Sensors and Detectors Flashcards
Density input is normally used in steam flow instruments to convert __________ into __________.
A. mass flow rate; volumetric flow rate
B. volumetric flow rate; mass flow rate
C. mass flow rate; differential pressure
D. differential pressure; volumetric flow rate
volumetric flow rate; mass flow rate
If the steam pressure input to a density-compensated steam flow instrument fails high, the associated
flow rate indication will…
A. decrease, because the density input has decreased.
B. increase, because the density input has decreased.
C. decrease, because the density input has increased.
D. increase, because the density input has increased.
increase, because the density input has increased.
The density compensating input to a steam flow instrument is used to convert volumetric flow rate
into…
A. velocity flow rate.
B. gallons per minute.
C. mass flow rate.
D. differential flow rate.
mass flow rate.
If the steam pressure input to a density-compensated steam flow instrument fails low, the indicated
flow rate will…
A. increase, because the density input has increased.
B. decrease, because the density input has increased.
C. increase, because the density input has decreased.
D. decrease, because the density input has decreased.
decrease, because the density input has decreased.
A steam flow measuring instrument uses density compensation and square root extraction to convert
the differential pressure across the flow element to flow rate in lbm/hr.
The purpose of density compensation in this flow measuring instrument is to convert __________ into
__________.
A. volumetric flow rate; mass flow rate
B. steam pressure; mass flow rate
C. steam velocity; volumetric flow rate
D. differential pressure; volumetric flow rate
volumetric flow rate; mass flow rate
A main steam flow rate differential pressure detector was properly calibrated to produce a main steam
flow rate indication of 500,000 lbm/hr with the following initial input conditions:
Detector high pressure input = 1,000 psia
Detector low pressure input = 950 psia
The current detector input conditions are as follows:
Detector high pressure input = 985 psia
Detector low pressure input = 935 psia
Assume that the detector and associated circuitry do not have steam density compensation. Also,
assume that the main steam quality and volumetric flow rate do not change.
The current main steam flow rate indication is __________ 500,000 lbm/hr; and the current main
steam flow rate is __________ 500,000 lbm/hr.
A. equal to; greater than
B. less than; greater than
C. equal to; less than
D. greater than; less than
equal to; less than
A nuclear power plant is initially operating with the following main steam parameter values:
Main steam pressure = 1,000 psia
Main steam flow rate = 500,000 lbm/hr
Main steam pressure decreases and stabilizes at 950 psia.
Assume 100 percent quality saturated steam and that main steam volumetric flow rate is the same
before and after the pressure change.
Which one of the following is the approximate mass flow rate of main steam after the pressure
change?
A. 528,000 lbm/hr
B. 500,000 lbm/hr
C. 472,000 lbm/hr
D. 444,000 lbm/hr
472,000 lbm/hr
For water flowing through a venturi, there is a proportional relationship between flow rate and
differential pressure. For steam flowing through a venturi, the relationship must be modified to
account for changes in __________ as the steam flows through the venturi.
A. velocity
B. enthalpy
C. internal energy
D. specific volume
specific volume
A nuclear power plant is operating at 100 percent power with constant steam generator water levels.
Only main feedwater is entering the steam generators and only main steam is leaving the steam
generators. Both the main feedwater mass flow rate and the main steam mass flow rate instruments
use venturi flow sensing elements.
For the above conditions, the indication that most accurately reflects the mass flow rate through a
steam generator will typically be the mass flow rate indication for…
A. main feedwater, because condensation can adversely affect the characteristics of a steam flow
venturi.
B. main feedwater, because steam generator pressure changes affect the specific volume of steam
more than water.
C. main steam, because the enthalpy of high quality steam flowing through a venturi is constant,
unlike the enthalpy of water.
D. main steam, because a given mass flow rate of steam through a venturi develops a larger pressure
change than the same mass flow rate of water.
main feedwater, because steam generator pressure changes affect the specific volume of steam
more than water.
The most probable cause for fluctuating indication from a liquid flow rate differential pressure
detector is…
A. gas or steam being trapped in the liquid.
B. unequal temperature gradients in the liquid.
C. vortexing of the liquid passing through the flow device.
D. the valve on the high pressure sensing line being partially closed.
gas or steam being trapped in the liquid.
A properly calibrated differential pressure-type water flow detector is located several feet below a
horizontal pipe containing the detector’s sensing element. The detector was removed for inspection
and then reconnected to the sensing element with its low-pressure sensing line filled with air and its
high-pressure sensing line filled with water.
When the water system is operating, indicated flow rate will be…
A. zero.
B. equal to actual flow rate.
C. lower than actual flow rate.
D. higher than actual flow rate.
higher than actual flow rate.
How will flow rate indication be affected if the equalizing valve for the associated differential pressure
detector is fully opened?
A. Increase temporarily, and then return to the initial value.
B. Decrease temporarily, and then return to the initial value.
C. Increase to the maximum value.
D. Decrease to the minimum value.
Decrease to the minimum value.
