Controllers and Positioners Flashcards
The difference between the setpoint in an automatic controller and the steady-state value of the
controlled parameter is called…
A. offset.
B. gain.
C. deadband.
D. feedback.
offset
The range of values around the setpoint of a measured variable where no action occurs in an automatic
flow controller is called…
A. deviation.
B. error.
C. deadband.
D. bias.
deadband
An automatic flow controller is being used to position a valve in a cooling water system. The
controller develops a flow error signal and then increases the magnitude of the signal to drive the valve
operator.
The factor by which the magnitude of the flow error signal is increased is referred to as…
A. bias.
B. gain.
C. feedback.
D. offset.
gain
A typical flow controller uses a/an __________ method of control.
A. open-loop
B. on-off
C. closed-loop
D. external regulating
closed-loop
Which one of the following terms is used to describe the delay between a process parameter change
and the sensing of that change by the process controller?
A. Offset
B. Gain
C. Dead time
D. Time constant
Dead time
An automatic flow controller is being used to position a valve in a cooling water system. A signal
that is proportional to valve position is received by the controller. This signal is referred to as…
A. gain.
B. bias.
C. feedback.
D. error.
feedback
A flow controller has proportional, integral, and derivative control features. Which one of the
following lists the effect on the control features when the controller is switched from the automatic
mode to the manual mode?
A. Only the derivative feature will be lost.
B. Only the integral and derivative features will be lost.
C. All proportional, integral, and derivative features will be lost.
D. All control features will continue to influence the controller output.
All proportional, integral, and derivative features will be lost.
Consider a direct-acting proportional flow controller that is maintaining flow rate at a value that is
offset from the controller setpoint. If the controllers gain is increased, the controller’s offset will
__________; and the controller’s proportional band will __________.
A. decrease; decrease
B. decrease; increase
C. increase; decrease
D. increase; increase
decrease; decrease
An emergency diesel generator (DG) is operating as the only power source connected to an emergency
bus. The governor of the DG is directly sensing DG __________ and will directly adjust DG
__________ flow to maintain a relatively constant DG frequency.
A. speed; air
B. speed; fuel
C. load; air
D. load; fuel
speed; fuel
If the turbine shaft speed signal received by a typical turbine governor control system fails low during
turbine startup, the turbine governor will cause turbine speed to…
A. decrease to a minimum speed setpoint.
B. decrease until the mismatch with demanded turbine speed is nulled.
C. increase until the mismatch with demanded turbine speed is nulled.
D. increase until an upper limit is reached or the turbine trips on overspeed.
increase until an upper limit is reached or the turbine trips on overspeed.
A diesel generator (DG) is the only power source connected to an emergency bus. In this alignment,
the governor of the DG directly senses DG __________ and adjusts DG fuel flow to maintain a
relatively constant DG __________.
A. voltage; voltage
B. voltage; frequency
C. speed; voltage
D. speed; frequency
speed; frequency
If the turbine shaft speed signal received by a typical turbine governor control system fails high during
turbine startup, the turbine governor will cause turbine speed to…
A. increase until an upper limit is reached or the turbine trips on overspeed.
B. increase until the mismatch with the turbine speed demand signal is nulled.
C. decrease until a lower limit is reached or turbine steam flow is isolated.
D. decrease until the mismatch with the turbine speed demand signal is nulled.
decrease until a lower limit is reached or turbine steam flow is isolated.
Refer to the drawing of a pneumatic control system (see figure below).
An increasing steam generator (SG) water level will decrease the SG level control signal and
ultimately reduce the control air pressure applied to the feed control valve.
If the level control signal is manually increased, how will the pneumatic control system affect SG
level?
A. SG level will decrease because the valve positioner will close more, which causes the feed control
valve to close more.
B. SG level will decrease because the valve positioner will open more, which causes the feed control
valve to close more.
C. SG level will increase because the valve positioner will close more, which causes the feed control
valve to open more.
D. SG level will increase because the valve positioner will open more, which causes the feed control
valve to open more.
SG level will increase because the valve positioner will open more, which causes the feed control
valve to open more.
Refer to the drawing of a pneumatic control system (see figure below).
An increasing steam generator (SG) water level will decrease the SG level control signal and
ultimately reduce the control air pressure applied to the actuator of the feed control valve.
