The administrative label color for common equipment ports is?
purple
What are the five areas of infrastructure covered by ANSI/TIA/EIA-606-B
horizontal cable backbone cable telecom grounding/bonding telecom space fire stopping
according to ANSI/TIA/EIA-606B all inter-building backbone cables shall be identified with the color ______ regardless of level?
Brown
The administrative label color for horizontal cables is ______
blue
What standard specifies the administrative requirements of the telecommunications infrastructure
ANSI/TIA/EIA-606-B
The administrative label color for first-level backbone cables is?
White
according to ANSI/TIA/EIA-606-B what is needed for plywood in the DR?
A/C rated plywood
two coats fire rated paint
one wall minimum covered
mounted with galvanized, stainless steal, or zinc coated fasteners
What telecom standard describes the record keeping requirements
ANSI/TIA/EIA-606-B
two identical patch panels installed in two identical racks in two different DR’s must have unique _____.
identifiers
the color coding of termination hardware label is based on the hierarchical star configuration for backbone cabling as specified in ______ standard.
ANSI/TIA/EIA-568-B
The administrative label color for second-level backbone cables is?
Grey
each end of a horizontal cable shall be labeled within ______ of each end of the cable jacket
12 inches
the color coding of termination hardware label is based on the _______ for backbone cabling as specified in ANSI/TIA/EIA-568-B standard.
hierarchical star configuration
it is recommended that cable identifications be marked with _______
Labels
a cable shall be ________ on each end with a ________ or ________
a cable shall be marked on each end with a unique identifier or label
What is the correct label used on horizontal cables between a DR and a WA
machine printed label applied to cable
how are backbone cables labeled
an ID containing both DR numbers and a cable alpha numeric ID
How are horizontal cables labeled
each 4 pair cable
ANSI/TIA/EIA class 4
multiple sites separated by a distance
ANSI/TIA/EIA Class 1
Single building single ER no DR’s
ANSI/TIA/EIA Class 3
campus with more than one building
ANSI/TIA/EIA Class 2
single building with one ER and one or more DR’s
What is the minimum number of telecom Racks that must be installed in a DR before an identifier is required
one