Session 11. Flashcards
- Water meters that have been approved in N.Y.C. can be set by:
A. A licensed engineer.
B. A licensed master plumber.
C. A master fire suspension piping contractor.
D. The owner of the building.
B. A licensed master plumber.
- On which of the following types of service is there no goos neck required:
A. Two inch in diameter or less using brass pipe.
B. Two inch in diameter or less using copper tubing.
C, Ductile iron connections.
D. One inch copper tubing water service.
C, Ductile iron connections.
3. In which of the following ways shall connections of existing lead service pipes to copper tubing or brass service pipes be made: A. Wiped joint. B. Using a compression coupling. C. Brazed joint. D. Soldered.
B. Using a compression coupling.
- Water supply openings and outlets shall be protected by atmospheric-type or pressure-type vacuum breakers. The critical level of the vacuum breaker shall be set a minimum of:
A. A minimum of 2” above the waste outlet of the fixture.
B. A minimum of 6” above the flood level of the fixture.
C. A minimum of 2” above the point where submerged outlet enters the fixture.
D. At any location in the supply line supplying the submerged outlet enters the fixture.
B. A minimum of 6” above the flood level of the fixture.
5. Which of the following factors will most likely cause a vacuum breaker to fail to operate: A. Type of water used. B. The humidity. C. Closed air ports. D. Velocity of flow.
C. Closed air ports.
6. Vacuum breakers are used for which of the following purposes: A. Shut off valve. B. To stop leaks. C. To prevent siphonage. D. To flush fixtures.
C. To prevent siphonage.
7. What test medium is not used to clean (purging) a clogged natural gas line: A. Air. B. Oxygen. C. Carbon dioxide. D. Nitrogen.
B. Oxygen.
8. In a properly installed hot water supply system, which is least likely to cause a breakage: A. Excessive pressure. B. Setting of the building. C. Expansion joint. D. Water hammer.
D. Water hammer.
- On a roof tank which of the following determines the size of the overflow:
A. 2 commercial sizes larger than the water supply to the roof tank.
B. 1/2 commercial sizes larger than the water supply to the roof tank.
C. 1 commercial sizes larger than the water supply to the roof tank.
D. PC 606.5.4, Tables 606.5.4(1) & 606.5.4(2).
D. PC 606.5.4, Tables 606.5.4(1) & 606.5.4(2).
10. Siphonic action is caused by: A. Suction. B. Balance. C. Venting. D. Atmospheric pressure.
D. Atmospheric pressure.
- List 5 locations on the drainage system where clean-outs are required:
1, 2, 3, 4, 5.
- All horizontal drains, located not more than 100 ft. apart.
- Bldg. sewers not more than 100 ft. apart measured from the upstream entrance, of the clean-out.
- Each change of direction of bldg. drain or horizontal waste or soil lines greater than 40.
- Where more than one change of direction occurs only once C.O. in one run of piping for each 40’.
- At base of sail or waste stack.
12. A city water main is installed in a street, which would be the proper depth that would be required for the water service piping: A. j4' from the building. B. 5' from the sewer line. C. 6' from the sewer line. D. No more than 6' below the ground.
D. No more than 6’ below the ground.
13. Wiped joints in soil or waste lines shall be at least ... in length: A. 1-1/4". B. 1-1/2". C. 1-3/4". D. 2".
B. 1-1/2”.
14. Wiped joints in soil or waste lines have a minimum thickness of solder at the thickest part of the joint of: A. 3/8". B. 1/2". C. 3/4". D. 2".
A. 3/8”.
15. Fixture flanges of cast brass shall be at least: A. 3/8". B. 1/2". C. 3/4". D. 7/8".
A. 3/8”.
16. Adequate means shall be provided for taking care of expansion and contraction of all vertical lines of pipe in structures and shall be used: A. Every 75 feet. B. Every 100 feet. C Only where necessary. D. Every 150 feet.
C Only where necessary.
- On the discharge of a pneumatic ejector:
A. To house side of house trap.
B. To sewer side of house trap.
C. To sewer side of house trap with back=flow valve.
D. To sewer side of house trap with gate valve.
B. To sewer side of house trap.
18. Which dial will turn most on a water meter when a water tap is turned on at the downstream side of the meter: A. 1 cu. ft. B. 10 cu. ft. C. 100 cu. ft. D. 1000 cu. ft.