If the level control signal fails high, the control air pressure to the valve positioner will __________,
which will cause SG water level to __________.
A. decrease; decrease
B. decrease; increase
C. increase; decrease
D. increase; increase
increase; increase
Refer to the drawing of a water storage tank and level control system (see figure below) that have just
been returned to service following replacement of the drain valve actuator. Unfortunately, the
original direct-acting actuator was mistakenly replaced with a reverse-acting actuator.
Given:
* The drain valve will now fail open if operating air pressure is lost.
* The level control system uses a direct-acting proportional-integral level controller with a
setpoint of 15 feet.
* The level controller receives input from a direct-acting level sensor.
* The level controller is currently in manual control, with an operator maintaining the tank water
level at 14 feet.
* Tank inlet and outlet flow rates are currently equal with the drain valve 50 percent open.
If the level controller is shifted to automatic control, the tank water level will…
A. increase and stabilize at 15 feet.
B. increase and stabilize slightly higher than 15 feet.
C. decrease until the tank nearly empties.
D. increase until the tank overflows.
decrease until the tank nearly empties.
Refer to the drawing of a 30-foot water storage tank and its level control system (see figure below).
The level control system has just been returned to service following replacement of the drain valve
actuator. Unfortunately, the original direct-acting actuator was mistakenly replaced with a
reverse-acting actuator.
Given:
* The drain valve will now fail open if air pressure is lost to its actuator.
* The level control system uses a direct-acting level sensor and a direct-acting
proportional-integral level controller with a setpoint of 15 feet.
* The tank water level is stable at 16 feet with the drain valve 50 percent open.
* The level controller is in Manual control.
If the level controller is shifted to Automatic control, the tank water level will…
A. increase until the tank overflows.
B. decrease until the tank almost completely empties.
C. initially increase, and then decrease and stabilize at 15 feet.
D. initially decrease, and then increase and stabilize at 15 feet.
increase until the tank overflows.
Refer to the drawing of a water storage tank with an automatic level control system (see figure below).
The makeup valve will fail closed if its actuator loses air pressure.
Given the following possible combinations of characteristics for the level sensor and controller:
Level Sensor
Controller
- Direct-Acting Direct-Acting
- Direct-Acting Reverse-Acting
- Reverse-Acting Direct-Acting
- Reverse-Acting Reverse-Acting
Which of the above combinations will work effectively with the makeup valve in the level control
system to maintain the desired tank water level?
A. 1 only
B. 1 and 4
C. 2 only
D. 2 and 3
2 and 3
Refer to the drawing of a lube oil temperature control system (see figure below).
If the temperature transmitter fails high (high temperature output signal), the temperature controller
will position the temperature control valve more __________, causing the actual heat exchanger lube
oil outlet temperature to __________.
A. open; decrease
B. open; increase
C. closed; decrease
D. closed; increase
open; decrease
If a typical flow controller is in manual control, the output of the flow controller is determined by the…
A. operator.
B. system feedback.
C. plant computer.
D. flow error signal.
operator
Refer to the drawing of a lube oil temperature control system (see figure below).
If the temperature transmitter fails low (low temperature output signal), the temperature controller will
position the temperature control valve in the __________ direction, which causes the actual heat
exchanger lube oil outlet temperature to __________.
A. close; increase
B. close; decrease
C. open; increase
D. open; decrease
close; increase
Refer to the drawing of a lube oil temperature control system (see figure below).
Which one of the following describes the type of control used in the lube oil temperature control
system?
A. Open loop, because lube oil temperature feedback is being provided to the controller from the lube
oil temperature transmitter.
B. Open loop, because lube oil temperature is being controlled by positioning a flow control valve in
a separate system.
C. Closed loop, because lube oil temperature feedback is being provided to the controller from the
lube oil temperature transmitter.
D. Closed loop, because lube oil temperature is being controlled by positioning a flow control valve
in a separate system.
Closed loop, because lube oil temperature feedback is being provided to the controller from the
lube oil temperature transmitter.
Refer to the drawing of a lube oil temperature control system (see figure below). The temperature
control valve is currently 50 percent open.
If the cooling water inlet temperature decreases, the temperature controller will position the
temperature control valve more __________, causing cooling water differential temperature through
the heat exchanger to __________.