A differential pressure flow detector is connected to a calibrated orifice in a cooling water system.
Which one of the following will cause indicated volumetric flow rate to be lower than actual
volumetric flow rate?
A. System pressure decreases.
B. The orifice erodes over time.
C. Debris becomes lodged in the orifice.
D. A leak develops in the low pressure sensing line.
The orifice erodes over time.
Flow rate is being measured using a differential pressure flow detector and a calibrated orifice. If
actual flow rate remains constant, which one of the following will cause indicated flow rate to be
higher than actual flow rate?
A. The flow detector equalizing valve is inadvertently opened.
B. A leak develops in the high pressure sensing line.
C. Debris becomes lodged in the orifice.
D. The orifice erodes over time.
Debris becomes lodged in the orifice.
Refer to the drawing of a pipe elbow used for flow measurement in a cooling water system (see figure
below).
A differential pressure (D/P) flow detector is connected to instrument lines A and B.
If instrument line A develops a leak, indicated flow rate will __________ due to a __________
measured D/P.
A. increase; larger
B. increase; smaller
C. decrease; larger
D. decrease; smaller
decrease; smaller
If the orifice in a differential pressure (D/P) flow sensor erodes such that the orifice opening becomes
larger, indicated flow rate will __________ due to a __________ D/P across the orifice. (Assume
actual flow rate remains the same.)
A. increase; larger
B. increase; smaller
C. decrease; larger
D. decrease; smaller
decrease; smaller
Refer to the drawing of a horizontal pipe elbow (top view) in an operating water system (see figure
below).
Three separate differential pressure flow detectors are connected to taps A, B, C, and D as follows:
Detector
Taps
X A and D
Y B and D
Z C and D
Assuming zero head loss in this section of pipe, how will the detectors be affected if tap D ruptures?
A. All detectors will fail low.
B. All detectors will fail high.
C. Two detectors will fail low and one will fail high.
D. Two detectors will fail high and one will fail low.
All detectors will fail low.
Refer to the drawing of a pipe elbow used for flow measurement in a cooling water system (see figure
below).
A differential pressure (D/P) flow detector is connected to instrument lines A and B.
If instrument line B develops a leak, indicated flow rate will __________ due to a __________
measured D/P.
A. increase; larger
B. increase; smaller
C. decrease; larger
D. decrease; smaller
increase; larger
An orifice is being used in an operating cooling water system to measure flow rate. Which one of the
following will cause the differential pressure sensed across the orifice to decrease?
A. System pressure decreases.
B. System flow rate decreases.
C. Debris becomes lodged in the orifice.
D. A leak develops in the low pressure sensing line.
System flow rate decreases.
Refer to the drawing of a horizontal pipe elbow (top view) in an operating water system (see figure
below). Three separate bellows differential pressure flow detectors are connected to taps A, B, C, and
D as follows:
Detector
Taps
X A and D
Y B and D
Z C and D
Assume that water is incompressible and there is no head loss in this section of pipe. How will the
detectors be affected if system flow rate remains the same while system pressure increases from 1000
psig to 1200 psig?
A. All detectors will indicate higher flow.
B. Only two detectors will indicate higher flow.
C. Only one detector will indicate higher flow.
D. Detector indication will not change.
Detector indication will not change.
Refer to the drawing of a horizontal pipe elbow (top view) in an operating water system (see figure
below).
Three separate bellows-type differential pressure flow detectors are connected to taps A, B, C, and D
as follows:
Detector
Taps
X A and D
Y B and D
Z C and D
Assuming zero head loss in this section of pipe, how will the detectors be affected if tap B experiences
a significant leak? (Assume water system pressure does not change.)
A. All detectors will fail low.
B. All detectors will fail high.
C. Only one detector will fail, and it will fail low.
D. Only one detector will fail, and it will fail high.
Only one detector will fail, and it will fail high.
A steam flow measuring instrument uses density compensation and square root compensation to
convert the differential pressure across a flow element to flow rate in lbm/hr.
The purpose of square root compensation in this flow measuring instrument is to convert __________
into __________.
A. volumetric flow rate; mass flow rate
B. volumetric flow rate; differential pressure
C. differential pressure; mass flow rate
D. differential pressure; volumetric flow rate
differential pressure; volumetric flow rate
Flow detectors (such as an orifice, flow nozzle, and venturi tube) measure flow rate using the principle
that the flow rate of a liquid is…
A. directly proportional to the differential pressure (D/P) squared.
B. inversely proportional to the D/P squared.
C. directly proportional to the square root of the D/P.
D. inversely proportional to the square root of the D/P.
directly proportional to the square root of the D/P.
A cooling water system is operating at steady-state conditions indicating 900 gpm with 60 psid across
the flow transmitter venturi. If cooling water flow rate is increased to 1,800 gpm, differential
pressure across the flow transmitter venturi will be approximately…
A. 85 psid.
B. 120 psid.
C. 175 psid.
D. 240 psid.
240 psid.