A. 1 cu. ft.
19. In a garage storing inflammable gas and oils, an oil separator is required before emptying into the building drainage system or other point of disposal when there are at least: A. 4 cars. B. 3 cars. C. 2 cars. D. 1 cars.
D. 1 cars.
- Which of the following is correct for the minimum size riser on water distribution system:
A. The design of the water distribution system shall conform to accepted engineering practice.
B. Supply the fixtures with water at rates and pressure as required.
C. Methods utilized to determine pipe sizes shall be approved.
D. A, B & C.
D. A, B & C.
21. Waiver most nearly is: A. Relinquish. B. Change. C. Distribute. D. Follow up.
A. Relinquish.
- A two family house requires at least on water closet for each family.
T or F.
T.
- The free use of elevators for workers does not void the need that water closets should be one floor above or one floor below the floor that they work on.
T or F.
T.
- Flush pipes and fittings for water closets & urinals shall be of nonferrous material.
T or F.
T.
- Hopper bowls are not permitted inside structures because they prevent exposed surfaces to be thoroughly washed and are readily fouled.
T or F.
T.
- Washout bowls may be used if they have integral flushing rims.
T or F.
T.
- Fixture traps shall in any case be within … developed length of the fixture:
A. One
B. Two.
C. Three.
D. Two feet vertical from the trap weir, 30 inches horizontal.
D. Two feet vertical from the trap weir, 30 inches horizontal.
- The minimum diameter of water closet traps is:
A. 3”.
B. 2-1/2”.
C 2-3/8”.
D. Trap size shall be consistent with the fixture out.et size.
D. Trap size shall be consistent with the fixture out.et size.
29. By which of the following are taps, wet connections of other connections made to a city water main: A. Builder. B. Plumber. C. Department employees. D. Owner.
C. Department employees.
- The size of a new water meter to cover the entire premises is determined by which o the following:
A. The meter shall not be larger than the service pipe supplying the meter.
B. A meter shall be restricted to a size and type that will insure accurate registration on the basis of the water requirements of the premises.
C. For residential premises, the permit applicant shall perform a fixture count and develop a peak flow estimate using Appendix The #1 and #2. The meter shall be sized according to appendix #8.
D. A, B & C.
D. A, B & C.
31 Vacuum breakers are approved by which of the following:
A. Board of Health (BH).
B. Department of Buildings (DOB).
C. Department of Environmental Protection (DEP),
D. American Society of Sanitary Engineers (ASSE).
D. American Society of Sanitary Engineers (ASSE).
32. Approved deck mounted and integral vacuum breakers or equipment mounted vacuum breakers and faucets with integral atmospheric or spillproof vacuum breakers shall be installed in accordance with manufacturer's instructions and the requirements for labeling with the critical level not less than: A. 4 inches above the flood level. B. 3 inches above the flood level. C. 2 inches above the flood level. D. 1 inches above the flood level.
D. 1 inches above the flood level.
- Pipe required vacuum breakers shall be installed not less than:
A. 6 inches above the flood level rim of the fixture, receptor or device served.
B. 4 inches above the flood level rim of the fixture, receptor or device served.
C. 3 inches above the flood level rim of the fixture, receptor or device served.
D. 1 inches above the flood level rim of the fixture, receptor or device served.
A. 6 inches above the flood level rim of the fixture, receptor or device served.
34. All water cooled air conditioning or refrigeration systems shall be connected to a: A. Cooling tower. B. RPZ valves. C. Metered supply. D. Needle valve.
C. Metered supply.
- When the City water is piped to a water conserving device, the piping supplying such water shall discharge at least:
A. One inch above the overflow of the pan.
B. Two inches above the overflow of the pan.
C. Three inches above the overflow of the pan.
D. Four inches above the overflow of the pan.
B. Two inches above the overflow of the pan.
36. How many inches above the flow pipe in a roof tank must the ball stop inlet be: A. 2". B. 1". C. 3". D. 4".
D. 4”.
- Water recycling systems shall receive:
A. Storm water from roofs, Balconies and condensate reclamation systems.
B. Gray water discharge only of lavatories from public restrooms in commercial office buildings.
C. Treated effluent from an approved black water treatment system.
D. A, B & C.
D. A, B & C.
- The treated effluent from an approved back water treatment system to be used in a water recycling system shall be regulated by:
A. Department of Environmental Protection (D.E.P.).
B. Department ofBuildings (D.O.B.).
C. Department of Housing (D.O.H.).
D. Department of Health and Mental Hygiene (D.H.M.H.).
D. Department of Health and Mental Hygiene (D.H.M.H.).
- Recycled water shall not be utilized for:
A. Flushing water closets and urinals.
B. Cooling tower makeup.
C. Irrigation systems that are located in the same lot as the water recycling system.
D. Wash water for car washes.
D. Wash water for car washes.
40. Recycle water shall be considered: A. Non-potable. B. Potable accepted when used t wash sidewalks and streets. C. Re-usable for cleaning cars. D. A, B & C.