A. closed; increase
B. closed; decrease
C. open; increase
D. open; decrease
closed; increase
Refer to the drawing of a pressure alarm circuit (see figure below). The orientation of the bistable
symbol indicates the characteristics of the bistable, as is normal for a control circuit diagram.
The bistable turns on to actuate an alarm at a system pressure of 100 psig. The bistable has a 5 psig
deadband, or neutral zone.
If current system pressure is 90 psig, which one of the following describes the alarm circuit response
as system pressure slowly increases to 110 psig?
A. The alarm is currently actuated and will turn off at 95 psig.
B. The alarm will actuate at 100 psig and will not turn off.
C. The alarm is currently actuated and will turn off at 105 psig.
D. The alarm will actuate at 100 psig and will turn off at 105 psig.
The alarm is currently actuated and will turn off at 105 psig.
Refer to the drawing of a pressure alarm circuit (see figure below). The orientation of the bistable
symbol indicates the characteristics of the bistable, as is normal for a control circuit diagram.
The bistable turns on to actuate an alarm at a system pressure of 100 psig. The bistable has a 5 psig
deadband, or neutral zone.
If system pressure is currently 90 psig, which one of the following describes the alarm circuit response
as system pressure slowly increases to 110 psig?
A. The alarm is currently actuated and will turn off at 95 psig.
B. The alarm will actuate at 100 psig and will not turn off.
C. The alarm is currently actuated and will turn off at 105 psig.
D. The alarm will actuate at 100 psig and will turn off at 105 psig.
The alarm will actuate at 100 psig and will not turn off.
Refer to the drawing of a pressure alarm circuit (see figure below). The orientation of the bistable
symbol indicates the characteristics of the bistable, as is normal for a control circuit diagram.
The bistable turns on to actuate an alarm at a system pressure of 100 psig. The bistable has a 5 psig
deadband, or neutral zone.
If system pressure is currently 110 psig, which one of the following describes the alarm circuit
response as system pressure slowly decreases to 90 psig?
A. The alarm will actuate at 100 psig and will not turn off.
B. The alarm will actuate at 100 psig and will turn off at 95 psig.
C. The alarm is currently actuated and will not turn off.
D. The alarm is currently actuated and will turn off at 95 psig.
The alarm will actuate at 100 psig and will not turn off.
Refer to the drawing of four bistable symbols (see figure below).
A temperature controller uses a bistable that turns on to actuate a warning light when the controlled
temperature reaches a low setpoint. The warning light extinguishes immediately after the
temperature increases above the low setpoint.
Which one of the following bistable symbols indicates the characteristics of the bistable?
A. 1.
B. 2.
C. 3.
D. 4.
1
Refer to the drawing of four bistable symbols (see figure below).
A temperature controller uses a bistable that turns on to actuate a warning light when the controlled
temperature reaches a high setpoint. The bistable turns off to extinguish the warning light when the
temperature decreases to 5°F below the high setpoint.
Which one of the following bistable symbols indicates the characteristics of the bistable?
A. 1.
B. 2.
C. 3.
D. 4.
4
Refer to the drawing of a temperature alarm circuit (see figure below). The orientation of the bistable
symbol indicates the characteristics of the bistable, as is normal for a control circuit diagram.
The bistable turns on to actuate an alarm at a temperature of 130°F. The bistable has a 5°F deadband,
or neutral zone.
If the current temperature is 150°F, which one of the following describes the alarm circuit response as
temperature slowly decreases to 110°F?
A. The alarm is currently actuated and will not turn off.
B. The alarm will actuate at 130°F and will not turn off.
C. The alarm is currently actuated and will turn off at 125°F.
D. The alarm will actuate at 130°F and will turn off at 125°F.
The alarm will actuate at 130°F and will not turn off.
Refer to the drawing of a lube oil temperature control system (see figure below).
The temperature controller is a direct-acting proportional controller with a gain of 1.0. Which one of
the following describes the effect of changing the gain to 2.0?
A. Half the temperature deviation from setpoint will produce a given controller output.
B. Twice the temperature deviation from setpoint will produce a given controller output.
C. The temperature control valve will move half as far for a given change in controller output.
D. The temperature control valve will move twice as far for a given change in controller output.
Half the temperature deviation from setpoint will produce a given controller output.
A direct-acting proportional controller is being used with a direct-acting transmitter to control the
temperature of lube oil exiting a heat exchanger. The controller’s proportional band is 70°F to 120°F.