The flow rate of water passing through a venturi can be determined by measuring the…
A. differential pressure of the water as it passes through the venturi.
B. change in the velocity of the water as it passes through the venturi.
C. linear displacement of a metering plug installed in the throat of the venturi.
D. rotation rate of a paddle wheel-type device installed in the throat of the venturi.
differential pressure of the water as it passes through the venturi.
A cooling water system is operating at a steady-state flow rate of 700 gpm with 60 psid across the flow
transmitter venturi. If cooling water flow rate is increased to 1,000 gpm, differential pressure across
the flow transmitter venturi will be…
A. 85.7 psid.
B. 122.4 psid.
C. 171.4 psid.
D. 244.8 psid.
122.4 psid.
Refer to the drawing of a venturi flow element (see figure below) with direction of water flow
indicated by the arrow.
Where should the high pressure tap of a differential pressure flow detector be connected?
A. Point A
B. Point B
C. Point C
D. Point D
Point A
A differential pressure (D/P) detector is being used with a venturi to measure main steam flow rate.
With a steam flow rate of 5 x 10^6 lbm/hr, the measured D/P is 40 psid.
If steam flow changes such that the current D/P is 30 psid, what is the approximate current steam flow
rate? (Assume that main steam pressure at the inlet of the venturi remains constant.)
A. 2.1 x 10^6 lbm/hr
B. 3.5 x 10^6 lbm/hr
C. 3.7 x 10^6 lbm/hr
D. 4.3 x 10^6 lbm/hr
4.3 x 10^6 lbm/hr
Which one of the following flow measuring elements produces the largest unrecoverable head loss
when used in an operating fluid system?
A. Venturi
B. Flow nozzle
C. Pipe elbow
D. Orifice
Orifice
Refer to the drawing of a venturi flow element in an operating cooling water system (see figure
below).
At what point does the lowest pressure occur?
A. Point A
B. Point B
C. Point C
D. Point D
Point B
Refer to the drawing of a venturi flow element in an operating cooling water system (see figure
below).
A differential pressure detector measuring flow rate through the venturi will produce the highest flow
rate indication if its high-pressure tap is connected at point _____; and its low-pressure tap is
connected at point _____.
A. A; B
B. A; D
C. B; C
D. B; D
A; B
A cooling water system is operating at a steady-state flow rate of 500 gpm with 60 psid across the
associated venturi flow element. If cooling water flow rate increases to 1,000 gpm, the differential
pressure sensed by the venturi flow element will be approximately…
A. 85 psid.
B. 120 psid.
C. 240 psid.
D. 480 psid.
240 psid.
Refer to the drawing of a convergent-divergent venturi (see figure below). Subcooled water is
flowing through the venturi, and the pipe diameters at P1 and P2 are equal.
Compared to the conditions at the inlet of the venturi (P1), the pressure at the outlet of the venturi (P2)
is __________; and the water velocity at the outlet of the venturi is __________.
A. the same; the same
B. the same; slightly lower
C. slightly lower; the same
D. slightly lower; slightly lower
slightly lower; the same
Water is flowing through a venturi flow element. At the throat of the venturi, the __________ water
pressure and the __________ water velocity occurs.
A. highest; highest
B. lowest; lowest
C. lowest; highest
D. highest; lowest
lowest; highest
Water is flowing through each of the following devices. Which one of the devices will produce an
outlet pressure that is greater than the inlet pressure?
A. Convergent nozzle
B. Divergent nozzle
C. Orifice
D. Flow restrictor
Divergent nozzle
Refer to the drawing of a pipe elbow (top view) in an operating water system (see figure below).
At which one of the following pairs of connection points will the greatest differential pressure be
sensed? (Assume a constant pipe diameter and zero head loss in this section of pipe.)
A. Points A and B
B. Points B and C
C. Points C and D
D. Points D and A
Points B and C
A venturi is being used to measure the flow rate in a cooling water system. As the water flows from
the throat to the discharge of the venturi, water pressure will __________; and volumetric flow rate
will __________.
A. increase; remain the same
B. increase; increase
C. decrease; remain the same
D. decrease; decrease
increase; remain the same
A cooling water system is operating at a steady-state flow rate of 700 gpm with 60 psid across the
associated venturi flow element. If cooling water flow rate increases to 900 gpm, the differential
pressure sensed by the venturi flow element will be approximately…
A. 68 psid.
B. 77 psid.
C. 99 psid.
D. 127 psid.
99 psid.
A main steam flow rate measuring instrument uses a steam pressure input to produce main steam mass
flow rate indication. Assuming steam volumetric flow rate does not change, a steam pressure
decrease will cause indicated steam mass flow rate to…
A. increase, because the density of the steam has increased.
B. decrease, because the density of the steam has decreased.
C. remain the same, because steam pressure does not affect the mass flow rate of steam.
D. remain the same, because the steam pressure input compensates for changes in steam pressure.
decrease, because the density of the steam has decreased.