A. Non-potable.
Water captured for recycling purposes shall be collected in an approved reservoir constructed of durable, nonabsorbent and: A. Shall be made of plastic lined tank. B. Shall be made of non-metalic. C. Corrosion-resistant material. D. Reinforced concrete.
C. Corrosion-resistant material.
- The holding capacity of the reservoir for recycling system shall be closed and gas tight vessel and the holding capacity of the reservoir shall be a minimum of:
A. Twice the volume of water required to meet the daily flushing requirements of the fixture supplied with recycled water, but not less than 50 gallons.
B. Three tomes the volume of water required to meet the daily flushing requirements of the fixture supplied with recycled water, but not less than 100 gallons.
C. Four times the volume of water required to meet the daily flushing requirements of the fixture supplied with recycled water, but not less than 150 gallons.
D. five times the volume of water required to meet the daily flushing requirements of the fixture supplied with recycled water, but not less than 200 gallons.
A. Twice the volume of water required to meet the daily flushing requirements of the fixture supplied with recycled water, but not less than 50 gallons.
43. All water to be recycled in an approved manner when entering the reservoir shall pass through an approved filer such as a : A. Media. B. Sand. C. Diatomaceous earth filter. D. A, B & C.
D. A, B & C.
- When a recycled water system is used it must go through an appropriate filtration and disinfection process.
The recycled water shall be disinfected by an approved method that employs:
A. Ultraviolet.
B. Chlorine .
C. Iodine o ozone.
D. A, B & C.
D. A, B & C.
45. The source of makeup water for recycled water system shall be: A. Approved by D.E.P. B. Approved by D.O.B. C. Potable water. D. Approved by the F.D.
C. Potable water.
- The reservoir used to collect the recycled water shall be equipped with an overflow pipe of the same diameter as the influent pipe for the captured water. The overflow shall be connected to building house drainage system:
A. Indirectly.
B. Directly to the sanitary drainage system.
C. Indirectly through a service sink.
D. Directly to the storm drainage system.
B. Directly to the sanitary drainage system.
47. The overflow from an approved reservoir used to collect the recycled water shall be a minimum size of: A. 4". B. 5". C. 3". D. 2".
A. 4”.
- The venting for a reservoir shall:
A. Terminate to the nearest wall.
B. Be installed according to the plumbing code of the sanitary system of chapter PC 9.
C. Be based on the size of the reservoir influent pipe.
D. B & C.
D. B & C.
- The recycled water need to be identified by its appearance using a color:
A. Dyed blue with a food grade vegetable dye before such water is supplied to the fixtures.
B. Dyed green with a food grade vegetable dye before such water is supplied to the fixtures.
C. Dyed yellow with a food grade vegetable dye before such water is supplied to the fixtures.
D. A & B.
D. A & B.
- In residential occupancies, hot water (greater than 110F shall be supplied to all plumbing fixtures and equipment utilized for bathing, washing, culinary purposes, cleansing, laundry or building maintenance.
In nonresidential occupancies, hot water 9greater than 110F shall be supplied to all plumbing fixtures and equipment utilized for culinary purposes, cleansing, laundry or building maintenance.
In nonresidential occupancies, hot water (greater than 110F) or tempered water (temperature range between 85F and 110F shall be supplied for bathing and washing purposes.
Tempered water (85F to 110F) shall be delivered for accessible hand-washing facilities. With the information given above it can be said that:
A. There is a difference in the regulations for delivering hot and tempered water to residential and nonresidential occupancies.
B. In residential occupancies hot water is required for all plumbing fixtures.
C. In nonresidential occupancies the owner or lessee may provide water temperature no greater than 85F for bathing and washing facilities.
D. A, B & C.
D. A, B & C.
- In order to prevent back siphonage in a flushometer valve water closet, the piping thereto shall be:
A. Equipped with approved vacuum breaker set not less than 4” above the critical level of the flood level rim of the bowl.