Which one of the following will be the controller’s output percentage when the measured lube oil
temperature is 83°F?
A. 13 percent
B. 26 percent
C. 37 percent
D. 74 percent
26 percent
A reverse-acting proportional controller is being used with a direct-acting transmitter to control the
temperature of lube oil exiting a heat exchanger. The controller’s proportional band is 70°F to 120°F.
Which one of the following will be the controller’s output percentage when the measured lube oil
temperature is 83°F?
A. 13 percent
B. 26 percent
C. 74 percent
D. 87 percent
74 percent
The temperature of the water in a storage tank is monitored by a bistable alarm circuit. If water
temperature decreases to 50°F, a bistable turns on to actuate an alarm indicator. As soon as the water
temperature exceeds 50°F, the bistable turns off to clear the alarm.
Which one of the following bistable symbols indicates the characteristics of the bistable used in the
alarm circuit?
A. 1.
B. 2.
C. 3.
D. 4.
1
Refer to the drawing of a lube oil temperature control system (see figure below).
The temperature controller is a direct-acting proportional controller with a gain of 1.0. Which one of
the following describes the effect of changing the gain to 2.0?
A. Increases the range of lube oil temperatures that produces a proportional controller response.
B. Increases the change in valve position resulting from a given change in lube oil temperature.
C. Increases the difference between the controller setpoint and the lube oil temperature at steady-state
conditions.
D. Increases the lube oil temperature deviation from setpoint required to produce a given controller
output.
Increases the change in valve position resulting from a given change in lube oil temperature.
Refer to the drawing of a lube oil temperature control system (see figure below).
The temperature controller is a direct-acting proportional controller. Which one of the following
describes the effect of changing the controller’s gain from 1.0 to 2.0?
A. Half the change in measured temperature will produce the same change in controller input.
B. Twice the change in measured temperature will produce the same change in controller input.
C. The temperature control valve will move half as far for the same change in controller input.
D. The temperature control valve will move twice as far for the same change in controller input.
The temperature control valve will move twice as far for the same change in controller input.
Refer to the drawing of a lube oil temperature control system (see figure below).
The temperature controller is a direct-acting proportional-integral controller with a gain of 1.0. A
step increase in lube oil temperature results in an initial controller demand for the temperature control
valve (TCV) to open an additional 10 percent. After the lube oil temperature stabilizes, the final TCV
position is 60 percent open.
If the controller’s gain was 2.0 rather than 1.0, the initial controller demand for the above temperature
transient would be for the TCV to open an additional __________ percent; and the final TCV position
would be __________ percent open.
A. 5; 60
B. 5; less than 60
C. 20; 60
D. 20; more than 60
20; 60
Refer to the drawing of a lube oil temperature control system (see figure below).
The temperature controller is a direct-acting proportional-integral controller with a gain of 1.0. All
system temperatures are initially stable.
An increase in lube oil temperature causes the controller to open the temperature control valve (TCV)
farther. What would be the effect on the TCV response if the controller gain was 2.0 rather than 1.0?
A. The final TCV position would be half as far from its initial position.
B. The final TCV position would be twice as far from its initial position.
C. The final TCV position would be the same, but the TCV initially would travel a greater distance in
response to the lube oil temperature change.
D. The final TCV position would be the same, but the TCV initially would travel a shorter distance in
response to the lube oil temperature change.
The final TCV position would be the same, but the TCV initially would travel a greater distance in
response to the lube oil temperature change
Refer to the drawing of four bistable symbols (see figure below).
A temperature controller uses a bistable that turns on to actuate a warning light when the controlled
temperature reaches a low setpoint. The bistable turns off to extinguish the warning light when the
temperature increases to 5°F above the low setpoint.
Which one of the following bistable symbols indicates the characteristics of the bistable?
A. 1.
B. 2.
C. 3.
D. 4.
2
A direct-acting proportional controller is being used with a direct-acting transmitter to control the
temperature of lube oil exiting a heat exchanger. The controller’s proportional band is 80°F to 130°F.
Which one of the following will be the controller’s output percentage when the measured lube oil
temperature is 92°F?
A. 12 percent
B. 24 percent
C. 38 percent
D. 76 percent
24 percent
Refer to the drawing of a temperature alarm circuit (see figure below). The orientation of the bistable
symbol indicates the characteristics of the bistable, as is normal for a control circuit diagram.
