups on the side of large buildings coming out of the exterior wall.

A

18”

17
Q

What is the max operating pressure of a standpipe system? (75, 100, 250 or 350 PSI)

Hint: Standpipe is a large normally painted pipe coming out of concrete that look like submarine telescopes.

A

350 PSI