B. Equipped with approved vacuum breaker set not less than 6” above the critical level of the flood level rim of the bowl.
C. Equipped with both a continuous vent approved vacuum breaker set not less than 12” above the critical level of the flood level rim of the bowl.
D. Properly vented.
B. Equipped with approved vacuum breaker set not less than 6” above the critical level of the flood level rim of the bowl.
- In a three story building, the maximum developed length of the hot water piping is 25 feet, which one of the following is correct:
A. A circulation line is not required.
B. A circulation line of the smaller riser is required.
C. A circulation line is required.
D. An expansion joint shall be installed.
C. A circulation line is required.
53. Where water meter are installed, the meter shall not be larger than: A. Tap. B. Service. C. Distribution system. D. The larges riser.
B. Service.
54. The kind of piping that has the greatest coefficient of of expansion per degree rise in temperature is: A.j Brass. B. Lead. C. Copper. D. Steel.
B. Lead.
55. The disadvantage of the use of the yellow brass pipe for hot water lines and hot water circulation lines is that the yellow brass has a tendency to become: A. Flexible. B. Soft. C. Coated. D. Fragile.
D. Fragile.
56. The minimum spacing interval for corporation stops (taps) and wet connections for both three quarter (3/4) inch and one (1) inch corporation stops (taps) shall be: A. Eighteen inches. B. Twenty-four inches. C. Thirty inches. D. Thirty-six inches.
A. Eighteen inches.
- The one location where combination stop-and-waste valves or cocks are not permitted:
A. Base of risers.
B. Accessible pit on water distribution pipe.
C. Boiler feed.
D. Outside hose outlet.
B. Accessible pit on water distribution pipe.
- The flow velocity of the water distribution system shall be controlled to reduce the possibility of water hammer. A water-hammer arresters shall be installed where quick-closing valves are utilized. Water-hammer arrestor shall be installed where quick-closing valves are utilized. Water-hammer arrester shall conform to ASSE 1010, PDI WH201 and shall be instal in accordance the:
A. Department of buildings employees inspectors.
B. Department ofEnvironmental Protection.
C. Engineer of records design and approval.
D. Manufacturer’s specifications.
D. Manufacturer’s specifications.
- House control valves, which shall be made of material similar to the corresponding service pipes, shall be … type with the exception of those between the sizes of three quarter inch and two inches, which may be … valves. The house control shall be placed in the service pipe inside the building within two feet of the building wall, and shall be located where accessible at all times. All valves shall be designed for a … minimum working pressure.
For fire sprinkler and standpipe service pipes, and for any service pipe which supplies sprinkler heads, the house control valve shall be an … valve or an … valve approved by the department of buildings. Fill in the blanks.
A. Gate, full port ball. 150 psi. OS&Y, indicating.
B. OS&Y, gate, full port ball, 150 psi, indicating.
C. Indicating., OS&Y, fate, full port ball, 150 psi.
D. 150 psi, indicating, OS&Y, gate, full port ball.
A. Gate, full port ball. 150 psi. OS&Y, indicating.
60. Four pipe lines, each made of a different metal or metal alloy are carried in series of angle iron frames. The pipe line which will have the greatest expansion per foot per degree of temperature change is made of: A. Wrought iron. B. Steel. C. Copper. D. Brass.
D. Brass.
- when recess fittings are used, the piping should ideally:
A. Butt the shoulder.
B. Come within 1/16” of butting the shoulder.
C. Come within 1/8” of butting the shoulder.
D. Come within 1/4” of butting the shoulder.
A. Butt the shoulder.
- The least likely cause of a leak in threaded pipe joint is that:
A. Not enough pipe joint compound was used.
B. The threads are not smooth enough.
C. The number of threads is not sufficient.
D. Too much pipe joint compound has been used.
D. Too much pipe joint compound has been used.
- An adequately designed air chamber is installed on the discharge side of a reciprocating pomp. With the pump in operation the probable effect of this air chamber is to:
A. Increase the capacity of the pump.
B. Decrease the head against which the pump is operating.
C. Give a more uniform and steady delivery of water from the pump.
D. Decrease the power required to operate the pump.
C. Give a more uniform and steady delivery of water from the pump.
64. Wiping solder for lead pipes usually has a melting range (pasty) range of: A. 150*F to 250*F. B. 251*F to 350*F. C. 361*F to 484*F. D. 475*F to 600*F.