The bistable turns on to actuate an alarm at a temperature of 130°F. The bistable has a 5°F deadband,
or neutral zone.
If the current temperature is 150°F, which one of the following describes the alarm circuit response as
temperature slowly decreases to 110°F?
A. The alarm is currently actuated and will not turn off.
B. The alarm will actuate at 130°F and will not turn off.
C. The alarm is currently actuated and will turn off at 125°F.
D. The alarm will actuate at 130°F and will turn off at 125°F.
The alarm is currently actuated and will turn off at 125°F.
Refer to the drawing of a pressure alarm circuit (see figure below). The orientation of the bistable
symbol indicates the characteristics of the bistable, as is normal for a control circuit diagram.
The bistable turns on to actuate an alarm at a system pressure of 100 psig. The bistable has a 5 psig
deadband, or neutral zone.
If system pressure increases to 105 psig, and subsequently decreases to __________; the status of the
alarm will be __________.
A. 100 psig; off
B. 98 psig; off
C. 94 psig; on
D. 92 psig; off
92 psig; off
Refer to the drawing of a pressure alarm circuit (see figure below). The orientation of the bistable
symbol indicates the characteristics of the bistable, as is normal for a control circuit diagram.
The bistable will turn on at a system pressure of 100 psig. The bistable has a 5 psig deadband, or
neutral zone.
If system pressure is currently 98 psig, which one of the following describes the status of the alarm?
A. The alarm is not actuated.
B. The alarm is actuated and will turn off at 95 psig.
C. The alarm is actuated and will turn off at 105 psig.
D. Additional information is needed to determine the status of the alarm.
Additional information is needed to determine the status of the alarm
Refer to the drawing of a lube oil temperature control system (see figure below).
The temperature control system uses a direct-acting controller and transmitter. The temperature of
the lube oil leaving the heat exchanger is currently stable at 93F.
To be compatible with the controller, the temperature control valve must fail __________ on a loss of
control air pressure; and for the temperature control system to return the lube oil heat exchanger outlet
temperature to 93°F after a large change in lube oil heat loads, the controller must have a/an
__________ characteristic.
A. closed; integral
B. closed; derivative
C. open; integral
D. open; derivative
closed; integral
Refer to the drawing of a lube oil temperature control system (see figure below).
The temperature controller is a direct-acting proportional-only controller with a gain of 2.0. All
system temperatures are initially stable with the temperature control valve (TCV) 40 percent open.
A sudden increase in the lube oil heat load causes the controller to open the TCV farther. Eventually,
all system temperatures stabilize with the final TCV position at 50 percent open.
If the controller’s gain was 1.5 rather than 2.0 when the increase in lube oil heat load occurred, the
final TCV position would be __________; and the TCV would require __________ time to reach its
final position.
A. the same; less
B. the same; more
C. less than 50 percent open; less
D. more than 50 percent open; more
the same; more
Refer to the drawing of a lube oil temperature control system (see figure below). The temperature
control system uses a direct-acting transmitter and a direct-acting proportional controller with a 20°F
proportional band.
Given:
* The lube oil temperature controller setpoint is 90F.
* The heat exchanger lube oil outlet temperature is stable at 93F.
* The temperature control valve is 60 percent open.
If the controller’s proportional band is changed to 30°F, the heat exchanger lube oil outlet temperature
will stabilize __________ than 93°F; and the controller output needed to position the temperature
control valve to 60 percent open will be __________.
A. lower; the same
B. lower; greater
C. higher; the same
D. higher; greater
higher; the same
An air-operated valve requires 3,600 pounds-force from its diaphragm actuator for proper valve
operation. The diameter of the diaphragm is 12 inches.
Which one of the following is the minimum actuator air pressure needed for proper valve operation?
A. 32 psig
B. 47 psig
C. 81 psig
D. 96 psig
32 psig
Refer to the drawing of a lube oil temperature control system (see figure below).
The temperature control system uses a reverse-acting proportional controller and a direct-acting
transmitter. The controller’s proportional band is 80°F to 130°F.
Which one of the following will be the controller’s output percentage when the measured lube oil
temperature is 98°F?
A. 18 percent
B. 32 percent
C. 36 percent
D. 64 percent
64 percent