A differential pressure detector is being used with an orifice plate to measure water flow rate through a
pipe. When the flow detector was last calibrated, the following parameters were observed:
Upstream Pressure = 125 psig
Downstream Pressure = 116 psig
Actual Flow Rate = 100 gpm
Indicated Flow Rate = 100 gpm
Significant erosion of the orifice has occurred since the calibration such that actual flow rate through
the orifice has increased to 120 gpm while the upstream and downstream pressures have changed to
110 psig and 106 psig respectively.
What is the approximate flow rate that is currently indicated?
A. 44 gpm
B. 67 gpm
C. 81 gpm
D. 120 gpm
67 gpm
A cooling water system is operating at steady-state conditions at 900 gpm with 64 psid across the flow
transmitter venturi. Cooling water flow rate changes such that venturi differential pressure decreases
to 36 psid.
Which one of the following is the new system flow rate?
A. 506 gpm
B. 576 gpm
C. 675 gpm
D. 745 gpm
675 gpm
A differential pressure detector is being used with an orifice plate to measure water flow rate through a
pipe. When the flow detector was last calibrated, the following parameters were observed:
Upstream Pressure = 135 psig
Downstream Pressure = 120 psig
Actual Flow Rate = 100 gpm
Indicated Flow Rate = 100 gpm
Significant erosion of the orifice hole has occurred since the last calibration, such that actual flow rate
through the orifice has increased to 120 gpm while the upstream and downstream pressures have
changed to 124 psig and 109 psig respectively.
What is the currently indicated flow rate?
A. 44 gpm
B. 67 gpm
C. 100 gpm
D. 120 gpm
100 gpm
A cooling water system uses a horizontal venturi with a differential pressure flow detector to provide
flow rate indication. Water enters and leaves the venturi at 70°F, 120 psig, and 20 ft/sec. Water
velocity at the throat of the venturi is 45 ft/sec. Assume water is incompressible and the venturi
experiences no unrecoverable head loss.
What is the approximate pressure of the water at the throat of the venturi?
A. 109 psig
B. 98 psig
C. 86 psig
D. 71 psig
109 psig
A cooling water system is operating at steady-state conditions. A calibrated system flow meter
indicates 600 gpm with 50 psid across the flow element.
If cooling water flow rate increases to 900 gpm, the differential pressure sensed by the flow element
will be approximately…
A. 63 psid.
B. 75 psid.
C. 97 psid.
D. 112 psid.
112 psid.
The following is the current calibration data for an orifice plate that is being used for water flow rate
measurement:
Upstream Pressure = 135 psig
Downstream Pressure = 120 psig
Flow Rate = 100 gpm
During a surveillance, the following pressures are observed across the orifice plate:
Upstream Pressure = 124 psig
Downstream Pressure = 117 psig
What is the approximate water flow rate through the orifice plate?
A. 47 gpm
B. 57 gpm
C. 68 gpm
D. 78 gpm
68 gpm
Refer to the drawing of a differential pressure manometer (see figure below).
The manometer is filled with water and installed across an orifice in a ventilation duct to determine the
rate of air flow. The manometer is currently indicating a water level difference of 16 inches at an air
flow rate of 300 ft^3
/min.
Which one of the following will be the approximate rate of air flow when the manometer indicates a
water level difference of 4 inches?
A. 75 ft^3
/min.
B. 125 ft^3
/min.
C. 150 ft^3
/min.
D. 175 ft^3
/min.
150 ft^3
/min.
A differential pressure detector is being used with an orifice plate to measure water flow rate through a
pipe. When the flow instrument was last calibrated, the following parameters were observed:
Upstream Pressure = 125 psig Actual Flow Rate = 100 gpm
Downstream Pressure = 116 psig Indicated Flow Rate= 100 gpm
Since the calibration, debris has collected in the orifice such that the actual flow rate through the
orifice has decreased to 80 gpm while the upstream and downstream pressures have changed to 135
psig and 110 psig, respectively.
What is the approximate flow rate that is currently indicated by the flow instrument?
A. 125 gpm
B. 133 gpm
C. 156 gpm
D. 167 gpm
167 gpm
Refer to the drawing of a differential pressure manometer (see figure below).
The manometer is filled with water and installed across an orifice in a ventilation duct to determine the
rate of air flow. The manometer is currently indicating a water level difference of 8 inches at an air
flow rate of 300 cubic feet per minute (ft^3
/min).
Which one of the following will be the approximate air flow rate when the manometer indicates a
water level difference of 4 inches?
A. 75 ft^3
/min
B. 150 ft^3
/min
C. 188 ft^3
/min
D. 212 ft^3
/min
212 ft^3
/min
A cooling water system uses a horizontal venturi with a differential pressure flow detector to provide
flow rate indication. Water enters and leaves the venturi at 70°F, 100 psig, and 24 ft/sec. Water
velocity at the throat of the venturi is 50 ft/sec. Assume water is incompressible and the venturi
experiences no unrecoverable head loss.
