Diesel Generator Flashcards
What will automatically start the DG?
Starts in emergency mode- LOP, SIAS, AFAS
Starts in Test mode- CSAS
When will a DG trip when its running in emergency?
Overspeed, Low Lube oil pressure, Generator differential
The DG starts, what else starts?
Spray Pond Pump, Pump house fan, DG blg HVAC
What are the conditions for the DG output breakers to close automatically?
LOP, DG @ rated speed and voltage, No faults on normal or ALT breaker, Normal and ALT breakers open.
What are the conditions for the DG output breakers to be closed from the CR?
DG @ rated speed and voltage, No fault on the norm or alt breakers, alt supply breaker open
What power is the DG designed to supply?
- 5 MW continously
6. 05 MW 2/24 hours
On a loss of spray pond, how long can you run the associated DG?
2.6 minutes loaded
15 minutes unloaded
In the manual control of the DG, what is the engine speed limited to?
580-630 rpm while in droop mode
If we are operating the DG in parallel with offsite power in the test run mode. What happens if we receive a SIAS or AFAS?
The DG output breaker, PBA-S03B will trip open
What is the minimum jacket water and lube oil system temperature to maintain the DG operable?
105 degrees F
When will we have to call the DG inoperable, regarding level in the fuel oil storage tank?
- FOST level is less than 80% and greater then 71% for 48 hrs or more
- FOST level is less then 71%
What cools the DG?
Spray Pond (JW, LO, FO, and intercooler)
What are the fuel oil storage tanks designed for?
- 7 days of continuous operation at rated power plus a 15% margin for testing
Administrative level is 85% to ensure we are above TS minimum
What are the fuel oil day tanks designed for?
- 60 min of continuous operation at rated power plus a 10% margin
- 1100 gallons
- Min TS level 550 gallon (2.75ft)
When will the fuel oil transfer pump automatically fill the fuel oil day tank?
At 65% level
How much fuel does the DG use at full rated load?
6.4-7.0 GPM
What are the makeup sources for the JW system?
Norm- Demin
Backup- CST
Emer- Fire Protection
How many consecutive starts are the starting air receivers designed for?
5
The starting air control valves open on a start signal, when do they begin to close?
approx 280 rpm
At what temperature does the electric circulating pump and heater maintain the JW temperature at when the DG is not running?
120-135 degree’s F
When will the overspeed shutdown butterfly valve be tripped by the overspeed governor?
660 RPM
Physically how does the DG start?
Introducing high pressure air into the top of the power pistons turning the crankshaft and accelerating it
How does an AO emergency stop the DG?
- Manual shutdown push button on local control panel
- Main governor load limit control knob to min. position
- Fuel manual control handle in off position
- Manually trip overspeed butterfly valve
When the DG is in standby or shutdown; what position are the fuel racks in?
Minimum position
What pump is normally running to maintain it in a standby condition?
The electric circ pump and heater (maintain oil 120-135 degrees F)
What happens during the five minute cooldown?
Tests emergency run solenoids and pneumatic trip circuits