The notch for gas piping is located 5’ from the edge of a 2x12 joist. The joist is 12’ long. The notch is on the bottom. What is the maximum height of the notch. (1-1/2”, 2”, 3” or may not be located here)
May not be located here
What is the minimum distance a notch can be made on the edge of a stud before a shield plater is required? (1/2”, 1”, 1-1/2”, or 2”)
1”
Gas pipe shall not be ben though an arc greater than…
90 Degrees
Minimum test pressure for gas pipe is…
3 psi
Which method cannot be used for joints in plastic fuel gas pipe?
Threaded
Which of the following shall not be used for joints on metallic gas pipe?
Soldered
Vent connectors located in attics must be…
Type B or L vents
On a 3” gas line, a pressure tap must be installed a minimum of how far from an MP regulator? (24”, 30”, 36” or 42”)
30”
What is a good cleaner for removing scale from a water cooled condenser? (Iso Alcohol, Sodium Thiosulfate, Nitrogen and Muriatic Acid)
Muriatic Acid
Compressor runs constantly on ac system. Most likely cause is…
(low refrigerant, excessive refrigerant, low voltage or open thermostat)
Low refrigerant
What is the equivalent length of pipe in feet for two 6” 45’s and one 6’ gate valve? (6’,17’, 21’ or 29’)
17’
Vessel with open top is considered confined space if it is atleast how many feet deep (2, 4, 6, 8)
4’
What is the minimum number of openings communicating with outside air required to ventilate a confined space where a gas appliance has a clearance of 1”on both sides and the back and 6” in the front?
1
A gas fired unit heater in a warehouse must have how much clearance from the wall?
18”
When installing a recirculation direct-fired industrial air heater, what provisions must be made? (Ductwork, Make up water, Relief air vent)
Relief air vent
Gas vent terminates through roof with a 12/12 pitch, not at peak of roof. What is the minimum height from the roof to the lowest discharge opening?
4 FT
What is the smallest pipe that can be used on a 165’ piping system designed to carry 900 CFH of gas at 1 PSI and 1/2” water column?
2-1/2”
What is the appropriate size vent for a category one 125,000BTU appliance with Type B double wall vent if using for natural draft with a height of 15FT and a lateral run of 2FT.
5”
A fan assisted 125,000BTU appliance is placed into a room with 65,000BTU natural draft water heater. What is the common “Type B” vent size required if the vent is 23FT high?
5”