What is the approximate pressure of the water at the throat of the venturi?
A. 98 psig
B. 94 psig
C. 87 psig
D. 74 psig
87 psig
Refer to the drawing of a frictionless venturi flow element (see figure below). Subcooled water is
flowing through the venturi with the following initial conditions:
Flow rate = 500 gpm
Tap A pressure = 40 psia
Tap B pressure = 36 psia
Flow rate increases to 1,000 gpm, which results in a tap A pressure of 68 psia. What is the new
pressure at tap B?
A. 60 psia
B. 52 psia
C. 44 psia
D. 32 psia
52 psia
Refer to the drawing of a frictionless venturi flow element (see figure below). Subcooled water is
flowing through the venturi with the following initial conditions:
Flow rate = 500 gpm
Tap A pressure = 40 psia
Tap B pressure = 36 psia
When flow rate is increased to 750 gpm, the pressure at tap A increases to 68 psia. What is the new
pressure at tap B?
A. 66 psia
B. 62 psia
C. 59 psia
D. 52 psia
59 psia
Refer to the drawing of a frictionless venturi flow element (see figure below). Subcooled water is
flowing through the venturi with the following initial conditions:
Flow rate = 500 gpm
Tap A pressure = 48 psia
Tap B pressure = 44 psia
When flow rate is increased to 900 gpm, the pressure at tap A increases to 62 psia. What is the new
pressure at tap B?
A. 46 psia
B. 49 psia
C. 55 psia
D. 60 psia
49 psia
Refer to the drawing of a water storage tank with a differential pressure (D/P) level detector (see figure
below).
The associated level instrument was calibrated with the water storage tank at 100°F. If mass in the
tank remains constant and the water temperature increases to 120°F, the indicated level will…
A. remain the same although actual level increases.
B. increase but remain less than actual level.
C. decrease in direct proportion to the temperature rise.
D. increase in direct proportion to the temperature rise.
remain the same although actual level increases.
Refer to the drawing of a pressurizer differential pressure (D/P) level detection system (see figure
below). The pressurizer level instrument was calibrated while the plant was in a cold shutdown
condition.
When the plant is returned to normal operating conditions, pressurizer level will indicate __________
than actual level because a given pressurizer level at normal operating conditions produces a
__________ D/P compared to cold shutdown conditions.
A. higher; smaller
B. higher; larger
C. lower; smaller
D. lower; larger
lower; larger
Refer to the drawing of a water storage tank with a differential pressure level detector that was recently
calibrated at a tank water temperature of 80°F (see figure below).
If the mass of the water in the tank remains the same while the tank water temperature is raised from
80°F to 150°F, the indicated level will…
A. remain equal to actual level.
B. increase, due to the expansion of the water.
C. remain the same.
D. decrease, due to the expansion of the water.
remain the same.
Refer to the drawing of a water storage tank with two tank differential pressure (D/P) level indicators
(see figure below).
Two D/P level indicators are installed on a large water storage tank. Indicator 1 was calibrated at
100°F water temperature and indicator 2 was calibrated at 200°F water temperature.
Assuming both indicators are on scale, which indicator will indicate the higher level?
A. Indicator 1 at all water temperatures
B. Indicator 2 at all water temperatures
C. Indicator 1 below 150°F, indicator 2 above 150°F
D. Indicator 2 below 150°F, indicator 1 above 150°F
Indicator 2 at all water temperatures
Refer to the drawing of a water storage tank with a differential pressure (D/P) level detection system
(see figure below).
The level detector is being used in a level control system that was calibrated to maintain tank level at
80 percent when the tank water temperature was 100°F. If tank water temperature gradually
increases and stabilizes at 150°F, the level control system will cause actual tank level to…
A. remain stable at 80 percent.
B. increase and stabilize above 80 percent.
C. oscillate and then stabilize at 80 percent.
D. decrease and stabilize below 80 percent.
increase and stabilize above 80 percent.
Refer to the drawing of a water storage tank with two tank differential pressure (D/P) level indicators
(see figure below).
Two D/P level indicators are installed on a large water storage tank. Indicator 1 was calibrated at
100°F water temperature and indicator 2 was calibrated at 200°F water temperature.
Assuming both indicators are on scale, which indicator will indicate the lower level?
A. Indicator 1 at all water temperatures
B. Indicator 2 at all water temperatures
C. Indicator 1 below 150°F, indicator 2 above 150°F
D. Indicator 2 below 150°F, indicator 1 above 150°F
Indicator 1 at all water temperatures
Refer to the drawing of a water storage tank with two differential pressure (D/P) level indicators (see
figure below).
Two D/P level indicators are installed on a large water storage tank. Indicator No. 1 was calibrated at
200°F water temperature and indicator No. 2 was calibrated at 100°F water temperature.
