Section 9 - Leak Testing Flashcards
Which of the following is not a RPB (release prevention barrier)
Concrete reinforced pad
double bottom tank
Under Tank Liner (diaper)
Effective bottom side CP–
Advance leak detection systems are described in:
API 334
Tank Hydraulic Integrity is just a fancy way of saying:
The tank is not leaking
When visual inspection is performed, the inspector’s eyes should be within:
24 inches of the surface to be examined
When visual inspection is performed, the amount of light needed for general viewing should be at least
15 foot candles
When visual inspection is performed, the amount of light needed for inspecting small anomalies should be at least
50 foot candles
A tank floor is tested with a type of bubble test examination. In this test, an indicator solution is sprayed on the top-side of the floor and low pressure air is added under the floor. The air pressure for this test should not exceed:
3” of water
A tank floor is tested with another type of bubble test exam. In this test, about 6” of water is added inside the tank and low pressure air is added under the floor. The air pressure for this test should not exceeded:
9” of water
The effectiveness of a tank floor Bubble Test can be improved by:
Tapping the entire botton with an air operated hammer. AIR HAMMER
Another variation of the bubble test exam is to build a clay damn around the tank and add water under the tank. (basically a reverse hydro) The height of the water in the dam must be at least
6” above the highest point in the floor.
Another method to test a tank floor is to inject an inert gas on the bottom side of the tank floor and use a gas detector on the top side. A common gas for this test is:
Helium
A special leak detection method is called volumetric technology. The key measurements in this technology are:
Liquid Level and Temperature
Another special leak detection method is called Mass Balancing Technology. The key measurements in this are:
Pressure and Temperature
Another leak detection method is called the Chemical Marker Technology. Which of the following best describe this method?
Chemical is added to either the hydrotest water, or the tank’s product Detectors tubes are spaced on the bottom-side for air sampling
When the chemical marker technology is used, the typical inoculation concentration is
1 to 10 ppm