C. 361F to 484F.
- If the surfaces of the working faces of soldering iron became pitted and burnt, it is a good practice to:
A. Discard the soldering iron.
B. Dip the soldering iron in nitric acid.
C. Reheat until copper oxide forms on the surface.
D. File these faces with a flat file.
D. File these faces with a flat file.
66. A problem that may exist when the water velocity through the pipes is excessive is its: A. Sweating. B. Noise. C. Expansion. D. Leaks.
B. Noise.
667. The ideal height that water in a pipe (barometric loop) cannot be siphoned is most nearly: A. 14.7 feet. B. 30 inches. C. 20.0 feet. D. 35 feet.
D. 35 feet.
- Offset swing gooseneck (brass) on service pipe shall consist of::
A. Three feet of copper tubing and four elbows.
B. Three feet of brass pipe and four elbows.
C. Three feet of ductile pipe and four elbows.
D. Four feet of brass pipe and four elbows.
B. Three feet of brass pipe and four elbows.
- The potable water supply to lawn irrigation systems shall be protected against back-flow by:
A. Atmospheric-type vacuum breaker.
B. Pressure-type vacuum breaker.
C. Reduced pressure principle back-flow preventer.
D. A, B & C.
D. A, B & C.
70. A gate valve is to be installed as a house control valve. This valve should be designed for a minimum water pressure of: A. 125 psi. B. 150 psi. C. 175 psi. D. 200 psi.
B. 150 psi.
71. Metal tags for potable water lines shall: A. Be a diameter of : B. Bear the legend: C. Have letters a height of: D. Be placed at maximum intervals of: E. Be installed at both sides of:
A. Be a diameter of : 3”.
B. Bear the legend: Safe water.
C. Have letters a height of: 1/2”.
D. Be placed at maximum intervals of: 25’.
E. Be installed at both sides of: at points where pipes pass through walls.
72. Metal tags for non-potable water lines shall: A. Be a triangle, each side: B. Bear the legend: D. Have letters a height of: E. Be installed on both sides of: F. And at all:
A. Be a triangle, each side: 4'. B. Bear the legend: Water unsafe. D. Have letters a height of: 1/2". E. Be installed on both sides of: 25'. F. And at all: above and below points where pipes pass through floors and walls.
73. Water distribution system design criteria required capacity at fixture supply outlet. The fixture using the least gallons per minute flow rate is: A. Drinking fountain. B. Flushometer tank water closet. C. Lavatory. D. Bidet.
A. Drinking fountain.
- Water distribution system design criteria required capacity at fixture supply outlet. The fixture using the most gallons per minute flow rate is:
A. Flushometer valve siphonic water closet.
B. . Flushometer valve blow out water closet.
C. Valve urinal.
D. Hose bib sill cock.
A. Flushometer valve siphonic water closet.
B. . Flushometer valve blow out water closet.
75. There are minimum required sizes of water supplies for pipes serving fixtures. What fixture required sizes of water supplies for pipes serving fixtures. What fixture required sizes of water supplies for pipes serving fixtures. What fixture requires the largest of all the supply pipes: A. Flush valve urinal. B. Flushing rim sink. C. Flush valve water closet. D. Bathtubs larger than 60"x32".
C. Flush valve water closet.
76. Assume that a three inch diameter hot water galvanized iron pipe is to be replaced with brass pipe or copper tubing. According to recommended practice, the proper size of brass or copper tubing that could be substituted for the 3 inch galvanized line is most nearly: A. The same commercial size. B. One commercial size lager. C. One commercial size smaller. D. Two commercial size smaller.
C. One commercial size smaller.
77. Of following valves and fittings, the one that offers the least resistance to the flow of water under similar conditions is: A. 45* degree standard ell. B. Gate valve. C. Standard tee, run. D. Standard tee, side outlet.
B. Gate valve.
- Cutting brass pipe with a conventional tree-wheel cutter equipped with a thin blade:
A. Speed up the cutting time and increase the size of the burr.
B. Slow down the cutting time without forming a pronounced burr.
C. Speed down the cutting time and decrease the size of the burr.
D. Slow down the cutting time but form no burrs.
A. Speed up the cutting time and increase the size of the burr.
79. The piping of a newly installed drainage system shall be tested upon completion of the rough plumbing with the head of water not less than: A. 10'. B. 15'. C. 20'. D. 25'.