Assuming both indicators are on scale, which indicator will indicate the lower level?
A. Indicator 1 at all water temperatures.
B. Indicator 2 at all water temperatures.
C. Indicator 1 below 150°F, indicator 2 above 150°F.
D. Indicator 2 below 150°F, indicator 1 above 150°F.
Indicator 2 at all water temperatures.
Refer to the drawing of a water storage tank with two differential pressure (D/P) level indicators (see
figure below).
Indicator 1 was calibrated at 120°F and indicator 2 was calibrated at 180°F. If tank water temperature
is currently 150°F, then indicator…
A. 1 will read greater than indicator 2, and greater than actual level.
B. 1 will read greater than indicator 2, and less than actual level.
C. 2 will read greater than indicator 1, and greater than actual level.
D. 2 will read greater than indicator 1, and less than actual level.
2 will read greater than indicator 1, and greater than actual level.
Refer to the drawing of a water storage tank with two differential pressure (D/P) level indicators (see
figure below).
Indicator 1 was calibrated at 180°F and indicator 2 was calibrated at 120°F. If tank water temperature
is 150°F, then indicator…
A. 1 will read greater than indicator 2, and greater than actual water level.
B. 1 will read greater than indicator 2, and less than actual water level.
C. 2 will read greater than indicator 1, and greater than actual water level.
D. 2 will read greater than indicator 1, and less than actual water level.
1 will read greater than indicator 2, and greater than actual water level.
Refer to the drawing of a steam generator differential pressure (D/P) level detection system that was
calibrated at normal operating conditions (see figure below).
A reactor coolant system cooldown has decreased steam generator pressures from 900 psia to 400 psia.
Without density compensation of the level instrumentation, at the end of the cooldown the steam
generator level indication will be __________ than actual level because the density of the water in the
__________ has changed significantly.
A. higher; reference leg
B. higher; steam generator
C. lower; reference leg
D. lower; steam generator
higher; steam generator
Refer to the drawing of a steam generator (SG) differential pressure (D/P) level detection system (see
figure below) that was calibrated at the current SG pressure of 400 psia.
A reactor coolant system heatup has resulted in an increase in SG pressure from 400 psia to 900 psia
over 4 hours. The ambient air temperature surrounding the SG has remained constant.
Without density compensation of the level instrumentation, at the end of the heatup SG level
indication would indicate __________ than actual level because the density of the water in the
__________ has changed significantly.
A. higher; steam generator
B. higher; reference leg
C. lower; steam generator
D. lower; reference leg
lower; steam generator
A reactor is currently shut down with the reactor coolant system at 140°F and 150 psig. Pressurizer
level is being monitored using a differential pressure detector with a wet reference leg. The
pressurizer level instrument was calibrated at normal plant operating conditions.
The pressurizer level instrument currently indicates __________ than actual pressurizer level because,
compared to the calibration conditions, there has been a significant change in the density of the fluid in
the __________.
A. lower; reference leg
B. lower; pressurizer
C. higher; reference leg
D. higher; pressurizer
higher; pressurizer
Refer to the drawing of a pressurizer and differential pressure (D/P) level detection system that was
recently calibrated at normal operating conditions (see figure below). Assume that the associated
pressurizer level instrument does not use density compensation.
With the nuclear power plant shut down at reduced reactor coolant system temperature and pressure,
the pressurizer level instrument will indicate __________ than actual water level because the D/P
currently sensed by the D/P detector is __________ than the D/P for the same pressurizer water level
at normal operating conditions.
A. lower; smaller
B. lower; larger
C. higher; smaller
D. higher; larger
higher; smaller
Refer to the drawing of a pressurizer differential pressure (D/P) level detection system (see figure
below).
The associated pressurizer level instrument was recently calibrated with the nuclear power plant at
normal operating conditions. Assume that the level instrument does not use density compensation.
If the plant is currently shut down at reduced reactor coolant system temperature and pressure,
pressurizer water level will currently indicate __________ than actual water level because, for a given
pressurizer water level, the D/P sensed by the D/P detector is currently __________.
A. higher; smaller
B. higher; larger
C. lower; smaller
D. lower; larger
higher; smaller
Refer to the drawing of a differential pressure (D/P) level detection system for a pressurizer at normal
operating temperature and pressure (see figure below).
A nuclear power plant uses several differential pressure detectors like the one below to provide
multiple channels of pressurizer water level indication. A hot channel was calibrated when the
pressurizer was at normal operating temperature. A cold channel was calibrated when the pressurizer
was at 160°F.
How will the level indications on the two channels compare when the pressurizer is at normal
operating temperature?
A. The cold channel will indicate higher than the hot channel, due to the difference in reference leg
water density at the two calibration temperatures.
B. The cold channel will indicate lower than the hot channel, due to the difference in reference leg
water density at the two calibration temperatures.
C. The cold channel will indicate higher than the hot channel, due to the difference in pressurizer
water density at the two calibration temperatures.
