Desiccants are used in…
Driers
Which of the following is true? Stud wall cavity is proposed to be used as supply air plenum.
Not allowed by code
Air to air heat pump in the heating mode, the heating capacity will increase or decease as the outside temperature rises?
Increase
For condensation disposal on fuel burning appliances, every foot of a horizontal run shall slope… ____”
1/8”
Vent of appliance is prohibited from going through (attic, crawl, air duct)
Air duct
Outside or return air shall be a minimum of how many feet from vent?
10’
A plume discharge from a cooling tower must be a minimum of how many feet above ventilation inlet to a building? (3, 5, 8, 10)
5 ft
A thermostat wire passes through an air duct plenum. How must the wire be rated?
plenum
What is the maximum temperature exposure for non-metallic ducts such as duct board?
250 degrees
When insulating duct, when can the service opening be covered?
When the exact location of the opening is properly identified
Minimum size letters to mark access locations of smoke and fire detectors in an air duct system?
1/2 inch
What is the net free area of 12x12 metal louver in a combustion air opening? (36, 72, 108, 144)
108
A 120,000 BTU furnace is located in a confined space. All air is taken from inside. What is the minimum free area from all vents. (100, 120, 240, or 300 square inches)
240 square inches
In confined space, duct from combustion air must be a maximum of how many inches from floor?
12”
A 50,000 Btu furnace installed in a residential room with normal infiltration. The room is 20x20 and a 9’ ceiling. Not usually tight construction. What is the minimum size for combustion air opening- not required.
72 Cubic Feet per 1000 Btu
Residential gas fired fuel appliance is 80,000 Btu. Combustion air through vertical duct to outdoors. What is the minimum free area for openings? (25”, 20”, 18” or 16”)
20”
Minimum number of openings communicating with outside required to ventilate a confined space where a gas appliance has a clearance of one inch on it’s sides and 6” on front. (1, 2, 3, 4)
2
Minimum cross section of combustion air duct is ____ inches
3”
Minimum size mesh for combustion air openings for fuel burning appliances is ______”
1/4”
Which of the following is a metal sleeve with fabric connected and used to reduce noise in an exhaust system?
Vibration insulator
A boiler that furnishes water at 225 degrees and 150 psi is classified as a ______-____________ boiler.
low pressure
Where do steam traps discharge to?
Boiler
What type of refrigerant can be tested with air?
R717
What is the minimum distance a refrigeration fusible plug or purge system must vent above grade level from a mechanical room. (15, 20, 25, 30)
15’
What is the maximum size annealed temper copper tube that can be used for refrigerant piping?
2”
What is the maximum size outside diameter for annealed temper copper tubing in a refrigeration system that is permitted to have a flared fitting?
7/8
After piping a refrigeration system, pipes shall be tested at what minimum pressure?
Not less than the lower of the design pressure or setting of the relief device
What is the maximum smoke developed rating for hydronic pipe insulation? (50, 75, 100, 125)
50
Minimum clearance for hydronic piping at 250 degrees from combustibles is…
1”
Horizontal steam lines should slope so that condensation flows away from OR back towards the boiler?
Back towards the boiler
Minimum test pressure for “slab on grade” hydronic piping is ____ psi?
100 psi
Minimum test time for hydronic piping is ______ minutes?
15 minutes
What type of joint is used for copper hydronic piping installed in concrete slab?
Silver brazed
Where do you install an oil trap on a suction line riser?
At the “Base” of the vertical suction line
Liquid refrigerant entering the evaporator is suddenly at a Lower Pressure OR Higher Pressure?
Lower Pressure
Maximum flame spread for adhesive duct liner is… (15, 25, 30 50)
25
What joint or seam of a metal duct must be sealed as directed by sealing requirements of class C duct? (Helical, Longitudinal, Transverse)
Transverse
The maximum distance for supports on horizontal sheet metal duct is…
10ft
When is duct type smoke detectors required?
When return air is 2000 cfm or higher
A single 16,000 CFM roof top unit serves each floor of a 3 story commercial building. How many smoke detectors are required?
3
The net free area of a 12 x 12 metal louver in combustion opening is (36, 72, 108, 144) square inches.
108 square inches
What is prohibited from being installed within a plenum?
Fuel fired appliances