A. 10’.
80. The one of the following which should not be considered as a water conserving device is: A. Air conditioning. B. A water cooling tower. C. A spray pond. D. A water closet.
D. A water closet.
81. In high pressure steam heting systems, the steam pressure is greater than : A. 15 psig. B. 20 psig. C. 25 psig. D. 30 psig.
A. 15 psig.
82. Type K water service is made of: A. Cast iron. B. Copper. C. Lead. D. Galvanized steel.
B. Copper.
83. All water services shall be installed below the finished ground surface at a distance of at least: A. 2'. B. 3-1/2'. C. 5'. D. 8'.
B. 3-1/2’.
- The piping in all buildings having dual water distribution systems shall be identified by a color coding:
A. Green for potable water lines and red for non-potable water lines.
B. Green for potable water lines and yellow for non-potable water lines.
C. Yellow for potable water lines and green for non-potable water lines.
D. Yellow for potable water lines and red for non-potable water lines
B. Green for potable water lines and yellow for non-potable water lines.
85. The minimum required diameter of any soil stack extension which passes through the roof is: A. 3 in. B. 4 in. C. 5 in. D. 6 in.
B. 4 in.
86. A device used to prevent back-flow by siphonage action is called a: A. Relief valve. B. Sewage ejector. C. Foot valve. D. Vacuum breaker.
D. Vacuum breaker.
87. The maximum distance permitted between clean-outs in horizontal drainage lines is: A. 10'. B. 30'. C. 50'. D. 100'.
D. 100’.
88. A horizontal drainage pipe must have a minimum slope of 1/4 inch per foot if the pipe diameter measures: A. 2-1///2". B. 3". C. 4". D. 5".
A. 2-1///2”.
889. Curb valves shall be required on all domestic water service pipes with a diameter larger than: A. 1 in. B. 1-1/2 in. C. 2 in. D. 2-1/2 in.
C. 2 in.
90. When it is necessary to open a sidewalk in order to do plumbing work, a permit shall be obtained from the Department of: A. Water resources. B. Public works. C. Buildings. D. Transportation.
D. Transportation
91. Th e minimum number of fixture unit allowed for a bathroom group of fixtures consisting of a water closet (1.6 gpf), lavatory, bathtub or shower, including or excluding a bidet, an emergency floor drain or both. Such fixtures are located in the same room: A. 5. B. 6. C. 7. D. 8.
A. 5.
- The minimum number of plumbing fixtures required for a particular type of building occupancy depends mainly on:
A. The number of person expected to occupy the building.
B. Where the building is publicly or privately owned.
C. The load factor numbers.
D. The age group of the occupancy.
A. The number of person expected to occupy the building.
93. The waste water which would be most likely to corrode a cast iron pipe would have a PH value of: A. 3.0 B. 5.0 C. 7.0 D. 9.0
A. 3.0
- The main factor to consider in determining whether permission from a city department is required before connecting automatic power pumps directly to the street main is the:
A. Total water storage capacity in the building.
B. Total automatic pump capacity.
C. Number of persons expected to occupy the building.
D. Number of fixture units in the building.
B. Total automatic pump capacity.
45. Trap seal shall be vented so that they are at no time subject to a pressure differential of more than: A. 1 inch of water. B. 2 inches of water. C. .1 pound per square inch. D. .2 pounds per square inch.
A. 1 inch of water.
96. Machinery or equipment room floor drains that receive clear water only may be connected to a single trap where such trap is located not more than ... from the farthest drain: A. 5 feet. B. 10 feet. C. 15 feet. D. 20 feet.
C. 15 feet.
97. With the exception of commercial dishwashers or laundries, hot water may not be discharged into any part of drainage system at a temperature above: A. 150*F. B. 160*F. C. 170*F. D. 180*F.
A. 150*F.
98. ?The percentage if the total connected fixture unit flow rate that is likely to occur at any point in the drainage system is called: A. Discharge coefficient. B. Velocity coefficient. C. Load factor. D. Hydraulic factor.
C. Load factor.
99. The top edge over which water in a receptacle can overflow is called the: A. Inlet rim. B. Air-gap level. C. Drain level. D. Flood-level rim.
C. Drain level.
100. A device designed to separate and retain undesirable matter from normal waste and permit normal sewage to discharge into the disposal terminal is called: A. A catch basin. B. A dead end. C. A seepage pit. D. An interceptor.
D. An interceptor.