D. The cold channel will indicate lower than the hot channel, due to the difference in pressurizer
water density at the two calibration temperatures.
The cold channel will indicate lower than the hot channel, due to the difference in pressurizer
water density at the two calibration temperatures.
Refer to the drawing of a pressurizer differential pressure (D/P) level detection system (see figure
below).
With the pressurizer containing saturated water and steam at 2,250 psia, pressurizer level indication is
20 feet. Assume that reference leg level and temperature do not change. Also, ignore the effect of
steam density changes on level indication.
With no change in actual pressurizer level, what will level indication be at 600 psia (saturated)?
A. 14.9 feet
B. 18.3 feet
C. 22.4 feet
D. 26.8 feet
26.8 feet
Refer to the drawing of a water storage tank with a differential pressure (D/P) level detection system
(see figure below).
If the differential pressure detector equalizing valve is opened, level indication will:
A. decrease and stabilize below actual level.
B. increase and stabilize above actual level.
C. oscillate above and below actual level.
D. remain constant at the current level.
increase and stabilize above actual level.
Refer to the drawing of a water storage tank with a differential pressure (D/P) level detector (see figure
below).
The level detector is being used in a level control system that is calibrated to maintain tank level at 75
percent at the current water temperature of 90°F. If water temperature gradually increases and
stabilizes at 120°F, the level control system will cause actual tank level to…
A. remain at 75 percent.
B. increase and stabilize above 75 percent.
C. oscillate around 75 percent.
D. decrease and stabilize below 75 percent.
increase and stabilize above 75 percent.
Refer to the drawing of a water storage tank with a differential pressure (D/P) level detection system
(see figure below).
The D/P sensed by the detector varies in the __________ direction as the temperature of the water in
the tank if the __________ of the tank water is constant. (Assume reference leg and tank water
temperatures are initially the same.)
A. same; level
B. inverse; level
C. same; mass
D. inverse; mass
same; level
Refer to the drawing of a water storage tank with a differential pressure (D/P) level detector (see figure
below).
The level detector is being used in a level control system that is calibrated to maintain tank level at 75
percent at the current water temperature of 120°F. If water temperature gradually decreases and
stabilizes at 90°F, actual tank level will…
A. remain at 75 percent.
B. increase and stabilize above 75 percent.
C. oscillate around 75 percent.
D. decrease and stabilize below 75 percent.
decrease and stabilize below 75 percent.
A cooling water system is cooling a lube oil heat exchanger. Cooling water system surge tank level is
being measured using a differential pressure level detector that has been calibrated at the current water
temperature in the tank. A leak in the heat exchanger results in lube oil collecting in the surge tank.
Assuming that the temperature of the contents in the surge tank does not change, indicated tank level
will be __________ than actual tank level because lube oil is __________ than water.
A. higher; more dense
B. higher; less dense
C. lower; more dense
D. lower; less dense
lower; less dense
Many steam generator water level instruments are designed with a condensing chamber in the
reference leg. The purpose of the condensing chamber is to…
A. maintain a constant water level in the reference leg during normal operations.
B. provide reference leg compensation for the steam generator pressure exerted on the variable leg.
C. prevent reference leg flashing during a rapid depressurization of the steam generator.
D. ensure the reference leg temperature remains close to the temperature of the variable leg.
maintain a constant water level in the reference leg during normal operations.
Refer to the drawing of a water storage tank with a differential pressure (D/P) level detection system
(see figure below).
Assume the initial temperature of the reference leg and the water in the tank is 100°F, and that
reference leg temperature does not change.
If the temperature of the water in the tank increases by 20°F, the D/P sensed by the detector will
__________ as long as the water __________ is maintained constant.
A. increase; level
B. decrease; level
C. increase; mass
D. decrease; mass
increase; level
Refer to the drawing of a water storage tank with a differential pressure (D/P) level detection system
(see figure below). Assume that the initial temperature of the reference leg and the water in the tank
are the same, and that reference leg temperature and level do not change.
The level detector is being used in a level control system (not shown) that is calibrated to maintain tank
level at 75 percent at the current tank water temperature (70°F) and pressure (5 psig).
If the tank water temperature remains constant, but the tank pressure is increased by 10 psig, the level
control system will cause actual tank level to…
A. remain at 75 percent.
B. increase and stabilize above 75 percent.
C. oscillate around 75 percent.
D. decrease and stabilize below 75 percent.
remain at 75 percent.
The downcomer region of a steam generator contains 40 feet of saturated water at 536°F. A steam
generator water level detector has a pressure tap located at the bottom of the downcomer region.
Approximately how much of the total pressure at the pressure tap is caused by the downcomer water?
A. 0.6 psi
B. 13.0 psi
C. 27.7 psi
D. 156.0 psi
13.0 psi
Refer to the drawing of a differential pressure (D/P) level detection system (see figure below) for a
pressurizer at normal operating temperature and pressure. The level detector has just been calibrated.
