Spray Ponds Flashcards
When will a spray pond pump automatically start?
SIAS, CSAS, CREFAS, CREVIAS, DG running
How many spray pond nozzles per pond
320 nozzles
What are the holes on the bottom of some of the risers in the spray pond for?
Freeze protection
What is normal discharge pressure for an operating spray pond pump?
50-55 psig
What does the spray pond cool?
- Essential cooling water heat exchanger
- DG fuel oil cooler
- DG JW cooler
- DG air after cooler
- DG lube oil cooler
What are the makeup sources for spray pond?
TB and domestic service water
Can use Fire protection in an emergency
If the spray ponds are tied together and we lose all makeup sources; how long could the spray ponds supply adequate cooling?
26 days
What is the minimum Spray Pond level for Spray pond pump operation?
1’6”
What is the tech spec limit for spray pond level?
13’ 6”
At what level in the spray pond will the spray pond filter pump trip?
13’ 7.5”
At what level in the spray pond will the control room receive a low level alarm?
13’ 11”
At what level in the spray pond will the weir begin to overflow to the sump?
14’ 5”
At what level in the spray pond will the control room receive a high level alarm?
14’ 8”
If we lose makeup capabilities to the spray pond during a loss of coolant accident. What must we do at the spray ponds?
Open the cross tie valves (HCV-207 and HCV-208) and shutdown one train of emergency core cooling.
What is the maximum Spray pond motor bearing temp?
194 degrees F
What is the maximum design basis upper flow limit of the spray pond?
17,950 gpm
Design basis temperature for spray pond?
113 degrees F
Explain the re-circulation pump skid
3 pumps. One for each pond. And one that can be aligned to either pond.