The high pressure side of the detector is connected to the __________; and if the equalizing valve is
opened, the indicated pressurizer level will be __________ than the actual level.
A. condensing pot; lower
B. condensing pot; higher
C. pressurizer; lower
D. pressurizer; higher
condensing pot; higher
Refer to the drawing of a water storage tank with a differential pressure (D/P) level detection system
(see figure below).
The D/P level detector was just calibrated and returned to operation with the following conditions:
* The reference leg contains 20 feet of water at 70°F.
* The tank contains 18 feet of water at 70°F.
* Tank level indication is 18 feet.
Assume the actual tank water level and the temperature of the water in the tank and reference leg do
not change. Which one of the following will be the new tank level indication if the reference leg
water level decreases to 18 feet?
A. 22 feet
B. 20 feet
C. 18 feet
D. 2 feet
20 feet
Refer to the drawing of a water storage tank with a differential pressure (D/P) level detection system
(see figure below).
The water storage tank is 40 feet tall. The level detection system is calibrated to provide a level
indication of 30 feet when the tank and reference leg levels are equal.
If the tank is completely filled with water, the tank level will indicate…
A. less than 30 feet.
B. 30 feet.
C. greater than 30 feet, but less than 40 feet.
D. 40 feet.
30 feet
Refer to the drawing of a water storage tank with a differential pressure (D/P) level detection system
(see figure below).
Assume that the initial temperature of the reference leg and the water in the tank is 100°F, and that
reference leg temperature does not change.
If the temperature of the water in the tank increases by 20°F, the D/P sensed by the detector will
__________ if the __________ of the water in the tank is constant.
A. decrease; level
B. decrease; mass
C. remain the same; level
D. remain the same; mass
remain the same; mass
Refer to the drawing of a vented water storage tank with a differential pressure (D/P) level detection
system (see figure below). The water in the tank and reference leg is at the same temperature.
The tank level indicator was just calibrated to indicate 0 percent when the tank is empty and 100
percent when the water level reaches the upper tap. The indicator’s display range is 0 percent to 120
percent. The initial water level is as indicated in the figure.
If the tank water level slowly increases and stabilizes just below the top of the tank, the level indication
will increase until…
A. the water level stabilizes, at which time the level indication will stabilize at 100 percent.
B. the water level stabilizes, at which time the level indication will stabilize at a value greater than
100 percent.
C. the water level reaches the upper tap, at which time the level indication will remain at 100 percent
as the water level continues to increase.
D. the water level reaches the upper tap, at which time the level indication will continue to increase as
the water level continues to increase.
the water level reaches the upper tap, at which time the level indication will remain at 100 percent
as the water level continues to increase.
Refer to the drawing of a water storage tank with a differential pressure (D/P) level detection system
(see figure below). The level detector has just been calibrated.
How will the indicated level be affected if condensation partially fills the normally-dry reference leg?
A. Indicated level will not be affected.
B. Indicated level will be lower than actual level.
C. Indicated level will be higher than actual level.
D. Indicated level may be higher or lower than actual level depending on the pressure in the upper
volume of the tank.
Indicated level will be lower than actual level.
Refer to the drawing of a water storage tank with a differential pressure (D/P) level detector (see figure
below).
The level instrument has just been calibrated to read actual tank water level. If the reference leg
subsequently experiences high ambient temperature, indicated level will…
A. equal the actual level.
B. read less than the actual level.
C. read greater than the actual level.
D. drift above and below the actual level.
read greater than the actual level.
Refer to the drawing of a water storage tank with two differential pressure (D/P) level indicators (see
figure below).
Indicator 1 was calibrated at 200°F and indicator 2 was calibrated at 100°F. If tank water temperature
is 150°F, then…
A. indicator 1 will read greater than indicator 2.
B. indicator 2 will read greater than indicator 1.
C. indicators 1 and 2 will read the same.
D. both indicators will be inaccurate, but it is impossible to predict which indicator will read greater.
indicator 1 will read greater than indicator 2.
Refer to the drawing of two water storage tanks with four differential pressure (D/P) level detectors
(see figure below).
The tanks are identical with equal water levels and both are pressurized to 20 psig. All detectors were
calibrated at the current water temperature and 70°F external (ambient) temperature.
Which detectors will provide the most accurate level indication following an increase in external
(ambient) temperature from 70°F to 100°F? (Assume tank contents temperatures and external
pressure do not change.)
A. 1 and 3
B. 2 and 4
C. 1 and 4
D. 2 and 3
2 and 4
Refer to the drawing of a water storage tank with a differential pressure (D/P) level detection system
(see figure below).
A calibrated D/P level detector is being used to measure level in a vented tank inside the auxiliary
building. If building pressure increases with no change in temperature, the associated level indication
will…
A. decrease, then increase and stabilize at the actual level.
B. decrease and stabilize below the actual level.
C. increase and stabilize above the actual level.
D. remain at the actual level.
remain at the actual level.